26
Item
Range
Default
Value
Access Level
Description
AUX1 On Time
12:00A-11:59P
---
Installer/
Service Sub-
menu
Select ON time for AUX1 to take
effect.
AUX1 Off Time
12:00A-11:59P
---
Installer/
Service Sub-
menu
Select OFF time for AUX1 to stop.
AUX2 On Time
12:00A-11:59P
---
Installer/
Service Sub-
menu
Select ON time for AUX2 to take
effect.
AUX2 Off Time
12:00A-11:59P
---
Installer/
Service Sub-
menu
Select OFF time for AUX2 to stop.
Cooling
Deadband
2F–10F / 1C–5.5C
6F
Installer/
Service Sub-
menu
In Pool Auto mode, the cooling set-
point is the heating setpoint minus
this Cooling Deadband value.
Defrost Temp
20F–35F / -6.5C–1.5C
35F
Installer/
Service Sub-
menu
This is the temperature measured on
the coil when the control goes into
Defrost mode.
Def Terminate
40F–60F / 4C–15.5C
50F
Installer/
Service Sub-
menu
If the coil temperature reaches this
setpoint, Defrost will terminate. Other
Defrost algorithms are still operating
behinds the scene.
Outside Lockout
Off,
30F–50F / -1C–10C
Off
Installer/
Service Sub-
menu
The installer can program the control
to Lock out operation of the unit if a
specific outside temperature is meas-
ured. Off allows operation at any
ambient temperature.
Set Model Type
HEAT ONLY, POWER
DEFROST,
HEAT/COOL
HEAT/
COOL
Installer/
Service Sub-
menu
Set at the factory. Will need to be set
by Installer during any replacement of
the control board.
EXV
Disabled, Type 1,
Type 2
Disabled
Installer/
Service Sub-
menu
Set at the factory on new units.
Select “Disabled” if unit equipped with
TXV for board replacement. EXV
Type 1 is 500 step EXV. EXV Type 2
is 1600 step EXV.
Change EXV to
Yes/No
Installer/
Service Sub-
menu
This screen asks if you really want to
change the EXV setting – the UP or
DOWN button must be pressed to
show YES before the EXV type will be
changed.
Brownout
Detection On
On/Off
On
Installer/
Service Sub-
menu
This function will shut down operation
of the unit if the 24VAC signal drops
below 18VAC to protect the unit from
Low Voltage. This feature can be
turned off as desired.
Set Factory
Defaults
Installer/
Service Sub-
menu
Press and hold both the UP and
DOWN buttons for 3+ seconds to
reset the factory defaults in the con-
trol. When reset, the screen will
display “Defaults Set”.
NOTE:
Make sure that the values for each setting are recorded for future reference or if the control ever needs
to be reset to Factory Defaults. All these values will need to be re-entered.