Therm-X MVHRU HR95
Technical Manual
Page 46 of 59
Version 2.4, 25/09/2020
14.8.
ELECTRIC DUCT HEATERS
The
EOKO2
electric duct mounted heater is designed for heating or re-heating the supply air
in HVAC systems.
It can be used for pre-heating or re-heating air from the Therm-X
unit’s
heat recovery
device when the optional in-built heater capacity is not sufficient to achieve the required
temperature or when closer temperature control of the room is required.
The heater is manufactured of galvanized steel and open coil electric heating elements. The
electric IP rating of the cabling housing of the heater is IP 20.
The heater is supplied with fully integral control panel with 7 digit display to adjust the desired set temperature.
To detect the temperature of the air a temperature sensor for duct installation is provided with the heater.
Unit
Type
Order Reference
HR95-080-V
EOKO-250-4,5-3-D
HR95-150-V
EOKO-355-9,0-3-D
HR95-250-V
EOKO-400-9,0-3-D
HR95-350-V
EOKO-560-18,0-3-D
HR95-450-V
EOKO-560-18,0-3-D
HR95-550-V
EOKO-630-18,0-3-D
HR95-080-H
EOKO-250-4,5-3-D
HR95-150-H
EOKO-315-9,0-3-D
HR95-250-H
EOKO-400-9,0-3-D
HR95-350-H
EOKO-500-18,0-3-D
PLEASE NOTE:
-
The heater is supplied as a standalone product
-
Heater supplied loose for fitting and wiring on site by others
-
Power and control to the heater must be provided by an external source
-
The Therm-X integral control panel is capable of modulating the heater output and guarantees that it only runs
when there is airflow. It also ensures the heater is cooled down when the unit is turned off. All other emergency
and safety functions (minimum airflow, high temp limit, etc....) must be ensured by an external control system
-
A duct temperature sensor supplied with the heater must be installed downstream by others to allow the Therm-X
unit or other controller to modulate the heater
-
It is possible to control the heater from the Therm-X unit controller in certain scenarios, contact our office for more
information
-
Heater not suitable for external installation
-
For additional information please consult the
Therm-X MVHRU Accessories Technical Manual