I-46
H-093630_EN • 00
P
roduct
I
nstallatIon
Combustion Adjustment for Gas Conversion
Combustion and Gas Data
TX 99 FS
TX 230 FS
min
max
min
max
CO
2
contents
G20 (±0,3)
%
8,2
9,2
8,2
9,2
G25 (±0,3)
%
8,3
9,1
8,2
9,1
G31 (±0,3)
%
10,5
11,0
10,5
11,1
O
2
contents
G20 (±0,3)
%
6,2
4,5
6,6
4,6
G25 (±0,3)
%
5,9
4,4
6,0
4,3
G31 (±0,3)
%
4,9
4,1
4,8
3,9
Gas pressure
G20 (20 mbar)
mbar
17 - 25
G25 (25 mbar)
mbar
20 - 30
G25.1 (25 mbar)
mbar
18 - 33
G25.3 (25 mbar)
mbar
20 - 30
G31 (30/37/50 mbar)
mbar
25 - 35 / 25 - 45 / 42,5 - 57,5
Gas flow rate
G20
m3/h
2,0
10,0
3,9
22,8
G25
m3/h
2,4
11,8
4,4
26,4
G31
m3/h
0,9
3,9
2,2
8,9
Conditions:
Tools and material:
î
Flue gas analyser
î
Screwdriver, flat head
î
Torx T15 & T40
î
Wrench, hex head, sizes 2 and 2.5
Adjustment Procedure (
Fig. 19 & Fig. 20
):
1.
Allow the appliance to operate for a few min-
utes.
2.
Connect the flue gas analyser probe to the
measuring port of the flue gas pipe.
3.
Check CO
2
contents in the flue gas at max
output as follows:
î
Using the rotary selector (
1
), select and
activate the
icon,
î
Select “
Special operations (1/3)
”,
î
Set “
Chimney sweep function
” to “
On
”,
î
Set “
Burner output”
to
“Full load”
.
4. Check the CO
2
(or O
2
) contents displayed on
the gas analyser, and compare the values with
those in the table below
.
5. If the value is outside the range, adjust the com-
bustion value by turning the gas valve throttle
(
2
) in small steps, to allow the value to stabi-
lise before performing additional adjustments.
TEXAS 99:
-
Rotate shutter screw (
2
)
clockwise (to the
right) to decrease
the CO
2
contents.
-
Rotate shutter screw (
2
)
counter-clockwise
(to the left) to increase
the CO
2
contents.
6. TEXAS 230:
-
Rotate shutter screw (
2
)
towards the “-”
sign to decrease
the CO
2
contents.
-
Rotate shutter screw (
2
)
towards the “+”
sign to increase
the CO
2
contents.
7.
Check CO
2
contents in the flue gas at min.
output as follows:
î
Set “
Burner output”
to
“Partial load”
.
î
Check the CO
2
contents, and compare the
values with those in the table at the bottom
of the page
.
î
If the value is outside the range, adjust the
combustion value by turning the offset screw
(
3
) in small steps to allow the value to stabilise
before performing additional adjustments.
Fig. 19. Combustion Adjustment - Control Panel
14:42
Special operations
(1/3)
Chimney sweep function
On
Back
1
ON
Содержание TEXAS 230
Страница 65: ...I 65 H 093630_EN 00 Maintenance Fig 27 Cleaning the Condensate Pipe and Trap 1 2 3 4 5 6 7 8 9 9 10 11 12...
Страница 67: ...Fig 28 Removing and Installing the Electrodes 3 I 67 H 093630_EN 00 Maintenance 1 2 3 4 5 mm 0 5 0 5...
Страница 73: ...Fig 31 Removing and Installing the Burner 1 2 3 4 5 6 7 8 I 73 H 093630_EN 00 Maintenance TEXAS 99 TEXAS 230...
Страница 75: ...Fig 32 Removing the Burner Plate 1 4 2 3 I 75 H 093630_EN 00 Maintenance...
Страница 91: ...I 91 H 093630_EN 00 Declaration of Conformity...
Страница 92: ...www myaic eu AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands...