Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking com
bustion. Take combustion sample beyond the flue outlet
and compare to the tables below.
TABLE 16
95AF2
Model
CO
2
%
For Nat
CO
2
%
For L.P
Low Fire
High Fire
Low Fire
High Fire
045
5.6 - 6.6
7.8 - 8.8
6.6 - 7.6
9.1 - 10.1
070
5.5 - 6.5
7.3 - 8.3
6.5 - 7.5
8.6 - 9.6
090
5.9 - 6.9
7.8 - 8.8
6.9 - 7.9
9.1 - 10.1
110
6.3 - 7.3
8.2 - 9.2
7.3 - 8.3
9.5 - 10.5
The maximum carbon monoxide reading should not exceed 50 ppm.
High Altitude
NOTE
- In Canada, certification for installations at eleva
tions over 4500 feet (1372 m) is the jurisdiction of local au
thorities.
Units may be installed at altitudes up to 10,000 ft. above
sea level without manifold adjustment. Units installed at al
titude of 4501 - 10,000 feet (1373 to 3048m) may require a
pressure switch change which can be ordered separately.
Table 18 lists conversion kit and pressure switch require
ments at varying altitudes.
The combustion air pressure switch is factory-set and re
quires no adjustment.
TABLE 17
Manifold and Supply Line Pressure 0-10,000ft.
95AF2
Unit
Gas
Manifold Pressure in.wg.
Supply Line Pressure in. w.g.
Low Fire
High Fire
Min
Max
All Sizes
Natural
1.7
3.5
4.5
10.5
LP/propane
4.9
10.0
11.0
13.0
NOTE -
A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion
procedure.
TABLE 18
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
95AF2
Unit
Natural to
LP/Propane
High Altitude
Natural Burner
Orifice Kit
High Altitude
LP/Propane Burner
Orifice Kit
High Altitude Pressure Switch
0 - 7500 ft
(0 - 2286m)
7501 - 10,000 ft
(2286 - 3038m)
7501 - 10,000 ft
(2286 - 3038m)
4501 - 7500 ft
(1373 - 2286m)
7501 -10,000 ft
(2286 - 3048m)
-045
*78W93
78W37
*78W96
93W81
93W84
-070
93W80
93W85
-090
93W82
93W80
-110
93W80
93W85
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).