Air King Qufresh F130D Скачать руководство пользователя страница 3

6727924 Rev. G 4/22

3 of 12

www.airkinglimited.com

2.  Pull the loose black, white and green wires out from the wire compartment (additional wires 

will be present). Install an approved electrical connector to the wire compartment cover (not 

included). Run a black (hot), white (neutral), and a green or bare ground wire from the supply 

through the electrical connector. Connect all wires from the supply to their corresponding 

wires within the wire compartment 

(Figure 6)

. Use approved methods for all connections.

3.  Carefully tuck wires back inside wire compartment and replace wire compartment cover 

securing with the screw that was removed earlier.

SECTION 5

Setting the Speed

1.  Remove the screws securing the access panel cover in place and open the cover to gain 

access. Locate the speed control panel inside the unit 

(Figure 7).

2. 

Determine the CFM required. The unit can be 

set from 30 CFM to 130 CFM in increments of 

10 CFM 

(Figure 8).

SECTION 6

Motorized Damper

An optional motorized damper can be connected to the unit. 

The damper is connect via a 24V transformer that plugs into the 

receptacle in the unit 

(Figure 9)

.

NOTE:

 Make sure to reference the instructions included with 

the motorized damper before installing or operating.

Operation

1. 

When installed the outlet will be energized anytime 

the unit is running. This will in turn open the damper. 

When the unit stops running, the damper will close. 

SECTION 7

Optional Air Filter

An air filter (available separately) can be added to this unit to provide additional filtration of the 

intake air. The unit will accept a 10

"

 x 10

"

 x 2

"

 filter. To install:

NOTE:

 Adding an air filter will decrease the airflow of the unit. You will need to increase the CFM 

selected in 

SECTION 5

 to account for the decreased air flow. Filters must be changed regularly. Refer 

to the filter manufacturer’s recommendations to determine how often the filter should be changed.
1. 

Remove the screws securing the access panel cover in place and open the cover to gain 

access to the controls and filter area.

2. 

Ensure the filter is facing the correct way and slide the filter into the slot in the housing. 
Make sure the filter is seated all the way to the bottom of the housing 

(Figure 10).

3. 

Close the access panel and reinstall the screw holding the access panel in place.

Figure 6

Supply from house

Black

Neutral (White)

Ground (Green or Bare)

Fa

n

Neutral (White)

Green

Black

Green

By others

Figure 7

Screw

Screw

Figure 9

Receptacle

Figure 10

Filter

Screw

Air Flow

Screw

SECTION 8

Completing the Installation

NOTE:

 When fan is mounted inline and no penetration is made into unconditioned spaces, there 

is no need to use a sealant appropriate for contact with the building materials present and for the 
temperature requirements of the installation to prevent air leakage from unconditioned spaces. 
Additional material (backing rod, ceiling material) are also not required.

NOTE:

 This unit is equipped with a wire mesh insect screen. Confirm that the screen is installed 

on the inside of the unit on the inlet ducting side.
1. 

If the screen is not in place, insert the screen into the tab at the base of the unit (make sure 

the wider side of the screen is running side to side inside the unit) 

(Figure 11).

2. 

Slide the screen to the side with the larger top tab making sure the screen fits behind the 

tab 

(Figure 11).

3. 

Slide the screen back over towards the smaller top tab making sure the screen fits behind 

the tab 

(Figure 12).

4. 

Confirm that the screen is being held in place by both top tabs 

(Figure 12).

 

5. 

Close the access panel and reinstall the screws holding the access panel in place.

6. 

Restore power and test your installation.

SECTION 9 (QFAMD only)

Using the Controller

1. 

On Mode:

 Fan will run continuously when the ON button (

) is pressed. If ambient 

temperature is lower than 34°F (2°C), the fan will stop and initiate Sampling Mode. Sampling 

Mode Cycle: stop 15 mins; run for 5 minutes to determine current air temperature. During 

Sampling Cycle, if the temperature is in the accessory heater (optional) control range, the 

heater will turn on (if it has been installed). The fan will return to continuous ventilation 

once ambient temperature rises above 34°F (2°C).

2. 

Energy Savings Mode:

 To enter the Energy Savings mode, press the Energy Savings 

button (

) until   appears on the left side of the display. Energy Savings mode 

engages the settings configured in 

SECTION 10

. When the unit is on, the display will 

show the current conditions (temperature and humidity level) as well as if it is in Energy 

Savings mode or not. Other icons/information that may be on the display include:

   

Fan icon appears when the fan is on.

   

“HI°F” appears if the intake temperature is above 150°F (65°C).

   

“Lo°F” appears if the intake temperature is below 15°F (-10°C).

   

“Lo%” appears if the intake humidity is below 10%.

3. 

Optional Heater Unit:

 An optional heater unit is available for climates that the air coming into 

the unit falls below 54°F (12°C). To install the unit, follow the directions that are included with 

that unit. The display will show a thermometer icon with either a “1”(

1

) or “1 2” (

1

2

) when 

the temperature range is at a level where the heating element would come on if present. 

Stage 1 - “1” turns on when the intake air temperature is between 39°F (4°C) and 54°F 

(12°C). Stages 1 and 2 “1 2” turn on when the intake air temperature is between 33°F (0°C) 

and 39°F (4°C).

Figure 11

Base Tab

Screen

Larger 

Top Tab

Figure 12

Screen

Smaller Top Tab

Screen

Figure 8

30

   4

0   50   60   70

   8

0   

90

   1

00  1

10  

120

  13

0

Содержание Qufresh F130D

Страница 1: ...ent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device such as a tag to the service panel WARNING TO REDUCE THE...

Страница 2: ...t routing possible for best performance and avoid installing the fan with smaller ducts than recommended Insulation around the ducts can reduce energy loss and inhibit mold growth Fans installed with...

Страница 3: ...use a sealant appropriate for contact with the building materials present and for the temperature requirements of the installation to prevent air leakage from unconditioned spaces Additional material...

Страница 4: ...tion display press and hold the SetH button for 5 seconds to switch the display position of temperature and humidity When the temperature is higher than 150 F 65 C the display will show HI F When the...

Страница 5: ...improper handling or operation shipping damage abuse misuse unauthorized repairs made or attempted This warranty does not cover shipping costs for the return of products to Air King for repair or rep...

Страница 6: ...take 5S1650002 3 1 6 Metal Collar Outlet 5S1650003 4 1 Blower Assembly 5S1650102 5 1 Wire Compartment Assembly 5S1650101 6 2 Adjustment Knobs 5S1299802 7 1 LCD Controller QFAMD 5S1650043 8 1 Insect Sc...

Страница 7: ...er l alimentation lectrique dans le panneau de distribution et verrouiller le dispositif de d connexionafind viterquel alimentationnerevienneaccidentellement Lorsque le dispositif ne peut tre verrouil...

Страница 8: ...re performance et vitez d installer le ventilateur avec des conduits plus petits que recommand L isolation autour des conduits peut r duire la perte d nergie et emp cher le d veloppement de moisissure...

Страница 9: ...opri pour le contact avec les mat riaux de construction pr sents et pour les exigences de temp rature de l installation Des mat riaux suppl mentaires tige de support mat riau de plafond ne sont pas no...

Страница 10: ...t Lorsque la temp rature est sup rieure 65 C 150 F l cran affichera HI F Lorsque la temp rature est inf rieure 10 C 15 F l cran affichera Lo F lorsque l humidit est inf rieure 10 l cran affichera Lo L...

Страница 11: ...arr te de fonctionner en raison d un accident d une mauvaise manipulation ou op ration de dommages d exp dition d abus de mauvaise utilisation de r paration faite ou tent es non autoris es Cette gara...

Страница 12: ...al de 6 po d admission 5S1650002 3 1 Assembl e de collier en m tal de 6 po sortie 5S1650003 4 1 Assembl e de la Soufflante 5S1650102 5 1 Assembl e du compartiment du fil 5S1650101 6 2 Boutons de r gla...

Отзывы: