INSTALLATION INSTRUCTIONS
CAUTION:

 

MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE 

STARTING INSTALLATION.

NOTE : 

When installing the Liner outdoors, the Air King Professional Liners are approved for 

use in 

covered

 outdoor kitchens only. Proper duct adapters, ducting, chimneys, roof/wall 

caps, etc. must be utilized as called out in the following instructions. Do not install the liner in 
an uncovered area directly exposed to the elements. 

SECTION 1

Preparing the Insert

1.  Unpack hood from the carton and confirm that all pieces are present. In addition to the 

range hood you should have:

 

 

8 -  Screws (LIN34, LIN40 models - 12; LIN46, LIN58 models - 14)

 

 

2 -  Halogen Bulbs (LIN58 models - 4)

 

 

1 -  Duct Adapter

 

 

1 -  Grease Trough

 

 

2 -  Grease Baffles (LIN24, LIN46, LIN58 models - 3)

 

 

2 -  Spacers (LIN24 models only)

 

 

1 -  Instruction/Safety Sheet   

NOTE:

 Some hoods may be shipped with a protective plastic adhered to the underside of the 

unit. It is recommended to leave this in place during installation to protect it from scratching. 
Remove when the installation is complete.

SECTION 2

Preparing the Area

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE 

STARTING INSTALLATION.

CAUTION:

 WHEN CUTTING OR DRILLING INTO WALL DO NOT DAMAGE 

ELECTRICAL WIRING AND OTHER HIDDEN UTILITIES.

1.  Cut an appropriately sized hole for the cabinet or canopy the liner will be mounted into 

(Figure 1):

 

 

LIN24M models: 

24.5" x 19.375"

  LIN24MD models: 

24.5" x 22.625"

 

 

LIN28M models: 

28.5" x 19.375"

  LIN28MD models: 

28.5" x 22.625"

 

 

LIN34M models: 

34.5" x 19.375" 

LIN34MD models: 

34.5" x 22.625"

 

 

LIN40M models: 

40.5" x 19.375" 

LIN40MD models: 

40.5" x 22.625"

 

 

LIN46MD models: 

46.5" x 22.625" 

LIN58MD models: 

58.5" x 22.625" 

NOTE:

 The hood must be mounted a minimum of 24" and a maximum of 36" from the 

cooking surface.

SECTION 3

Mounting the Liner

CAUTION:

 DUE TO THE WEIGHT AND BULK OF THE UNIT, IT IS RECOMMENDED 

THAT THREE PEOPLE ARE PRESENT DURING INSTALLATION TO LIFT, HOLD, AND SECURE 
THE UNIT IN PLACE.

1.  Lift unit up into position so that the bottom flanges are in solid contact with the bottom of 

the canopy or cabinet. Using the included wood mounting screws, secure the unit to the 
canopy or cabinet by driving the screws through the holes 

(Figure 2).

www.airkinglimited.com

6728024M Rev. D 9-12

2 of 12

NOTE:

 If additional support is required, install a 2" x .75" strip of wood between the back of 

the canopy (rear wall) and the hood. When installing the wood strip to the back of the canopy, 
locate studs in the wall to support the weight of the canopy. Center the wood strip 11.5" 
from the bottom of the canopy and attach the strip to at least two studs in the rear wall (do 
not fasten the strip to drywall only). Lift unit up into position so that the bottom flanges are in 
solid contact with the bottom of the canopy or cabinet. Using wood screws and washers (not 
included) secure the hood to the wood strip through the two keyholes in the back of the hood. 
Using the included wood mounting screws, secure the unit to the canopy or cabinet by driving 
the screws through the holes 

(Figure 3).

SECTION 4

Ducting

CAUTION:

 ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL 

BUILDING CODES.

WARNING:

 TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK.

1.  Determine the type of ducting you will require 

(Figure 4).

NOTE: 

For models using the B300, B500, and B600 blowers, a minimum of 6" diameter outlet 

adapter & ducting is required to achieve the proper air flow. The B900 requires a minimum of 8" 
diameter adapter and  ducting. The B1125 requires a minimum 10" diameter adapter and ducting. 

NOTE:

 When the duct termination is similar to that shown in 

Figure 4

 (passing through the wall 

to which the hood is mounted) the installation requires special consideration. Depending upon 
where the wall studs are located, it may be necessary to cut one or more of the wall studs and 
install a header and footer to transfer the load to the adjacent studs. Additional studs may need 
to be framed into the opening to attach dry wall or secure the hood. If this is your situation Air 
King recommends that you hire a professional and comply with all applicable codes.
2.  Install the proper sized outlet adapter to the hood by matching up the four holes on the 

flange of the adapter to the four corresponding holes on the hood and secure in place 
with the provided screws. Ensure an airtight seal around the adapter by securing all 
connections with ducting tape 

(Figure 5).

Figure 4

Wall Cap

Outlet 

Adapter

Roof Cap

Horizontal

Vertical

Figure 1

24.5"/28.5"/34.5"/ 

40.5"/ 46.5"/58.5"

19.375" 

22.625"

Figure 2

Screws

Flange

Canopy

Washer

Figure 3

Canopy

Wood 

Mounting 

Strip

OPTIONAL ADDITIONAL SUPPORT

Screws

Flange

Содержание LI34

Страница 1: ...do not damage electrical wiring and other hidden utilities WARNING TO REDUCE THE RISK OF FIRE AND TO PROPERLY EXHAUST AIR BE SURE TO DUCT AIR OUTSIDE DO NOT VENT EXHAUST AIR INTO SPACES WITHIN WALLS OR CEILINGS OR INTO ATTICS CRAWL SPACES OR GARAGES d Ducted fans must always be vented to the outdoors e This unit must be grounded f To avoid motor bearing damage and noisy and or unbalanced impellers...

Страница 2: ...mited com 6728024M Rev D 9 12 2 of 12 NOTE If additional support is required install a 2 x 75 strip of wood between the back of the canopy rear wall and the hood When installing the wood strip to the back of the canopy locate studs in the wall to support the weight of the canopy Center the wood strip 11 5 from the bottom of the canopy and attach the strip to at least two studs in the rear wall do ...

Страница 3: ...te Hot Black Figure 7 Outlet Adapter Hood Screws Flange Figure 5 Ducting 2 If the included removable grease trough is not already installed within the hood insert into the rear inside channel of the hood Make sure the taller side of the trough is facing towards the back of the hood Figure 8 3 Install the baffle filters and any spacers included with the unit by inserting the top of the filter into ...

Страница 4: ...required before a warranty claim will be accepted CUSTOMER SERVICE Toll Free 800 465 7300 Our Customer Service team is available to assist you with product questions service center locations and replacement parts They can be reached Monday through Friday 8am 4pm Eastern Please have your model number available as well as the type and style located on the label inside of your product Please do not r...

Страница 5: ...ion Replacement Part 9 2 Lamp Holder 5S1136075 10 2 45w PAR16 Bulb 5S1136099 11 2 Baffle Filter PHGB2 5S1136078 12 1 Grease Tray 5S1141370 LIN28 MODELS Qty Description Replacement Part 9 2 Lamp Holder 5S1136075 10 2 45w PAR16 Bulb 5S1136099 11 2 Baffle Filter PHGB3 5S1136079 12 1 Grease Tray 5S1136135 LIN34 MODELS Qty Description Replacement Part 9 2 Lamp Holder 5S1136075 10 2 45w PAR16 Bulb 5S113...

Страница 6: ...www airkinglimited com 6728024M Rev D 9 12 6 of 12 NOTES ...

Страница 7: ...VACUER L AIR VERS L EXTÉRIEUR NE PAS ÉVACUER L AIR DANS DES ESPACES DANS LES MURS LES PLAFONDS OU LES GRENIERS LES GALERIES TECHNIQUES OU LES GARAGES d Les ventilateurs avec conduits doivent toujours être évacués vers l extérieur e Cette unité doit être mise à la terre f Pour éviter des dommages aux roulements des moteurs et ou des hélices bruyantes ou déséquilibrées empêcher la poussière de clois...

Страница 8: ...2 8 of 12 REMARQUE Si vous avez besoin d un support additionnel installez une bande en bois de 2 po X 75 po entre le dos de l armoire mur arrière et la hotte En installant la bande en bois sur le dos de l armoire localisez les goujons dans le mur pour soutenir le poids de l armoire Centrez la bande en bois à 11 5 po du fond de l armoire et attachez la bande à au moins deux goujons dans le mur arri...

Страница 9: ...pes halogènes Utiliser des lampes PAR16 de base moyenne d un maximum de 45 watts L installer en insérant la lampe dans le réceptacle et en tournant en sens horaire jusqu à ce que la lampe soit fermement installée NE PAS serrer à outrance Connecteur à fils Figure 6 Vis Alimentation provenant de la maison Terre Vert ou nu Neutre blanc Vivant noir Figure 7 Adaptateur de sortie Hotte Vis Bride Figure ...

Страница 10: ...iode de garantie ou l exclusion ou la restriction des dommages accidentels ou indirects et par conséquent les présentes restrictions ne peuvent pas s appliquer La présente garantie vous donne des droits légaux spécifiques et peut être certains autres droits qui peuvent varier selon la province La preuve d achat est exigée avant qu une réclamation de garantie ne soit acceptée SERVICE À LA CLIENTÈLE...

Страница 11: ...N24 TOUS LES MODÈLES LIN de pièce Qté Description de remplacement 9 2 Douille 5S1136075 10 2 Lampe PAR16 de 45W 5S1136099 11 2 Filtre déflecteur PHGB2 5S1136078 12 1 Dalot à graisse 5S1141370 MODÈLES LIN28 de pièce Qté Description de remplacement 9 2 Douille 5S1136075 10 2 Lampe PAR16 de 45W 5S1136099 11 2 Filtre déflecteur PHGB3 5S1136079 12 1 Dalot à graisse 5S1136135 MODÈLES LIN34 de pièce Qté ...

Страница 12: ...www airkinglimited com 6728024M Rev D 9 12 12 of 12 REMARQUES ...

Отзывы: