AFRISO OSA 3 Скачать руководство пользователя страница 15

AFRISO EMA AB

 • Kilvägen 2, 232 37 Arlöv • Sweden • Phone +46-(0)40-92 20 50 • [email protected] • www.afriso.se

15

OSA 3

Seperator alarm OSA 3 • Manual

Maintenance

The function of the separator alarm must 
be tested as described in SS-EN 1825 and 
SS-EN 858.

For more details, see the operation and 

maintenance instructions for the separator.
The sensors may need to be periodically 
cleaned or wiped so as to prevent exces-
sive deposits building up that may cause 
the triggering of false alarms.

PROGRAMMING FUNCTIONS IN OSA 3

- Ver 1.03   18-02-16

This manual is intended for authorised service personnel only.

The flow chart below shows all the possible functions which can be ac-

cessed via the buttons on the unit.

The unit automatically logs all alarm changes with date/time in 

the background.

Alarms are saved with the date and time of each status change. 

Storage takes place cyclically. This means that when the memory 

is “full”, the oldest values are overwritten with new ones. 

To display the alarm log, hold down   and   together for 3 

seconds. This opens the alarm log. Pressing   or   allows you 

to scroll through the various events. In the example below, each 

status change is shown along with an indication of the time and 

which sensor was changed. 1=layer, 2=damming, 3=sludge. X 

means that the alarm has been triggered and – means that the 

alarm has been reset. If an acknowledgeable alarm has been 

acknowledged, this is indicated by the letter K and the relevant 

digit to indicate whether it relates 

to R1, R2 or both.

To stop scrolling, hold down Reset for 3 seconds. The unit then 

returns to its normal display.

It is possible to select or disable a sensor by calling 

the input menu. The sensor input status is displayed 

and   and   are used to select the relevant sen-

sor input. 

X = active, - = inactive. To change values, press  . 

When you have made your change, hold down   for 

3 sec. or cancel your change by holding down Reset 

for 3 seconds.  

 moves from the first digit in Date and forwards every 

time it is pressed. To reduce a value, press  , and to 

increase a value, press  . When you have made your 

change, hold down   for 3 sec. or cancel your change 

by holding down Reset for 3 seconds.  

The first letter of the relevant option is indicated with 

the cursor. The next option can be selected by press-

ing  . To select an option, hold down   for 3 seconds. 

Holding down Reset for 3 seconds allows you to leave 

the menu without changing the settings. 

Possible settings are for R1 and R2. Act = Acknowl-

edgeable/Non-acknowledgeable. ACT = Selection 

of which input(s) enables (enable) the relay output. 

 moves to the right between the various options. 

X = active, - = inactive. To change values, press  . 

When you have made your change, hold down   for 

3 sec. or cancel your change by holding down Reset 

for 3 seconds.  

Calling the settings menu allows you to display 

Languages. Selectable languages, and you can select 

a language using the   and   keys. To make your 

choice, the v key has to be held down for at least 3 

sec., or you can cancel your change by holding down 

Reset for 3 seconds.  

    Separator alarm      

      Status OK  

                    

  2012.10.01  16:00 

Main menu

  Sensor Layer        X 

  Sensor Damming   - 

  Sensor Sludge         -  

  X  <, >, V               

Inputs

   Swedish   X 

   English   -    

   German        -        

   French     -

Language selection

 >SERVICE 

   DATE-TIME           

   INPUTS

   RELAY OUTPUTS

Settings

 <, > = REDUCE/INCREASE

 V = NEXT          

 V (3 sec) = DONE

   2012.10.01   16:45

Date/Time

  REL1 -  Ack     -    

  Act 1  - Input X X X

  REL 2 – Ack    X  

  Act 2 – Input -  X  - 

Relay settings

+

Reset

[Reset]  

3 sec

   SERVICE 

 >DATE-TIME           

   INPUTS

   RELAY OUTPUTS

   SERVICE 

   DATE-TIME           

 >INPUTS

   RELAY OUTPUTS

Settings

   SERVICE 

   DATE-TIME           

   INPUTS

 >RELAY OUTPUTS

Settings

   DATE-TIME           

   INPUTS

   RELAY OUTPUTS

 >LANGUAGE

Settings

    Separator alarm      

      Status OK  

                    

  2012.10.01  16:00 

Main menu

2012.01.02,10:03 1  

2012.01.02,12:03 1- 

2012.01.03,18:03 2X

2012.01.04,05:03 K1

Logger display

+

 

in 3 sec

[Reset]  

3 sec

[Reset]

 /

 

3 sec

[Reset]

 /

 

3 sec

[Reset]

 /

 

3 sec

[Reset]

 /

 

3 sec

Содержание OSA 3

Страница 1: ...e 2460 CONTENTS Functional description 2 Component parts 3 Spare parts 5 Safety regulations 6 Checklist 7 Installation 8 Commissioning 11 Operation 14 Maintenance 15 Troubleshooting 16 Technical data 18 Retain these instructions for future use Edition 1 3 18 11 22 OSA 3 Level alarm for oil separator ...

Страница 2: ...of oil or grease exceeds the alarm value ES8 Ultrasonic type sludge Ex sen sor for raising the alarm when sand or particles in the separator exceed a predefined level R6 S Thermistor type Ex damming sen sor for indication of a high level OSA 3 is an Intrinsically Safe Ex central alarm control unit approved for use with the listed Ex sensors The central alarm control unit has two individually progr...

Страница 3: ...OMPONENT PARTS OSA 3 level sensor Art nr 1316 Central unit OSA 3 1 x Level sensor ES4 1 x Central unit OSA 3 1 x Level unit ES4 1 x Damming sensor R6 S 1 x Central unit OSA 3 1 x Level sensor ES4 1 x Damming sensor R6 S 1 x Sludge sensor ES8 1 x OSA 3 Level and damming alarm Art no 1318 OSA 3 Level damming and sludge alarm Art no 1319 ...

Страница 4: ...PONENT PARTS OSA 3 Level and damming alarm Art no 13347 Central unit OSA 3 1 x Level sensor ES4 1 x Sludge sensor ES8 1 x Central unit OSA 3 1 x Sludge sensor ES8 1 x OSA 3 Slamgivare Art nr 13345 OPTIONS Float Float for level sensor ES4 where the surface is not constant Art no 1236 SMS ALARM GSM dialer for alarm transmission Art nr 1324 ...

Страница 5: ...Capacitive sensor ES4 Emits alarm if thick layer of oil grease in separator Art nr 1147 LEVEL SENSOR ES4 20 meters Capacitive sensor ES4 Emits alarm if thick layer of oil grease in separator Art nr 1148 DAMMING SENSOR R6 S 5 meters Thermistor sensor Emits alarm if high level in separator Art nr 990143 DAMMING SENSOR R6 S 20 meters Thermistor sensor Emits alarm if high level in separator Art nr 990...

Страница 6: ...age to equipment Attention required SYMBOL DESCRIPTION Read instructions before installation Installation may only be carried out by a qualified installation engineer The intrinsically safe circuit must not be earthed Observe regulatory requirements when connected in an EX classified area SYMBOL DESCRIPTION Regulations applicable to OSA 3 To note when there is a risk of explosion Note Safety regul...

Страница 7: ...s recom mendation before carrying out a sensor function control Switch on the power and check sensor signals Carry out a function control as shown in the commissioning instructions Important information Note that the unit s intrinsically safe sensor outputs on terminal block K3 1 2 3 G are galvanically isolated from earth This user manual constitutes the basis for certification governing protectio...

Страница 8: ...unction box should be used that allows the shielded cable to be grounded to earth When making connections between the central control unit and a junction box this should be interconnected using a multi core cable 6 core 1 0mm with connec tions made as shown in the following diagram Terminals K1 230 VAC 4 VA K2 R1 Voltage free relay output Symbols on the circuit board are indicated in the alarm con...

Страница 9: ... an ES8 sludge sensor an external junction box should be used that allows the shielded cable to be grounded to earth Terminals K1 230 VAC 4 VA K2 R1 Voltage free relay output Symbols on the circuit board are indicated in the alarm condition K2 R2 Voltage free relay output Symbols on the circuit board are indicated in the alarm condition K4 Terminal contact for membrane keypad ribbon cable not show...

Страница 10: ... with your separator manufacturer for more details The following recommendations apply Level sensor ES4 is fitted so that its underside H is fixed approx 100 500 mm below the static water level The precise installation depth H below the static water level is specified in the separator manual The underside of the level sensor must be in water so as NOT to trigger an alarm see the illustration below...

Страница 11: ...red The buzzer sound is repeated automatically after 20 hours if R1 is not set for an acknowledgeable function Checks when starting the electronic unit Check that all connections and installation are completed correctly before connecting to a power supply Switch on the power supply to the elec tronic unit This screen is displayed for approx 15 seconds after which the current program version can be...

Страница 12: ...ted In the main menu press the RESET key at the same time for 3 seconds The following screen will appear Activate the service mode by pressing for 3 seconds The unit will now show a number on the screen indicating which probe is being scanned The unit remains in service mode for 30 minutes and returns automatically into normal mode All connected sensors should be tested af ter installation The fol...

Страница 13: ...ld then be displayed When this has been displayed remove the sensor from the water and wait for up to 2 minutes The unit should then return to Normal operation screen Testing of sludge sensor ES8 Lift the sludge sensor up into the air and wait The following screen should be displayed within approx 60 sec Press the reset button the following should then be displayed When this has been displayed sus...

Страница 14: ...zer sounds Action This is a critical alarm and means that the shut off valve in the separator has been closed or there is a blockage in the outlet to the tank Check the instructions from the separator manufacturer to find out what action is recommended Sludge alarm SLUDGE ALARM appears in the display and the buzzer sounds Action This normally means that the sludge layer in the tank is too thick th...

Страница 15: ...lues press When you have made your change hold down for 3 sec or cancel your change by holding down Reset for 3 seconds moves from the first digit in Date and forwards every time it is pressed To reduce a value press and to increase a value press When you have made your change hold down for 3 sec or cancel your change by holding down Reset for 3 seconds The first letter of the relevant option is i...

Страница 16: ...lay Sensor err on input 1 level alarm appears in the display Sensor err on input 2 high level alarm appears in the display Sensor err on input 3 sludge alarm appears in the display Sludge alarm act alarm The sludge level has reached a set alarm level normal alarm High level alarm act alarm Check the thickness of the oil grease layer Measure voltage at sensor Measure voltage at sensor Measure volta...

Страница 17: ...sor circuits an error message will be displayed on OSA 3 indicating which sensor output is detecting an error The output voltage to the sensor in question can be measured in order to check what is wrong Sensors are scanned in the following se quence and sensors can only be checked when the are active Sensor 1 layer sensor ES4 active in 4 sec sensor 2 thermis tor sensor R6 S active in 45 sec sensor...

Страница 18: ...fe circuit up to 50 of the value of Lo is permitted and up to 1 uF Level sensor ES4 Intrinsically safe design II 1 G Ex ia IIA T4 Ga Sensor type Capacitive type ES4 Must be connected to a barrier which is galvanically isolated from earth Electrical parameters Ci 500 nF Li 10 μH Ii 170 mA Ui 25 0V Pi 1 2 W Damming sensor R6 S Intrinsically safe design II 1 G Ex ia IIA T3 Ga Sensor type Thermistor s...

Страница 19: ...ds Emission standard for residential commercial and light industrial environments LVD EN 61010 1 2010 Safety requirements for electrical equipment for measurement control and laboratory use Part 1 General requirements ATEX EN 60079 0 2012 A11 2013 Explosive atmospheres Part 0 General requirements EN 60079 11 2012 Explosive atmospheres Part 11 Equipment protection by intrinsic safety i EC Type exam...

Страница 20: ...Afriso Ema AB Kilvägen 2 232 37 Arlöv Sweden T 46 0 40 92 20 50 F 46 0 40 19 33 58 www afriso se Afriso EMA AB 2018 11 22 Notes ...

Отзывы: