Therm-X MVHRU HR95
Technical Manual
Page 23 of 59
Version 2.4, 25/09/2020
HR95-250-V
Air Volume
[m
3
.h
-1
]
Air Volume
[m
3
.s
-1
]
ESP
[Pa]
SFP
[W.(l.s)
-1
]
Casing Breakout @ 3m
[dB(A)]
1630
0.45
200
1.90
38
1223
0.34
200
1.69
33
815
0.23
200
1.63
30
1765
0.49
150
1.80
38
1324
0.37
150
1.50
33
883
0.25
150
1.34
28
1885
0.52
100
1.71
38
1414
0.39
100
1.31
32
943
0.26
100
1.06
26
2000
0.56
50
1.63
38
1500
0.42
50
1.13
31
1000
0.28
50
0.79
24
HR95-350-V
Air Volume
[m
3
.h
-1
]
Air Volume
[m
3
.s
-1
]
ESP
[Pa]
SFP
[W.(l.s)
-1
]
Casing Breakout @ 3m
[dB(A)]
2120
0.59
300
1.90
35
1590
0.44
300
1.84
34
1060
0.29
300
1.98
33
2745
0.76
250
1.90
37
2059
0.57
250
1.67
34
1373
0.38
250
1.61
33
3140
0.87
200
1.90
38
2355
0.65
200
1.54
35
1570
0.44
200
1.36
32
3460
0.96
150
1.90
39
2595
0.72
150
1.44
35
1730
0.48
150
1.16
32
PLEASE NOTE:
-
Performance is shown for standard configuration with G4+F7 supply and G4 extract filters, midpoint filters
-
Casing breakout at 3 meters calculated for a non-punctiform source and spherical propagation as described
in ISO 3744
-
For accurate acoustic performance data please request a detailed software selection