8 – TROUBLESHOOTING (con't)
SECTION 8 – TROUBLESHOOTING
Personnel should be familiar with the operation of the VELTRON II (see Section 5) before performing any troubleshooting.
If after following the Troubleshooting steps the VELTRON II continues to operate improperly,
contact the Service Department for further assistance (see Section 10).
Problem
AUTO-purge Function is
not working.
AUTO-purge Function goes
through cycle but purge
panel does not initiate.
Alarms not working.
"CPU Activated" LED is not
flashing
"CPU Activated" LED is
flashing, display has
characters but is not
functioning.
"Unreliable" is displayed
on Line 1 of the display.
Unable to access
Operator Setup
Solution
– Verify AUTO-purge is on, interval and activation are properly set (see Section 5.11).
– Check for proper terminal strip wiring and connections (see Section 4.5).
– Verify correct wiring to purge panel (see Section 4.5).
– Check Fuse F1 (see Figure 5.2 for location).
– Verify that Alarm is ON and setpoints are set to correct value (see Section 5.13).
– Check for proper terminal strip wiring and connections (see Section 4.5).
– Replace I/O Board.
– Turn power switch OFF and back ON.
– Replace CPU Board.
– Replace CPU Board.
– Process signal is outside of –10% to +110% of the calibrated process range.
– If the password has changed from the factory default of 1,111 and forgotten,
Operator can access the Password Selection Menu by sequentially pressing
UP, DN, UP, and ESC.