12. Sensor programming
Locking level
Locked functions
0
None
1
Measuring range + element flags + output mode
3
+ units
4
+ zero-point corr gain correction
5
+ base value + exponent
6
+ analog output, start and end
+ zero-point adjustment, temporary
7
+ limit values, maximum and minimum
Function
Locking mode
:
Locking level : 5
In the
SENSOR PROGRAMMING
menu the functions are listed from top to bot-
tom in such a way that the locked functions cannot be selected.
12.5 Limit values
Two limit values (MAXIMUM and MINIMUM) can be programmed per measur-
ing channel. Exceeding one of these limit values is treated as a fault (in the
same way as exceeding a measuring range limit or as sensor breakage). In the
display, in front of the measured value affected, the appropriate arrow
or
appears and the alarm relays connected by relay cable are triggered (see
14.2). Limit values can also have relays assigned to them (see 12.12.2). This
alarm status remains effective until the measured value returns within the pre-
scribed limit value by the amount set as hysteresis. Hysteresis is normally set
to 10 digits but this can be adjusted to any number between 0 and 99 (see
13.7). The event of a limit value being exceeded can also be used to start or
stop a measuring operation (see 12.12.2).
Function
Enter limit value, maximum (see 8.5):
7 Limit value, maximum: 123.4°C
Limit value, minimum :
7 Limit value, minimum : -----°C
To disable limit values :
<OFF>
To enable limit values :
<ON>
12.6 Scaling, Decimal point setting
To display the electrical signal of a sensor as a measured value in its physical
size it is nearly always necessary to perform a zero-point shift and multiplica-
tion by a factor. To perform these steps the functions BASE and FACTOR are
provided. For a detailed description of scaling, with an example, please refer to
the Manual, Section 6.3.11.
Displayed value
= (corrected measured value - BASE) x FACTOR
48 ALMEMO
®