Mechanical Data
±
Condensers
CR12
CR16
CR22
CR26
CR30
Total Heat of Rejection CR
(1)
kW
14.1
18.6
24.6
30.7
31.3
Dimensions - Horizontal
(2)
H x W x L
mm
972 x 1000 x 907
972 x 1000 x 907
1167 x 1000 x 1102
1167 x 1000 x 1102
1167 x 1000 x 1102
Dimensions
±
Vertical
(2)
H x W x L
mm
1076 x 972 x 907
1076 x 972 x 907
1090 x 1167 x 1102
1155 x 1000 x 1102
1090 x 1167 x 1102
Weight
Machine
kg
62
70
77
93
90
Construction
Material/Colour
Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)
Condenser
Air Cooled - Rifled Copper Tube/Turbulated Aluminium Fins
Dry Cooler
Air Cooled - Copper Tube/Turbulated Aluminium Fins
Total Face Area
m²
0.58
0.58
0.91
0.91
0.91
Nominal Airflow
m³/s
1.3
1.1
2.3
3.3
1.9
Discharge
-H
Horizontal or
-V
Vertical (
Please Specify at Order
)
Fan & Motor
Axial
Quantity
1
1
1
1
1
Diameter
mm
500
500
630
710
630
Maximum Speed
rpm
910
910
895
930
895
Refrigeration - CR
Single Circuit
Refrigerant Type
R410A
Holding Charge
Inert Gas
Coil Volume
l
3.0
6.0
4.7
4.7
9.3
Refrigerant Charge
(3)
kg
1.4
2.7
2.2
2.2
4.3
Dry Cooler
Internal Water Volume
L
6.6
6.6
11.9
Nominal Flowrate
l/s
0.53
0.65
0.7
Pressure Drop
kPa
11.9
17.8
20.7
Connections
Liquid Line
±
Sweat
in
5/8
5/8
5/8
5/8
3/4
Discharge Line
±
Sweat
in
5/8
5/8
5/8
5/8
3/4
OPTIONAL EXTRAS
Short Case Axial Fan
Designed to 75 Pa ESP
Dimensions - Horizontal
H x W x L
mm
972 x 1000 x 907
972 x 1000 x 907
1167 x 1000 x 1102
1167 x 1000 x 1102
1167 x 1000 x 1102
Dimensions - Vertical
H x W x L
mm
1080 x 972 x 907
1080 x 972 x 907
1130 x 1167 x 1102
1140 x 1167 x 1102
1130 x 1167 x 1102
Weight
Machine
kg
67
75
88
105
101
EC Fan
Dimensions - Horizontal
H x W x L
mm
972 x 1000 x 907
972 x 1000 x 907
1167 x 1000 x 1102
1167 x 1000 x 1102
1167 x 1000 x 1102
Dimensions - Vertical
H x W x L
mm
1065 x 972 x 907
1065 x 972 x 907
1127 x 1167 x 1102
1170 x 1167 x 1102
1127 x 1167 x 1102
Weight
Machine
kg
67
76
83
90
96
(1)
Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.
All performance data is supplied in accordance with BS EN 14511-1:2013
(2)
Overall dimensions for clearance;.
(3)
For guidance only.