Maintenance&Trouble Shooting

18

Trouble-Shooting List

GFCI Fault

Ground Fault 

Circuit Interrupter 

fault

Ground Fault Circuit 

Interrupter fault

restart the inverter

Bus High 

Fault/Bus 

Fault

Bus Voltage High 

/Bus Fault

· PV Input voltage high

· AC side poor connection

· check PV input voltage within 

450Vdc(up to 3.0kw model), 

500Vdc(up to 5.0kw model)

· check AC connector, circuit breaker 

well connection

No Utility

Utility loss

· utility loss

· AC side circuit breaker 

turn off

· AC side poor connection

· inverter fault

· grid back to the normal, the inverter 

will restart automatically

· replace the AC circuit breaker

· check AC connector well 

connection

· after seceral retart the fault remains, 

replace inverter

Ground 

Current 

Fault

Leakage current 

high

1. poor earthing, leakage 

current high

2. PV(+) or PV(-)  earthed

1. check the AC output wring and 

restart the inverter

2. check PV array wiring

Over 

Temperatu

re Fault

Inverter too hot

· inverter enclosure too hot

· temperatrue sensor fault

· turn off the inverter still the 

temperature down to the normal. Or 

install the inverter at a well ventilated 

site.

· replace the temperature sensor

PV Over 

Fault

PV input voltage 

high

· PV array's Voc high

· re-design the PV array 

configuration

· measure the PV array voltage is the 

same as inverter displayed.

M Grid 

Volt Fault

Grid voltage out of 

range

· grid voltage out of  the 

setting range

· grid back to the normal, the inverter 

will restart automatically

· check Country standard setting is 

correct

Isolation 

Fault

Insulation 

Resistance high · PV(+) or PV(-

Code

Error 

Display

Error Message

Possible Fault

Correctie Measure

E0

E6/E11

E9

E10

E13

E15

E17

E18

)  earthed

check the resistance between PV(+) 

and ground, PV(-) and ground bigger 

than 2MΩ.

E19

E12

E24

E29

Current 

DC Offset

DC bias high

· AC side DC bias high

restart the inverter

Over 

Current

Over current fault · grid fluctuate

· AC side poor connection

· the inverter will restart automatically

· check the AC output wring and 

restart the inverter

Relay 1/2 

Fault

Relay fault

· inverter fault

restart the inverter

MGrid 

FreqFault 

Grid frequency out 

of range

· grid fluctuate

· grid frequency out of 

setting range

· grid back to the normal, the inverter 

will restart automatically

· check inverter frequency setting 

range correct

Содержание HNS7000TL

Страница 1: ...Installation and Operation Manual On Grid PV Inverter ...

Страница 2: ...ter 3 5 Electrical Connection 3 5 1 PV Connection 3 5 2 Grid Connection 3 5 3 Communication Connection WIFI Ethernet GPRS RS485 4 Operation 4 1 Control Panel 4 2 Menu Structure 4 3 Setting 4 3 1 Startup Setting 4 3 2 Parameter Setting 5 Commissioning 6 Shut Down Restart the Inverter 6 1 Shut Down Procedures 6 2 Restart the inverter 7 Maintenance Trouble Shooting 7 1 Maintenance 7 2 Fault Code and ...

Страница 3: ...ust only be performed by qualified personnel Single Phase One MPPT Tracker HNS7000TL HNS8000TL Please keep this manual all the time available in case of emergency About This Manual 01 The typical connection diagram for the entire PV system is on grid PE WIFI RS485 Cloud server Portal web Porta Smart phone PV Inverter Circuit Breaker N L 3 AC Grid Surge Protective Device CircuitBreaker 1 SurgeProte...

Страница 4: ...ackers HNS7000TL HNS8000TL 32 35 5 50 50 Max AC Current A Rated current of AC breaker A Circuit Breaker and Surge Protector Recommendation Note The Inverter can be only connected to low voltage grid 220 230Vac 50 60Hz SPD Lightning protection system refer to the following options AC side nominal discharge current 20KA second grade lightning protection protection voltage 2 5KV DC side nominal disch...

Страница 5: ...tions during installation operation and maintenance Safety Symbols 03 2 2 Explanations of Symbols Do not dispose of this device with the normal domestic waste Without transformer This inverter does not use transformer for the isolation function CE mark The inverter complies with the requirements of the applicable CE guidelines Refer to manual before service Danger of electric shock The inverter co...

Страница 6: ...heck the packing list shown as below Installation 04 No 1 2 3 4 5 6 7 1 1 1 1 1 1 4 Solar Inverter Certificate Of Inspection Quick Installation Instructions Warranty Card Wall Mounting Bracket Waterproof Cover Wiring Cover Screw 8 9 10 11 12 3 3 1 1 1 Plastic Expansion Tube Mounting Bracket Screw Security Screw Screwdriver For Security Screw Grounding Terminal Qty Items No Qty Items 6 2 3 4 5 1 8 ...

Страница 7: ...figures show the assignment of the individual connection areas on the bottom of the inverter Installation 05 3 2 Product Overview No 1 2 3 4 DC Switch DC Side For PV String AC Side Monitor Module Items 345mm 460mm 170mm DCA DCA DCB DCB N L 1 2 3 4 ...

Страница 8: ...e or corrosion materials where is suitable for inverter s weight and dimensions The ambient temperature should be within 25 60 between 13 F and 140 F The installation of inverter should be protected under shelter Do not expose the inverter to direct sunlight water rain snow spray lightning etc Installation 06 3 3 Mounting Location The inverter should be installed vertically on the wall or lean bac...

Страница 9: ...on 07 3 4 Installation On grid PV Inverter Leave the enough space around inverter easy for accessing to the inverter connection points and maintenance 300mm 100mm 100mm 500mm Step 1 Step 2 328 5mm 26mm 26mm 35mm ...

Страница 10: ...string are correct Use the DC plugs in the accessory The lightning protector should be equipped between PV string and inverter Disconnect all of the PV DC switch during wiring 3 5 1 PV Grid Connection Warning The fatal high voltage may on the DC side please comply with electric safety when connecting Please make sure the correct polarity of the cable connected with inverter otherwise inverter coul...

Страница 11: ...ox are correctly connected Use the AC plugs in the accessory The surge protector should be equipped between grid and inverter Disconnect the AC grid switch during wiring Installation 9 Warning The fatal high voltage may on the AC side please comply with electric safety when connecting Please make sure the right line of AC grid connected with inverter otherwise inverter could be damaged Step 1 Note...

Страница 12: ... DCA DCA DCB DCB N L DCA DCA DCB DCB N L Unscrew the row of screws insert the wire harness into the DCA DCA DCB DCB N L caps one by one and tighten the screws N Neutral line L Live line DCA DCA DCB DCB N L fix cover with screws 4x ...

Страница 13: ...rotective earth PE terminal to prevent electric shock And make sure this PE terminal is properly grounded Step 1 Step 2 3 5 mm Grounding terminal Note copper cable or aluminum cable more than 6mm Grounding terminal is connected to the inverter at left or right side ...

Страница 14: ...o Communication Configuration Instruction for detailed instruction Install the Wi Fi GPRS RS485 Communication 3 5 3 Communication Connection 4 Operation 4 1 Control Panel 1 3 5 2 4 UP DOWN ESC ENT 6 POWER FAULT COM I It te em ms s N No o I It te em ms s N No o 1 2 3 4 LCD Display ESC Touch Button UP Touch Button DOWN Touch Button 5 6 FAULT LED Indicator COM LED Indicator ENT Touch Button POWER LED...

Страница 15: ... Uersion M xxxx Version S xxxx Version S xxxx S N Machine Sxxxxxxxxx First Level Menu Second Level Menu Wifi Info IP Wifi 192 168 xx xx S N Wifi xxxxxxxxxx Error Record No Error Date Time Time H M S Date Year month day Set PassWord xxxx Upstream PassWord xxxx ...

Страница 16: ...Day Time Date Dd Mm 2015 Time Hh Mm Ss Waiting Xx Power XXW CY China Set Eng1G83 Nouns Explanation Inverter Info Display the serial number and firmware version of inverter Check the error list of inverter including date and time Display the WIFI serial number and assigned IP address Set date and time of the inverter Countercurrent Set the protection parameters of inverter Error Record WiFi Info Da...

Страница 17: ...ET Enter Enter Enter Enter Enter Enter Input Password Para Adj Para XXX Power Off and Restart Inverter Finish Para View Max VoLtage XXX Min VoLtage XXX Max FrEquency XXX Min FrEquency XXX Safety XXX Note The inverter need to be restarted to finish parameter setting ...

Страница 18: ...ordingly to local standards or regulations Commissioning Procedures Turn on the AC switch between inverter output and the public grid Turn on the DC switch on the inverter Turn on the PV switch of the system 5 Commissioning Sign Color Explanation COM Green On Off On Off On Off Green Red FAULT Inverter is feeding power Inverter is not feeding power at the moment Power On No Power Fault occurred No ...

Страница 19: ...uble shooting list to solve the problem Turn off the DC switch on the inverter Turn off the PV switch of the system Turn off the AC switch between inverter output and the public grid Follow the procedures below when the inverter needs to be restarted Follow the Shut Down Procedures of Article 6 to shut down inverter Follow the Commissioning Procedures of Article 5 to turn on the inverter 7 Mainten...

Страница 20: ...re down to the normal Or install the inverter at a well ventilated site replace the temperature sensor PV Over Fault PV input voltage high PV array s Voc high re design the PV array configuration measure the PV array voltage is the same as inverter displayed M Grid Volt Fault Grid voltage out of range grid voltage out of the setting range grid back to the normal the inverter will restart automatic...

Страница 21: ...9 1 EN50438 RD 1699 UNE 217001 RD 413 IEC61727 IEC62116 IEC61683 VDE4105 UL1741 VDE0126 AS4777 2 NB T 32004 2013 UNT C 15 712 1 ABNT NBR 16149 ABNT NBR 16150 PV Reverse Polarity Protec on PV Insula on Resistance Detec on AC Short Circuit Protec on AC Over Current Protec on AC Over Voltage Protec on An Islanding Protec on Residual Current Detec on Over Temperature Protec on Integrated DC switch Sur...

Отзывы: