WARNING! The inverter charger must be connected to a battery bank in order to turn on and
transfer AC power.
Power
DC Input voltage
Wire Gauge
1KW
12V
AWG 1/0
1KW
24V
AWG 4
1.5KW
12V
AWG 1/0
1.5KW
24V
AWG 4
2KW
12V
AWG 1/0
2KW
24V
AWG 1/0
2KW
48V
AWG 4
3KW
12V
AWG 4/0
3KW
24V
AWG 1/0
3KW
48V
AWG 4
4KW
12V
AWG 4/0
4KW
24V
AWG 1/0
4KW
48V
AWG 1/0
5KW
24V
AWG 4/0
5KW
48V
AWG 1/0
6KW
24V
AWG 4/0
6KW
48V
AWG 1/0
Battery cables must be crimped (or preferably, soldered and crimped) copper compression lugs unless
aluminum mechanical lugs are used. Soldered connections alone are not acceptable. High quality, UL-listed
battery cables are available. These cables are color-coded with pressure crimped, sealed ring terminals.
Battery terminal must be clean to reduce the resistance between the DC terminal and cable connection. A
buildup of dirt or oxidation may eventually lead to the cable terminal overheating during periods of high
current draw. Use a stiff wire brush and remove all dirt and corrosion from the battery terminals and cables.
Содержание Global LF Series
Страница 1: ...Global LF Series Pure Sine Wave Inverter Charger User s Manual Version 9 0 PICOGLF10W PICOGLF60W ...
Страница 2: ......
Страница 17: ...15 2 5 8 LED Indicator Lights Status ...
Страница 29: ...27 3 6 Install Flange 1000W 1500W Models 2000W 3000W Models 4000W 6000W Models ...
Страница 30: ...28 DC Side View ...
Страница 36: ...34 ...
Страница 38: ...36 Appendix 2 Installation Diagram DC shunt is not required ...
Страница 39: ......
Страница 40: ...614 01206 09 ...