SAFETY CONSIDERATIONS 

WARNING: 

Never expose eyes or skin to UVC light from any source. 

 

Looking directly at the UVC light may cause permanent eye damage or blindness. 

 

Never operate the Air-Care UVC MAX-36 out of the plenum

.

 

 

 

Designed for a closed duct system. Do not mount near a supply or a return air opening. 

 

All  duct  openings  in  direct  line  of  site  of  the  UV  light  must  be  sealed  with  aluminum  tape  or 
equivalent sealing methods. 

 

Wear  UVC  protected  safety  glasses  during  installation.  They  will  help  block  accidental  UVC 
exposure to eyes. 

WARNING: 

UVC light will break down plastic materials not rated for UVC exposure: 

(Examples: wire insulation, flex duct, drain pans and humidifiers) 

 

The unit must be mounted at least 30” from the above stated type of materials. 

 

If  it  is  necessary  to  mount  the  unit  in  direct  line  of  site  of  these  types  of  materials,  they  must  be 
shielded with aluminum foil, aluminum foil tape, or sheet metal. 

WARNING: 

DO NOT mount this unit outdoors. 

 

This product is designed for indoor installation only (i.e. Attics, crawl spaces, basements, etc.). 

WARNING: 

Never touch broken bulb or internal contents of bulb. The bulb contains mercury. 

 

After opening the carton, unpack and inspect the unit and bulb for damage. Do not install this unit if 
any  damage  is  noticeable.  If  bulb  is  damaged,  cracked  or  broken,  do  not  touch  bulb  or  other 
contents in carton. Close carton and return to seller immediately. 

 

In case of accidental exposure to internal contents of bulb, wash hands and any other affected skin 
area  with  mild  detergent.  Remove  affected  clothing  immediately.  If  skin  surface  is  pierced,  seek 
medical attention immediately

NOTE: 

If you touch the glass of the bulb, you should wipe the glass clean with isopropyl alcohol and a lint 

free wipe. If the bulb is not cleaned, the film of hand oils causes a reduction in the light intensity. 

WARNING: 

Before installing or servicing a humidifier, air filter, heat system, or this unit, etc., always turn all 

power  OFF  and  have  unit  unplugged.  Electrical  shock  can  cause  personal  injury  or  death.  Never  expose 
eyes or skin to direct UVC light from any source. 

WARNING: 

To prevent water damage or electric shock, do not mount unit under a humidifier. 

 
 
WARNING: 

This product is designed for indoor installation only (i.e. attics, crawl spaces, basements, etc.). 

For use on gas fired, oil fired, electric and split system heat pump forced air systems*. This product is NOT 
designed to be mounted outside on gas fired or heat pump packaged units**. 
 

*Split system heat pumps are systems where the air handler and the air conditioning compressor are separate units. 
**Packaged units are systems where the air handler and the air conditioning compressor are built together and are installed outside of the building

 

 

Содержание MAX-36

Страница 1: ...of the home system and operates continuously to automatically purify the air in the home 24 hours a day This product is not sold as a medical device and is not for the purpose of diagnosis of any disease or condition nor for use in the mitigation treatment or prevention of any disease or condition READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION ITEMS INCLUD...

Страница 2: ... noticeable If bulb is damaged cracked or broken do not touch bulb or other contents in carton Close carton and return to seller immediately In case of accidental exposure to internal contents of bulb wash hands and any other affected skin area with mild detergent Remove affected clothing immediately If skin surface is pierced seek medical attention immediately NOTE If you touch the glass of the b...

Страница 3: ...ith bare hands Oils on the hands tend to shorten bulb life WARNING Never expose eyes or skin to UVC light from any source Looking directly at the UVC light may cause permanent eye damage or blindness Never operate the Air Care UVC MAX 36 out of the plenum Avoid touching the glass portion of the bulb with your hands 6 Plug the power supply cord into a standard electric wall outlet Check bulb operat...

Страница 4: ...r local disposal or recycling requirements WARNING Never touch broken bulb or internal contents of bulb The bulb contains mercury NOTE In case of accidental exposure to internal contents of bulb wash hands and any other affected skin area with mild detergent Remove affected clothing immediately If skin surface is pierced seek medical attention immediately TROUBLESHOOTING GUIDE 1 Make sure the unit...

Страница 5: ... back to the purchaser s location Any additional expedited service charges for quicker shipping shall be born by the purchaser If the product or component is not found to be a warranty issue the purchaser will be responsible for return shipping charges Air Care is not responsible or liable for indirect special or consequential damages arising out of or in connection with the use of performance of ...

Страница 6: ... 6 Air Care is a Division of D P L Enterprises Inc 3868 E Post Road Las Vegas NV 89120 702 454 5515 Fax 702 454 5225 Website www air care com E mail Info Air Care com ...

Отзывы: