eLeCTRiCAL iNSTALLATiON
iNPUT POweR
CHOOSE ONLY
ONE
SOURCE OF INPUT POWER
24vAC
OPeRATiON
24 AC/DC
N/–
AC
AC
24VAC
50/60Hz
0.251A MAX.
115vAC
OPeRATiON
N
115H 230H
H
115VAC
50/60Hz
0.05A MAX.
N
24vDC
OPeRATiON
24 AC/DC
N/–
(+)
(–)
24VDC
0.100A MAX.
230vAC
OPeRATiON
N
115H 230H
230VAC
50/60Hz
0.029A MAX.
H
1
H2
wiRiNG
Conduit Knockouts:
Determine knockout size required based upon installation wiring.
TiP:
¾" knockout is typically used for power
Select knockout. To remove, eliminate the node with a pair of sidecutters or similar, place a
screwdriver at the opposite edge of the knockout from the node and tap with a hammer until the
knockout breaks out. Clean all holes before installing the proper conduit fitting.
TeRMiNAL AND POweR CONNeCTiONS
Prior to connecting input power to the duct unit, determine the correct input voltage/current
availability and ensure it is connected to the correct terminals.
With detector head removed, connect one of the appropriate dedicated power sources to the
applicable terminals (see below). Replace detector head and press and hold the cover removal
switch (COVER REMOVAL) and the unit will be energized. The green pilot LED will be illuminated,
and when pressing the test/reset button (TEST RESET), the red alarm LED will be illuminated. This
test confirms the correct basic operation of the duct smoke unit, excluding the detector head (see
functional testing).
SHUT DOWN WIRING EXAMPLE
In alarm NC and COM will open,
interrupting voltage supply to fan.
NC
COM
NO
ALARM
1
OR ALARM 2 RELAY
FAN SUPPLY SOURCE
NOTE:
CURRENTS SHOWN ARE DUCT SMOKE DETECTOR LESS ANY REMOTE ACCESSORIES
In the event of a fire alarm, certain equipment may be required to be shut down. For example, shut
down may be achieved by interrupting the fan supply source to that particular piece of equipment
when wired as indicated (shown below).
*TROUBLE CONTACTS ARE
SHOWN IN ENERGIzED
CONDITION. UNDER
NORMAL OPERATION
CONTACTS WILL BE HELD AS
SHOWN.
HvAC USe
ALARM 1
ALARM 2
TROUBLe
NC
COM NO
NC
COM NO
NC
COM
NO
NC
C
NO
NC
C
NO
NC
C
NO
FORM “C”
ALARM
FORM “C”
ALARM
FORM “C”
TROUBLE*
125VAC @ 10A
¼HP @ 125VAC (NC)
1
∕
3
HP @ 125VAC (NO)
TeRMiNAL BLOCK FeATUReS AND wiRe PReP
Each terminal features two holes: one (larger) hole for wire plus one (smaller) hole for convenient
test meter probe access (patent pending).
TEST METER
PROBE ACCESS
FOR WIRING
(14 - 24 AWG)
TeRMiNAL BLOCK
Wires should be stripped a minimum of ¼",
maximum
3
⁄
8
"
for proper connection.
¼"
3
⁄
8
"