INSTALLATION & MAINTENANCE INSTRUCTIONS
PREMA
CEILING VOID ENERGY RECOVERY VENTILATION UNITS
11
CTRL-DSP Display
E
DATE:
shows the current date
N
Menu scroll
LEFT
F
APPLICATION:
shows the current application
O
To go
DOWN
in menus
G
MODE:
shows auto fan [all modes except
manual] or manual position
P
To go
UP
in menus
H
TIME:
shows the time
Q
On / Off:
power the unit (hold for 5 seconds)
I
Remote Enable:
shows remote enable is
disabled
U
TIMECLOCK:
shows timeclock on / off
J
Boost:
fans run at full speed 10V
R
FAULT:
shows error alarm, refer to error codes
K
ESC key:
to exit and go back to the previous
menu
Y
BYPASS:
shows when active
L
OK key:
to enter the selected menu
X
HEATER:
shows heater output is active
M
Menu scroll
RIGHT
ERROR CODE
– see page 26
To enter the main menu press OK or ESC
To exit the main menu press ESC or wait approx. 60 seconds
Auto mode applications
Manual mode
0-10V, CO
2
and pressure
Main menu on CTRL-DSP
Installation, Operating & Maintenance
PERMA
Controls
The controller software is designed to handle Four (4) different applications.
Each application has its own set of parameters (input value range, set points, p-band, min and max
speeds, etc.) and control function. The application is preselected at factory but can be changed like the
other parameters using the CTRL-DSP.
When the device is enabled, the fan speeds are controlled by the value of the 0-10VDC CONTROL INPUT
SIGNAL, depending on the application: (e.g. CO
2
sensor, pressure control, BMS or manual)
APPLICATIONS
0-10V control
Control input signal 0-10VDC determines the fans speed 0-100% of configured max. speed.
High input signal gives high fan speed.
CO
2
control
The room’s CO
2
content (Control input signal 0-10VDC mapped to CO
2
sensor range) is controlled by a P
controller (P band). High CO
2
rate gives high fan speed.
Pressure control
Duct air pressure (Control input signal 0-10VDC mapped to pressure sensor range) is controlled by a PID
controller (Proportional, Integrating and Derivating).
High pressure value gives low fan speed
Manual fan speed control
The fan speed is set manually using the CTRL-DSP’s UP and DOWN buttons (resolution 1%).
Fixed speed
With the unit Enabled and Fixed Speed input open, fans will run at fixed speed, settable in parameter P06
CTRL-DSP display
Ⓔ
DATE
: shows the current date
Ⓝ
Menu scroll
LEFT
Ⓕ
APPLICATION
: shows the current application
Ⓞ
To go
DOWN
in menus
Ⓖ
MODE
: Shows auto fan [all modes except manual]
or manual position
Ⓟ
To go
UP
in menus
Ⓗ
TIME
: shows the time
Ⓠ
On/Off
: power the unit (Hold for 5 seconds)
Ⓘ
Remote
Enable
: shows remote enable is disabled
Ⓤ
TIMECLOCK
: shows timeclock on/off
Ⓙ
Boost:
Fans run at full speed 10V
Ⓡ
FAULT
: shows error alarm, refer to error codes
Ⓚ
ESC key: to exit and go back to the previous menu
Ⓨ
BYPASS
: Shows when active
Ⓛ
OK key: to enter the selected menu
Ⓧ
HEATER
: Shows heater output is active
Ⓜ
Menu scroll
RIGHT
ERROR CODE
– see page 20
Error code
Installation, Operating & Maintenance
PERMA
To enter the main menu press OK or ESC
To exit the main menu press ESC or wait approx. 60 seconds
Auto mode applications
Manual mode
0-10V, CO
2
, and Pressure
Main Menu on CTRL-DSP
Display Functions
Use
or
to select required menu
Press OK to enter any parameter
P02 to P04 only visible in selected applications Pressure or CO
2
P12 only visible if P11 set to “Pre” or “Post” heating type
Main Menu
Language
Date/Time
P01: Fan Application
P02: Sensor Range MIN
P03: Sensor Range MAX
P04: Setpoint
P05: PID Control
P06: Fixed speed value
P07: Run On Time (minutes)
P08: Min Fan Speed
P09: Max Fan Speed
P10: Extract Fan Speed Offset
P11: Heating Type
P12: Heating Threshold (
Only If P11 set
)
P13: Desired Temperature
P14: Max Free Heating Temperature
P15: Min Free Cooling Temperature
Weekly timer
Working Hours Counter
Save Settings
Load Settings
Restore Default Settings
Contrast
Debug Page