Quick Start Setup Instructions for Müller RCM ISO -
Single Product
Product 1 Master/Dump Valve
:
No Master/Dump Valve
(When Dump Valve is selected, the valve will remain open
when not applying)
Boost Pump
: Unchecked
(Put a checkmark if the system is setup for use of a booster
pump)
Control PWM Base Freq
:
GX5 (hydraulic)…
150 Hz
GX2
(electric)…….150 Hz
GX40 Synergist….150 Hz
*These settings are adjusted as needed
.
P:
This is a portion of the loop that is proportional to the amount of time the error is present
I:
This is the portion
of the loop that accumulates previous errors. It is the “memory” of the control loop. For each
loop cycle, the
integrator adds the current error to the previous integrator value.
Dead Band:
The allowable value that NO controlling/corrections will be made to the control valve. A low number may result in
oscillation around the target rate. High number may result in not achieving the target rate.
Minimum/Maximum Time:
Min/ms
is the value the output will start from no matter how much correction is needed. Max/ms is
the max
value the output will reach once saturation of the output has been reached
•
P
ress the 3
-
dot icon to go to the next page of the
Advance Configuration.
Advance Configuration (Features) Continued
•
P
ress the 3
-
dot icon to go to the next page of the
Advance Configuration.
Product 1 Controller Settings*:
P:
GX5
(hydraulic)…
.
3.0
GX2 (electric)…….
3.0
GX40 Synergist….
3.0
D:
GX5 (hydraulic)…
0.5
GX2 (electric)…….
0.5
GX40 Synergist….
0.5
PWM Min:
GX5 (hydraulic)…
10%
GX2 (electric)…….
10%
GX40 Synergist….
10%
I:
GX5 (hydraulic)…
.
3.0
GX2 (electric)…….
3.0
GX40 Synergist….
3.0
Dead Band:
GX5 (hydraulic)…
3
%
GX2 (electric)…….
0.0
GX40 Synergist….
0.0
PWM Max:
GX5 (hydraulic)…
100%
GX2
(electric)…….
100%
GX40 Synergist….
100%
AGXCEL,