RECTANGULAR TANKS
MODEL NUMBER
CAPACITY
(Liters)
REQUIRED
VENTING
CAPACITY
m^3/min
MAX. TEST
PRESSURE
(kPa)
RFV 1100
1135
34
35
RFV 2400
2400
48
35
RFV 5000
5000
125
20
Table 2C
TANK GROUNDING:
Standard Westeel tanks include at least 1 carbon steel grounding lug or attachment point. Ground lugs have a minimum
3/8” hole. If no ground lug is shown on the drawing, a 3/8 hole can be drilled on a suitable location on the tank saddle
(on horizontal tanks) without structural integrity concerns or another tank ladder or pipe support lug can be used for
grounding purposes.
Requirements and installation details for grounding is outside the scope of ULC standards and the tank
user or installer should refer to electrical codes governing the installation of electrical equipment attached to the tank.
Use of a dielectric sealant (not provided by Westeel) is recommended to maintain electrical continuity of the ground wire
connection to the tank and stud or bolt shown below.
Typical Ground Detail
TANK LIFT LUGS:
Care must be taken to prevent damage during handling. When lifting and moving the tank, use only, and all of, the lift
lugs identified on the tank for this purpose. The lift cable or chain length must be allow for a minimum angle of 60 degree
between a horizontal plane and the sling. Tanks designed for stationary applications should never be transported or lifted
with product contained within.
NOTE: LIFT LUGS ARE NOT CERTIFIED TO LIFT THE TANK CONTAINING PRODUCTS.
Lift Lug Decal