Switch the cooling function on and off | 1.1.1
398051_4_0119
9 / 16
1.1.1
Switch the cooling function on and off
Switch off the cooling function for cleaning purposes
only.
Switch off cooling
function (start
manual defrost):
Press
for at least 3 s.
„OFF“ and the current
temperature are shown on the
display.
Switch on cooling
function (normal
operation):
Press
for at least 3 s.
The current temperature and
the symbols
are
shown on the display.
1.1.2
Setpoint
Display setpoint
Show set setpoint
(temperature):
Press
1 s.
Leave setup menu:
Press
again.
Change setpoint
Show set setpoint
(temperature):
Press
1 s.
Increase setpoint:
Press
.
Decrease setpoint:
Press
.
Assume new
setpoint:
Press
.
1.1.3
Assign bus address
Before assigning the bus addresses, the devices (1,
2,...n) must be networked with an appropriate bus
cable.
The first device (1) must be connected to market mon-
itoring (M) via the bus cable.
The bus cable must be terminated with a terminating
resistor (R) on the last device (n).
M
R
2
n
1
Fig. 4:
Bus system diagram
Bus cable
Patch cable CAT 5-S/FTP
Bus system
(optional)
PROTOCOL MODBUS RTU
RS-485 2-WIRE
Connection via RJ45 socket/
RJ45 plug
Baudrate
9600 oder 19200 Bit/s
Data Lenght
8 Bit
Parity
none
Stop bit
1
Minimum TimeOut
60ms
Pin 4
Pin 5
Pin 8
Fig. 5:
RJ45 connector bus cable, RJ45 sockets device and
terminating resistor (R)
Pin
Data
Colour
4
B / +
Blue
5
A / -
Blue/White
8
Ground
Brown
The controller are delivered with the bus address
„1“ (corresponds to a „stand-alone“- unit). For identific-
ation of several units in the bus system, the bus ad-
dresses must be assigned starting with „1“.
Bus addresses must not be assigned twice. After-
wards, we recommend entering the addresses accord-
ing to the actual wiring sequence.
A maximum of 207 addresses are possible.
Access programming level
1.
– Press
for at least 3 s .
„PS“ and afterwards „0“ are shown on the
display.
2.a
Variant with password
– Press
or
until „22“ appears.
Then press
.
„/2“ is shown on the display.
2.b
Variant without password
– Press
.
„St“ or „H0“ are shown on the display.
3.
– Press
or
until „H0“ appears.
Then press
.
Assign bus address
4.
– Increase bus address: Press
.
– Decrease bus address: Press
.
5.
– Accept new entry: Press
once.
Leave programming level
6.
– Press
5 s.
The current temperature is shown on the display
again.
Assign bus address for subsequent units:
– Repeat point 1 to 6 on each unit and set next free
bus address.