background image

18 

(V) B22 - for ACGH and ACGC 

20/28/35/45/55/75/95 

 

The combustion air is taken directly in the 
room and the evacuation of the smoke is 
made vertically through the roof.  

 

The kits KB2280 (ø80), KB22100 (ø100) 
and KB22130 (ø130) 

consists of: a T-piece 

with sealed plug (2), length  one metre (1), 
and a roof terminal (3). The kit K

B2280

 is 

delivered with a sliding moulding (7). The 
minimum height of the roof outlet must be the 
same as  the ridge of the roof.  
The kits for 20/28/35/45 provide for a 
dimension (B) of 2150 mm, dimension (C) 
125 mm. For the  55/75/95 a dimension (B) of 
2150 mm, dimension (C) 135 mm. 
It is possible to extend or deviate the roof 
outlet using accessories such as elbows and 
straight lengths of 0.5 m or 1 m shown on  
page 15.  

Provide sufficient ventilation. The 
required new air supply must be at least 
100 m

3

/h per unit heater.  

 

CAUTION : 
The section of the smoke conduits must 
be at least equal to the outlet diameter. 
Smoke evacuation can only be vertical or 
at a maximum of 45 °. The total length of 
the circuit must not exceed 8 metres, 
taking into account that an elbow of 90° or 
45 ° corresponds to a length of 1 metre. A 
double wall conduit must be provided if 
the part outside the building is over 2 
metres. 

 

5-6  Connection to outlet - B22 – for ACGC, ACGH unit heaters and ACGV destratificator 

 

(VI) B22 - for ACGV 28/35/55/75/95 

 

The combustion air is taken directly in the 
room and smoke evacuation is made 
vertically through the roof.  

 

The kits KB2280V (ø 80) and KB22130V (ø 
130) 

consists of a sealed elbow at 90° (1), a 

sealed length 0.5 m (2), a T-piece with sealed 
plug (3), two lengths of one metre (4) and a 
chimney cap (5).  The kit 

KB2280V 

is 

supplied with a sliding moulding (6). The roof 
outlet must be as a minimum the same as the 
height of the roof ridge.  
Dimension (B) of kits KB2280V and 
KB22130V is 2150 mm, dimension  (C) 630 
mm for ACG28/35V and dimension (C) 750 
mm for ACG55/75/95V. 
It is possible to extend or to deviate the roof 
outlet using accessories such as elbows and 
straight lengths of 0.5 m or 1 m shown on  
page 15.  

Provide sufficient ventilation. The 
required new air supply must be at least 
100 m

3

/h per unit heater.  

 

CAUTION : 
The section of the smoke conduits must 
be at least equal to the outlet diameter. 
The smoke evacuation can only be 
vertical or at a maximum of 45 °. The total 
length of the circuit must not exceed 8 
metres, taking into account that an elbow 
of 90° or 45 ° corresponds to a length of 1 
metre. A double wall conduit must be 
provided if the part outside the building is 
over 2 metres. 

 

VI 

(VII) C32 - for ACGV 28/35 

 

The connections for combustion air intake 
and smoke evacuation are made vertically 
through the roof at the outside of the building. 

 

The connection on the device is concentric at 
Ø 80/125. 

The kit KC3280V

 

(ø 80/125) 

consists of a 

roof terminal (1) and a condensate recoverer 
(3). 
The roof sealing must be used using 
standard flashing or special flashing 
depending on the type of roof. The sliding 
moulding (5) supplied with terminal can be 
used to cover  the flashing for perfect sealing.  
The exterior part must be at least 250 mm, 
dimension (A), the terminal provides for a 
total length of 1095 mm, dimension (B). 
It is possible to shorten, lengthen or to 
deviate the cup outlet using accessories such 
as elbows, straight lengths of 0.5 m or 1 m or 
the telescopic extensions shown on page 15. 

 

CAUTION  : 
The junction between the tubes must be 
sealed and rigid. The total length of the 
circuit must not exceed 6 metres, taking 
into account that an elbow of 90° or 45 ° 
corresponds to a length of 1 metre. In the 
case of greater lengths, please consult us. 

 

(

VIII) C32 - for ACGV 55/75/95 

 

The connections for combustion air intake 
and smoke evaculation are made vertically 
through the roof to the outside of the building.  

 

The connection on the device uses bi-tubes 
Ø130 mm. 

The kit KC32130V

 

(ø 130/200) 

consists of a 

roof terminal (1), of a condensate recoverer 
(2) and of a sealed length of 250 mm (3). 
Roof sealing is carried out using a standard 
flushing or special flashing depending on the 
type of roof. The fixed moulding mounted on 
the terminal can be used to cover the flashing 
(minimum dimension of 201 mm – maximum 
dimension of 208 mm), for perfect sealing.  
The exterior part of the terminal 955 mm 
dimension  (A), interior part 1060 mm 
dimension (B). 
It is possible to shorten, extend or to deviate 
the cup outlet using accessories such as 
elbows, straight lengths of 0.5 m or 1 m or 
telescopic extensions shown on page 15. 

 

CAUTION : 
The junction between the tubes must be 
sealed and rigid. The total length of the 
circuit must not exceed 8 metres, taking 
into account that an elbow of 90° or 45 ° 
corresponds to a length of 1 metre. In the 
case of greater lengths, please consult us. 

 

5-7 Concentric roof cup connection - C32 – for ACGV destratificator

 

VII 

VIII 

Содержание ACGC 20

Страница 1: ...1 DTC AT 13 135 FR GAZ FIRED AIR HEATERS TECHNICAL NOTICE AND INSTRUCTIONS FOR MONTAGE ACGH 16 20 28 35 45 55 75 95 ACGC 20 28 35 45 55 75 95 ACGV 26 28 36 45 55 75 95 1312BO3933...

Страница 2: ...16 20 26 28 35 36 45 55 10 3 2 Rotation console for IPN adjustable for ACGH 16 20 26 28 35 36 45 55 10 3 3 Adjustable wall mounted console for ACGH75 95 11 3 4 Adjustable wall mounted console for ACGC...

Страница 3: ...ich accompany the product at its shipment can be considered as contractual keep the instructions carefully near the device 1 1 Description of the device Operation The ACG gas unit heater is a generato...

Страница 4: ...on which is unsuitable or not in conformity with current standards Only defects in manufacture or raw materials are concerned The guarantee is limited to the replacement of parts which are found to be...

Страница 5: ...er mm 80 125 80 125 80 125 80 125 80 125 80 125 100 130 130 130 Air inlet mm 100 130 130 130 Supply voltage Electrical power VA 290 300 310 310 320 320 350 500 580 750 Weight kg 54 81 82 82 85 85 105...

Страница 6: ...V Calorific output kW 26 36 45 55 71 92 Usable power kW 23 5 32 5 40 5 50 64 4 84 Efficiency 91 91 91 91 91 91 No of fans 1 1 1 1 1 2 Rotation speed Rpm 900 900 900 1400 1400 900 Air flow at 15 C Air...

Страница 7: ...128 490 217 677 100 100 1 2 The ACGV models are retained at their upper part by four tightened M8 nuts Blowing is vertical towards the ground and the installation height must not be lower or higher th...

Страница 8: ...4 76 m3 h 5 28 m3 h 3 51 kg h 5 82 m3 h 6 43 m3 h 4 30 kg h 7 40 m3 h 8 22 m3 h 5 46 kg h Smoke diameter mm 80 125 80 125 80 125 100 130 130 Air input diameter mm 100 130 130 Supply voltage Electrical...

Страница 9: ...w pressure curves with filter consult us for this application Maximum dimension of the ACGC models and optional accessories A A1 A3 B B1 H L L1 L2 F Air AT 20 1040 750 780 480 440 460 356 381 310 80 1...

Страница 10: ...ke sure of the strength of the bracket C ACG16 H ACG20H ACG26H ACG28H ACG35H ACG36H ACG45H ACG55H Connection B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 Dim A mm 110 160 162 160 18...

Страница 11: ...CG35C ACG45C ACG55C ACG75C Connection B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 Dim A mm 115 125 115 125 115 125 125 190 135 205 135 205 Dim B mm 205 205 230 245 295 410 Dim C mm 585 585 585 585...

Страница 12: ...cs of the gas heaters ACGH ACGC 4 ELECTRICAL WIRING 4 2 Electrical schematics of centrifugal gas air heaters ACG75 Phase brown Neutral blue Earth green yellow Pilot black Phase brown Neutral blue Eart...

Страница 13: ...Inspection box MVE Smoke extractor PA Burner air pressure switch SI Ionisation sensor EA Ignition electrode MOD Gas modulating valve 2 speed option EVG Gas solenoid valve TI Isolation transformer Und...

Страница 14: ...orced ventilation and remote resetting Several models of thermostat 4 are available The use of these thermostats will provide you with supplementary functions such as remote resetting and forced venti...

Страница 15: ...EG112 Individual controller without thermostat Ambient thermostat with on off fan switch and remote resetting Clock programmable ACG gas unit heaters are equipped as standard with a receiver which ena...

Страница 16: ...h of 250 500 1000 mm 6 Concentric length of 500 1000 mm 7 Sealed elbow at 45 or 90 8 Concentric elbow at 45 or 90 9 Flat flashing 10 Tilted flashing with lead strip 4 6 9 10 5 3 Connecting to the unit...

Страница 17: ...n air inlet and smoke evacuation are vertical through the roof to the outside of the building The connection is concentric in diameter 80 125 and is connected directly onto the unit heater The KC3280...

Страница 18: ...total length of the circuit must not exceed 8 metres taking into account that an elbow of 90 or 45 corresponds to a length of 1 metre A double wall conduit must be provided if the part outside the bui...

Страница 19: ...hanging the seals Item 4 and making sure concerning sealing The injectors must be installed dry 5 Reassemble the ramp and connect the gas line to the gas valve replacing the seal make sure during asse...

Страница 20: ...lator pressure Gas ramp injectors Extractor washer Low speed High speed Low speed High speed Low speed High speed ACG16 6 mbar 9 mbar 4 x AL 1 90 40 7 mbar 12 mbar 4 x AL 1 90 40 13 mbar 25 mbar 4 x A...

Страница 21: ...delivered with the device Tighten the union onto the network before connecting it to the unit heater Check that the gas supply circuit is correctly sealed upto the gas solenoid valve see schematic 8...

Страница 22: ...22 ATE024 ATE022 ATE025 13 Inspectioni and safety box ATE318 ATE318 ATE318 ATE318 ATE318 ATE318 ATE318 14 Burner regulation airstat 65 C ATE146 ATE146 ATE146 ATE146 ATE146 ATE146 ATE146 15 Fan airstat...

Страница 23: ...and clean them Injectors Clean the gas injectors Ionisation sensor and electrodes Check their condition change them if necessary Gas filter Disassemble the dirty cartridge and clean it with compresse...

Страница 24: ...ing Check the pressure The device goes into safety position during operation red light comes on Gas supply interrupted Reset by pressing the red push button on the control box Cold air when starting I...