AGF 5100ALBV Скачать руководство пользователя страница 3

Quality Components for Fire Sprinkler Systems

3

AGF Manufacturing • Phone: 610-240-4900 • [email protected] • 

www.agfmfg.com

Model 5100/5200 INSTALLATION INSTRUCTIONS
Retrofitting onto an Existing System:

1.  Isolate branch line or zone where the COLLECT

an

DRAIN is to be installed.

2.  Relieve air pressure from the branch line.
3.  Remove existing auxiliary drain (drum drip, low-point drain).
4.  Install the COLLECT

an

DRAIN by attaching the supply valve (upper) to the 

fire sprinkler system pipe in accordance with NFPA 13 standards pertaining 
to low-point drains (auxiliary drains).

5.  Confirm that the supply valve (upper) is in the open position and ready to 

collect condensation, the drain valve (lower) is closed, and the plug is tight.

Installation into a New System:

1.  Install the COLLECT

an

DRAIN by attaching the supply valve (upper) to the 

fire sprinkler system pipe in accordance with NFPA 13 standards pertaining 
to low-point drains (auxiliary drains).

2.  Confirm that the supply valve (upper) is in the open position and ready to 

collect condensation, the drain valve (lower) is closed, and the plug is tight.

3.  Activate the fire sprinkler system for operation.

NOTE: 

The presence of a 

small amount of water

 in the COLLECT

an

DRAIN Model 

5100 will activate the Model 5100ALBV water detector’s visual and audible alarms. 
The COLLECT

an

DRAIN must be completely drained to silence the alarms. If the 

Model 5100ALBV is wired directly to a fire panel or BMS call or email AGF for 
instructions on silencing the water detector’s local alarms.

Model 5100/5200 OPERATING INSTRUCTIONS
To Collect Condensation per NFPA 25:

1.  Close the drain valve (lower) by making sure the valve handle is 

perpendicular to the collection assembly.

2.  Apply a proper sealant to the drain plug threads and make sure it is secured 

tightly into the bottom of the drain valve (lower).

3.  Slide the Anti-Trip Plate to its lowest position.
4.  Open the supply valve (upper). If equipped, install the anti-tamper lock.

Содержание 5100ALBV

Страница 1: ...INST 5100 5200 6 22 Models 5100ALBV 5100 5200 www agfmfg com Owner s Manual Owner s Manual Owner s Manual Owner s Manual Model 5100ALBV Model 5100A Model 5200A...

Страница 2: ...LECTanDRAIN Models 5100 and 5200 are NOT designed to prevent freezing or automatically drain condensation from the system FAILURE TO DRAIN CONDENSATION MAY RESULT IN CATASTROPHIC SYSTEM FAILURE DUE TO...

Страница 3: ...FPA 13 standards pertaining to low point drains auxiliary drains 2 Confirm that the supply valve upper is in the open position and ready to collect condensation the drain valve lower is closed and the...

Страница 4: ...NSTRUCTIONS The Model 5100ALBV Water Detector operates on the principle of conductivity It contains a probe that is attached to the piping system and when condensate collects in the piping and reaches...

Страница 5: ...ately for this and any other loads on the same circuit Battery Operation 1 Remove the four screws on the alarm box and take the cover off 2 For battery operation check to make sure the Voltage Jumper...

Страница 6: ...g B Ensure DC is from a clean power supply and not full wave rectified without a capacitor 6 Replace the cover with the four screws TEMPERATURE SENSING FUNCTION When the Temperature Sensing Function i...

Страница 7: ...Alarm also features a Remote Notification Function This function allows you to connect the unit directly to the fire control panel or BMS so when water is detected in the auxiliary drain you will be...

Страница 8: ...AGF Manufacturing 100 Quaker Lane Malvern PA 19355 Phone 610 240 4900 techsupport agfmfg com www agfmfg com...

Отзывы: