50
4
★
★
Frequency decreasing or prohibition of
frequency rising caused by too high compressor
discharge temperature
5
Limit to the max operating frequency caused by
too low power voltage
6
★
★
★
Operation at fixed frequency (in the case of
capability measuring or compulsory operation at
fixed frequency)
7
Protective frequency decreasing against outdoor
overload (overpower, over frequency conversion
rate, over torque, detection of DC under-voltage)
8
★
Frequency decreasing caused by indoor and
outdoor communication fault
9
★
Frequency decreasing or prohibition of
frequency rising protection against overload of
outdoor coiled pipe
10
★
Frequency decreasing or prohibition of
frequency rising for power-saving when it is
being used simultaneously with other appliances
2.Indication by the indoor unit:
2.1.
T
he 7-segment tube of the indoor display board will show the error code automatically when the
unit has the following trouble:
Error
code
Power Timer Running Sleep Remark
:★
Light o Flash x OFF
1 2 3 4
Content
Remark
The root cause is may be
one of the following
EA
the error code
will display when
the
communication
between display
board and
control board
have in trouble
a.
The connection between
the
display board and control
board is loose;
b. The indoor control board
is failure.
c. The wiring of the display
board is failure.
2.2.When the unit has the following trouble and the compressor stops running, press the sleep button on the
remote controller for 4 times in ten seconds and the 7-segment tube of the display board will show the error code
as the following, if two malfunction happened at the same time, it need press the sleep button for 4 times again,
the LED will show the other error code.
Refer to the remote controller which the sleep key can set into 4 different combination ways (Hisense's new
design remote controller), when using to check the error codes only takes effect for pressing the sleep key 10
times in ten seconds instead of 4 times.
NOTE: If the troubleshooting inquiry display by 7-segment tube, then the error code will be displayed,
otherwise only the LED of the display board can show.
Error
code
Running Timer Sleep Power Remark
:★
Light o Flash x OFF
1 2
3 4
Content Remark
The root cause is may be one
of the following
Содержание ABXCI4H4S0
Страница 15: ...15 Outdoor 1854707...
Страница 20: ...20 L1 04...
Страница 21: ...21 Function Instruction 1 Major general technical parameters...
Страница 63: ...63 3 4...
Страница 64: ...64 5...
Страница 65: ...65...
Страница 66: ...66 DC fan motor test point...
Страница 68: ...68 6 test point Check the screw of IPM fastening...
Страница 70: ...70 test point The resistance of the compressor U W V W 7 SI and N test point...