© STULZ S.p.A. – all rights reserved IT/10.2021/i04
WLA CompACT - TRANSLATIoN oF oRIGINAL INSTRUCTIoNS
12.7. pre-heating resistance
Installation of an armoured heating element immersed in the tank.
The option requires the installation of the “electrical level” to interrupt the functioning with lack of
water.
Power supply
230 V / ~1 / 50-60 Hz
Power
300 W
Material
AISI 321
Attack
G 1” 1/4
12.8. Under-beam kit
Installation of an electro-valve on hydraulic return in the tank.
It allows the installation of the chiller with free water level tank under application level, avoiding
the overflowing of the tank when the pump is stopped.
Power supply
230V / ~1 / 50-60 Hz
Material
Brass
Attack
G 1/2”
55