Air King Qufresh F130D Скачать руководство пользователя страница 2

6727924 Rev. G 4/22

2 of 12

www.airkinglimited.com

INSTALLATION INSTRUCTIONS

CAUTION:

 

MAKE SURE POWER IS SWITCHED OFF AT SERVICE 

PANEL BEFORE STARTING INSTALLATION.

SECTION 1

Preparing the Fan

1. 

Unpack fan from the carton and confirm that all pieces are present. In addition to the fan 

you should have:

 

2 - Collar Assembly (attached) 

2 - Mounting Brackets (attached)

 

1 - Controller (attached) (QFAMD Only)  1 - Instruction/Safety Sheet

2.  Choose the location for your fan. To ensure the best air and sound performance, it is 

recommended that the length of ducting and the number of elbows be kept to a minimum, 

the radius of each elbow be as large as possible for the installation, and that insulated hard 

ducting be used. This fan will require at least 12” of clearance in the ceiling or wall. The fan 

mounts using the provided mounting brackets or can be surface mounted to a wall or ceiling.

NOTE:

 

The fan must be installed into a location that can be easily accessed once installed.

3. 

No additional vibration deadening materials are needed for this fan.

SECTION 2

Mounting the Fan

1. 

Confirm the fan is positioned so the air flow is in the correct direction.

2a. 

Surface Mounting: 

Locate at least one stud or joist. Place the fan in position so that the 

mounting bracket is centered on the stud or joist and make the location for the four (4) 

holes. Remove the fan and install properly rated wall/ceiling anchors for the holes that do 

not go directly into a joist or stud. Position fan in place and secure with screws (not 

included) 

(Figure 1).

2b. 

Mounting to a Joist:

 Install two - 2 x 4 headers (not included) between the joists. Position 

the fan housing on top of the headers and secure the mounting brackets with screws (not 

included) to the header 

(Figure 2)

.

2c. 

Hanging Bar Mounting: 

Lift unit up onto the threaded rods and secure in place using 

appropriate hardware (not included) 

(Figure 3).

Figure 1

Screws

Stud/Joist

Anchor

Air Flo

w

Figure 2

Joist

2 x 4 Header

Bracket

12"

Figure 3

Bracket

Housing

Threaded Rod

SECTION 3

Ducting

NOTE: 6” OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.

CAUTION:

 

ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL 

BUILDING CODES.

NOTE:

 The ducting from this fan to the outside of the building has a strong effect on the air 

flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible for 

best performance, and avoid installing the fan with smaller ducts than recommended. Insulation 

around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing 

ducts may not achieve their rated air flow.

WARNING:

 

MAKE SURE THE FRESH AIR INTAKE PORT COMPLIES WITH 

ALL LOCAL AND NATIONAL CODES AND IS LOCATED AT LEAST 6 FEET AWAY 

FROM SOURCES OF CONTAMINATION SUCH AS BUT NOT LIMITED TO: DRYER, 

FURNACE OR CENTRAL VACUUM EXHAUSTS, GAS APPLIANCES SUCH AS BBQ GRILLS, 

GARBAGE BINS OR OTHER EXHAUST PORTS.
NOTE: 

To ensure quiet operation of in-line and remote fans, each fan shall be installed using sound 

attenuation techniques appropriate for the installation. This can typically be achieved by installing 

insulated flexible ducting between the exhaust or supply grille(s) and the fan. 
1. 

Connect the ducting to the fan’s duct collar 

(Figure 4).

 Seal ducting to housing with 

appropriately rated tape. Use screws or suitable clamps to secure in place. Make sure the 

fresh air intake is connected to a properly installed intake port that is a suitable weather 

hood with insect screen to protect air intake. It is recommended that low restriction 

termination fittings be used.

2. 

Ensure duct joints and exterior penetrations are sealed with caulk or other similar material 

to create an air-tight path to minimize building heat loss or gain and to reduce the potential 

for condensation. Place/wrap insulation around duct and/or fan in order to minimize possible 

condensation buildup within the duct, as well as building heat loss or gain.

NOTE:

 At the base of the duct adapter, there is a small diameter test port hole covered with a 

plastic cap. Make sure the test port is not covered up with the ducting so that it can be accessed 

for pitot tube testing. To access the port, remove the port cover and insert tube.

SECTION 4

Wiring

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT SERVICE 

PANEL BEFORE STARTING INSTALLATION.

CAUTION:

 ALL ELECTRICAL CONNECTIONS MUST BE MADE 

IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL 

ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF 

INSTALLING ELECTRICAL WIRING, SECURE THE SERVICES OF A 

QUALIFIED ELECTRICIAN.

NOTE:

 This unit includes a side access panel for wiring that does not require the removal of the 

fan’s blower assembly.
1.  Remove the wire compartment cover screw and place cover in a secure place 

(Figure 5).

Figure 4

Air Flow

Intake  Ducting

Outlet  Ducting

Test Port

Figure 5

Screw

Wire 

Compartment 

Cover

Ground 

Screw

Содержание Qufresh F130D

Страница 1: ...ent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device such as a tag to the service panel WARNING TO REDUCE THE...

Страница 2: ...t routing possible for best performance and avoid installing the fan with smaller ducts than recommended Insulation around the ducts can reduce energy loss and inhibit mold growth Fans installed with...

Страница 3: ...use a sealant appropriate for contact with the building materials present and for the temperature requirements of the installation to prevent air leakage from unconditioned spaces Additional material...

Страница 4: ...tion display press and hold the SetH button for 5 seconds to switch the display position of temperature and humidity When the temperature is higher than 150 F 65 C the display will show HI F When the...

Страница 5: ...improper handling or operation shipping damage abuse misuse unauthorized repairs made or attempted This warranty does not cover shipping costs for the return of products to Air King for repair or rep...

Страница 6: ...take 5S1650002 3 1 6 Metal Collar Outlet 5S1650003 4 1 Blower Assembly 5S1650102 5 1 Wire Compartment Assembly 5S1650101 6 2 Adjustment Knobs 5S1299802 7 1 LCD Controller QFAMD 5S1650043 8 1 Insect Sc...

Страница 7: ...er l alimentation lectrique dans le panneau de distribution et verrouiller le dispositif de d connexionafind viterquel alimentationnerevienneaccidentellement Lorsque le dispositif ne peut tre verrouil...

Страница 8: ...re performance et vitez d installer le ventilateur avec des conduits plus petits que recommand L isolation autour des conduits peut r duire la perte d nergie et emp cher le d veloppement de moisissure...

Страница 9: ...opri pour le contact avec les mat riaux de construction pr sents et pour les exigences de temp rature de l installation Des mat riaux suppl mentaires tige de support mat riau de plafond ne sont pas no...

Страница 10: ...t Lorsque la temp rature est sup rieure 65 C 150 F l cran affichera HI F Lorsque la temp rature est inf rieure 10 C 15 F l cran affichera Lo F lorsque l humidit est inf rieure 10 l cran affichera Lo L...

Страница 11: ...arr te de fonctionner en raison d un accident d une mauvaise manipulation ou op ration de dommages d exp dition d abus de mauvaise utilisation de r paration faite ou tent es non autoris es Cette gara...

Страница 12: ...al de 6 po d admission 5S1650002 3 1 Assembl e de collier en m tal de 6 po sortie 5S1650003 4 1 Assembl e de la Soufflante 5S1650102 5 1 Assembl e du compartiment du fil 5S1650101 6 2 Boutons de r gla...

Отзывы: