- 17
4 Operation
4.1 Recommended Operating Conditions
Installation location
Indoors (wall or flat mounted)
Operating temperature
@
-4°F to 149°F (-20 to 65°C)
Operating temperature
(Recommended)
59°F to 86°F (15 to 30°C)
Humidity
5% to 95%
Altitude
Max 6,562ft (2,000m)
Cooling
Natural Convection
4.2 Powering Battery Pack
1. Turn on power switch after installing the battery pack. For parallel connected batteries, turn on power
switch one by one.
2. Within seconds, the internal main relay will turn on, all LEDs will light up.
3. If the battery pack initializes successfully, the RUN LED indicator on the front will turn green. The SOC
LED indicator will show the current capacity.
4.Turn on inverter.
CAUTION
If battery doesn’t turn on and indicates a FAULT or fails to operate, do not use the battery pack and contact
AIMS Power.