2.Safety & Symbols
2.1 Safety Precautions
1. All work on the inverter must be carried out by qualified electricians.
2. The device may only be operated with PV panels.
3. The PV panels and inverter must be connected to the ground.
4. Do not touch the inverter cover until 5 minutes after disconnecting both DC and
AC power supply.
Safety & Symbols
02
Type
Single-Phase(Two MPPT Trackers)
HNS7000TL
HNS8000TL
32
35.5
50
50
Max AC Current [A]
Rated current of AC breaker[A]
Circuit Breaker and Surge Protector Recommendation:
Note:
The Inverter can be only connected to low-voltage grid.
(220/230Vac, 50/60Hz).
SPD: Lightning protection system, refer to the following options:
AC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 2.5KV
DC side, nominal discharge current 20KA, second grade lightning protection,
protection voltage 3.2KV
The wiring distance between the inverter and the distribution box should be at
least 5 meters.