Using the room unit
You can adjust the temperature by rotating the knob (A) on the default screen: for floor and radiator
heating (LO and HI) you adjust the indoor temperature (5-35°C), and for constant temperature control
(CT) you adjust the supply water temperature (0-90°C). The set temperature will blink five times on the
display, and then it will become effective. You can also confirm the setting by pushing Enter (C).
ECO button (B)
The ECO button can be used for switching on the ECO and HOLIDAY modes.
ECO mode is designed for adjusting the temperature temporarily, for example for decreasing the
temperature during a workday. Of course, the function can also be used for increasing the temperature
temporarily.
HOLIDAY mode is designed for longer-term temperature adjustment, for example for the duration of a
holiday or indefinitely.
ECO mode can be switched on by a single push of the ECO button (B) (the
default setting is 8 h/20.5 degrees). When ECO mode is switched on, its duration
is displayed in the upper right-hand corner for 20 seconds.
HOLIDAY mode can be switched on by pushing and holding the ECO button (B)
for more than three seconds (the default setting is 30 days/18.5 degrees). When
HOLIDAY mode is switched on, its duration is displayed in the upper right-hand
corner for 20 seconds.
Enter button (C)
A single push displays a quick menu that shows the measured indoor and supply water temperatures,
calculated supply water set point, and valve position. The menu can be navigated with the rotating knob
(A) or one step at a time with the Enter button.
Pushing and holding the Enter button (C) for more than three seconds opens the user menu. The menu
can be navigated with the rotating knob (A), and the Enter button (C) activates the current selection.
After this, the value to be adjusted will blink on the display. A blinking value can be changed with the
rotating knob (A), and the selection is confirmed with Enter (C) (see Figure 1 on page 2).
Minimum supply water temperature
radiator heating: min. 5-35°C/factory setting: min. 5°C
floor heating: min. 5-35°C/factory setting: min. 20°C
NOTE! In ECO and HOLIDAY modes, the minimum supply water temperature is
5°C so that the temperature can be reduced as desired.
Maximum supply water temperature
radiator heating: max. 40-95°C/factory setting: max. 60°C
floor heating: max. 20-50°C/factory setting: max. 35°C
28
29
Содержание AM20 SW 1.16
Страница 2: ...1 2 D C B A 2 ...
Страница 16: ...Symbole dolnego rzędu menu użytkownika menu ustawień tryb ECO tryb HOLIDAY 16 ...
Страница 20: ...In English Setup and User Guide for AFRISO BWR Heating Controller AM20 SW 1 16 RU SW 1 18 20 ...
Страница 32: ...Bottom row symbols user menu setup menu ECO mode HOLIDAY mode 32 ...
Страница 36: ...Πо русски Руководство по настройке и эксплуатации терморегулятора BWR AM20 SW 1 16 RU SW 1 18 36 ...
Страница 48: ...Символы нижнего ряда меню пользователя Меню настроек режим ECO режим ОТПУСК 48 ...
Страница 52: ...3 2016 AFRISO Sp z o o Szałsza ul Kościelna 7 42 677 Czekanów zok afriso pl www afriso pl ...