WLA08
Cooling capacity
(1)
W
3242
Sound pressure level at 1 m
(1) (2)
dB(A)
61,9
Refrigerant
R134a
N° of refrigerant circuits
1
Nominal power supply
V/-/Hz
230-1-50
230-1-60
400-3-50
460-3-60
Max power absorbed with standard pump
W
2064
2704
2074
2734
Max current absorbed with standard pump
A
11,77
13,97
9,67
10,71
Inrush current con Standard pump
(3)
A
36,71
37,80
26,71
25,80
Transport weight (no tank, no pump, no accessories)
(5)
kg
58,5
58,5
Transport weight (Tank, P3 pump, no accessories)
(5)
kg
75,4
75,4
Operating weight (Tank, P3 pump, no accessories)
(5)
kg
95,4
95,4
Height
mm
527
527
Width
mm
801
801
Depth
mm
632
632
Compressor
N°
1
1
Compressor type
rotary vane
rotary vane
Max power absorbed
kW
1,01
1,24
1,02
1,27
Max current absorbed
A
4,50
5,50
2,50
2,40
Inrush current
A
30,0
30,0
20,0
18,0
Axial fan
N°
1
1
Fan diameter
mm
250
250
Freeblowing air flow
m
3
/h
1820
1970
1820
1970
Power absorbed
W
134
164
134
164
Current absorbed
A
0,71
0,80
0,71
0,80
Evaporator
Flow rate of the fluid to be cooled
(1)
l/min
9,3
9,3
Load loss from the side of the fluid to be cooled
(1)
kPa
16,4
16,4
Flow rate of the fluid to be cooled min/max (3 ÷ 7K)
l/min
6,2 ÷ 16,5
6,2 ÷ 16,5
Flow rate of the fluid to be cooled @60Hz
l/min
10,4
10,4
Accumulation tank
Tank capacity
l
20
Standard pump
Max power absorbed
W
920
1300
920
1300
Max current absorbed
A
5,00
6,00
5,00
6,00
Max pressure head
kPa
420
600
420
600
medium / High prevalence pump
Max power absorbed
W
920
1300
920
1300
Max current absorbed
A
5,00
6,00
5,00
6,00
Max pressure head
kPa
660
860
660
860
S
tandar
d t
echnical
da
ta shee
t.
V
erify
on
m
ANU
AL
p
AR
T
2
possib
l
e modifica
tions
31