13
Measurements
EN
GPG 01
6.2
Wet test
You can use water or fuel oil/diesel for the wet test.
1. Prepare a container with liquid.
1. Press the arrow key "right" to start the wet test.
- A countdown of 45 seconds starts.
2. Submerge the level sensor into the liquid.
- The product detects the submerged level sensor.
- The display shows "OK".
- The switch-off time in seconds is displayed.
3. Press the arrow key "right" to display the test results (heating phase and
switch-off time).
4. Press the arrow key "right" again to start the test of the heating process.
5. Document the test result of the heating phase and the wet test in the
inspection certificate.
- The test certificate form can be found at www.afriso.com.
If you press the arrow key "left" during the measurement, the measurement
is cancelled.
If an error is detected during operation, the display colour changes to red.