25
Mounting
AFA 11
EN
5.5.5
Relay output
NOTICE
VOLTAGE PEAKS WHEN INDUCTIVE CONSUMERS ARE SWITCHED OFF
When inductive consumers are switched off, this can cause voltage peaks and
can lead to adverse effects on electrical systems and may destroy the switching
contact.
•
Use commercially available standard RC combinations such as
0.1
μ
F/100 Ohm for inductive consumers.
Failure to follow these instructions can result in equipment damage.
The operating state is available via the relay output (voltage-free change-
over contact). The alarm can be transmitted to an additional alarm unit (for
example, ZAG 01).
1. Connect the additional equipment to the terminals "Alarm".
Содержание AFA 11
Страница 12: ...11 Produktbeschreibung AFA 11 DE 4 2 Abmessungen 60 mm 65 mm 100 mm 188 mm 166 mm ...
Страница 23: ...2 3 1 4 5 22 Montage DE AFA 11 2 Schließen Sie das Signal teil ...
Страница 47: ...46 Anhang DE AFA 11 15 2 EU Konformitätserklärung ...
Страница 48: ...47 Anhang AFA 11 DE 15 3 Leistungserklärung ...
Страница 49: ...48 Anhang DE AFA 11 ...
Страница 62: ...11 Product description AFA 11 EN 4 2 Dimensions 60 mm 65 mm 100 mm 188 mm 166 mm ...
Страница 73: ...2 3 1 4 5 22 Mounting EN AFA 11 2 Close the control unit ...
Страница 101: ...11 Description du produit AFA 11 FR 4 2 Dimensions 60 mm 65 mm 100 mm 188 mm 166 mm ...
Страница 112: ...2 3 1 4 5 22 Montage FR AFA 11 2 Fermez l unité de com mande ...
Страница 141: ...11 Descripción del producto AFA 11 ES 4 2 Dimensiones 60 mm 65 mm 100 mm 188 mm 166 mm ...
Страница 152: ...2 3 1 4 5 22 Montaje ES AFA 11 2 Cierra la unidad de con trol ...
Страница 181: ...11 Descrizione del prodotto AFA 11 IT 4 2 Dimensioni 60 mm 65 mm 100 mm 188 mm 166 mm ...
Страница 192: ...2 3 1 4 5 22 Montaggio IT AFA 11 2 Chiudere lʼunità di segnale ...