Preventive maintenance
Warning. Make certain that the
power supply is disconnected
Changing the fan unit (DXP100, D
1. Switch OFF the safety switch
and lock it.
2. Disconnect the electric cable from the fan
units terminal box (1). The fan unit weighs
45 to 55 kg. Lifting tackle is recommended.
3. Unscrew the screws (2) that hold the
plate. Lift out the fan unit by using strops
under the arms (3).
Standstill
During long periods when the unit is not
in operation the fans should be run at least
four times a month. They are to be run
until the motor reaches normal working
temperature, i.e., for about 15 minutes.
Assemble the fan unit (DXP100, D
1. Lift the fan unit back and fit the screws (2).
2. Connect the electric cable in the fan units terminal box. (1).
3. Unlock the safety switch and switch ON.
1
2
3
DCP100)
DCP100)