Maintenance&Trouble Shooting 

22

Trouble-Shooting List 

Storage device fault

low start up power under low light 

conditons, inverter self-check procedure 

cannot be complete

The  inverter will restart automatically when the start up power is enough

Ground Fault Circuit Interrupter 

fault

1.ground leakage current high

2.PV(+) or PV(-)  earthed

1. check the AC output wring and restart the inverter

2. check PV array wiring

Grid Frequency fault

1. grid fluctuate

2. grid frequency out of setting range

1. grid back to the normal, the inverter will restart automatically

2. check inverter frequency setting range correct

3. check the AC output wiring well connected

 

Grid voltage fault

1. grid fluctuate

2. grid voltage unbalance between phase 

to phase

1. grid back to the normal, the inverter will restart automatically

2. check each phase's voltage via inverter LCD

Internal fault B

Bus voltage out of range

1. check PV input voltage (not bigger than

 

900Vdc per channel)

2. check the AC output wiring well connected

Internal fault D

Software over current fault

1. check PV array confirguration is correct

2. fluctuate on grid, wait for the grid back to the normal, the inverter

will restart automatically

Error Display

 

Error Message

 

Possible Fault

Correctie Measure

EepromErr

GFCI.Err

GridF.OutLim

GridV.OutLim

IntFaultB

IntFaultD

Internal fault E

Over current fault

grid back to the normal, the inverter will restart automatically

 

Internal fault G

DCI high

1.check each PV array's confirguration is correct

2..check the voltage difference between BUS+ and BUS- is too high

Internal fault K

Bus voltage fault

1.check the AC output wring well connect.Use stranded copper cable 

2.check PV array confirguration is correct 

3.check the voltage difference between BUS+ and BUS- is too high

 

 

 

IntFaultE

IntFaultG

IntFaultK

Internal fault M

Bus voltage fault

1.check the AC output wring well connect.Use stranded copper cable 

2.check PV array confirguration is correct 

3.check the voltage difference between BUS+ and BUS- is too high

 

IntFaultM

Internal fault N

Hardware fault

check the AC out put wring well connect.

Use stranded copper cable

IntFaultN

Internal protection A

Bias current protection

1. turn off AC, then DC circuit breaker, restart the inverter

2. replace the control board

IntProtectA

Internal protection B

Relay fault

turn off AC, then DC circuit breaker, restart the inverter

IntProtectB

Internal protection C

Inverter current protection

turn off AC, then DC circuit breaker, restart the inverter, check 

the each phases' AC voltage is correct through LCD

 

IntProtectC

Internal protection D

Boost current protection

turn off AC, then DC circuit breaker, restart the inverter

IntProtectD

Internal protection G

Bus voltage protection

1.check the AC output wring well connect.Use stranded copper cable

 2.check PV array confirguration is correct 

3.check the voltage difference between BUS+ and BUS- is too high

 

 

 

IntProtectG

Internal protection I

Bus voltage protection

1.check the AC output wring well connect.Use stranded copper cable 

2.check PV array confirguration is correct 

3.check the voltage difference between BUS+ and BUS- is too high

IntProtectI

Internal protection K

Bus over voltage protection

check the AC output wring well connect.Use stranded copper cable

IntProtectK

Internal protection N

Inverter over current protection

fluctuate on grid, wait for the grid back to the normal, the inverter 

will restart automatically

 

IntProtectN

Internal protection P

Frequency fault protection

frequency abnormal of grid, wait for the grid back to the normal, 

the inverter will restart automatically

 

IntProtectP

Internal protection Q

DCI protection

1.1.check PV array confirguration is correct 

2.check the voltage difference between BUS+ and BUS- is too high

 

IntProtectQ

Internal protection R

DCI circuit protection

 

1.turn off AC, then DC circuit breaker, restart the inverter

2. replace the control board

 

IntProtectR

IntProtectT

Internal protection T

PV over current protection

turn off AC, then DC circuit breaker, restart the inverter

IsolationErr

Insulation resistance fault

Insulation resistance low

check the resistance between PV(+) and ground, PV(-) and 

ground bigger than 2MΩ.

 

PVVoltOver

PV voltage high

PV over voltage

check PV array confirguration is correct

SPICommErr

SPI fault

SPI communication fault

check the RS485 cable is well connect

 

TempOver

Over temperature

Over temperature

1. turn off the inverter still the temperature down to the normal. 

Or install the inverter at a well ventilated site. 

2. check the heat sink and the fans is working

TempSensorErr

Temperature sensor fault

Temperature sensor fault

1. turn off AC, then DC circuit breaker, restart the inverter 

2. replace the temperature sensor

 

Содержание BNT050KTL

Страница 1: ...Installation and Operation Manual On Grid PV Inverter ...

Страница 2: ...trical Connection 3 5 1 PV Connection 3 5 2 Grid Connection 3 5 3 Earth Connection 3 5 4 Communication Connection WIFI Ethernet GPRS RS485 4 Operation 4 1 Control Panel 4 2 Menu Structure 4 3 Startup Setting 5 Commissioning 6 Shut Down Restart the Inverter 6 1 Shut Down Procedures 6 2 Restart the inverter 7 Maintenance Trouble Shooting 7 1 Maintenance 7 2 Fault Code and Trouble Shooting 8 Specific...

Страница 3: ...ualified personnel Three Phase BNT050KTL BNT060KTL Please keep this manual all the time available in case of emergency About This Manual 01 The typical connection diagram for the entire PV system is on grid Circuit Breaker Circuit Breaker 1 Surge Protective Device DCA1 DCA1 PE N L 3 PV Inverter PVA1 AC Grid Circuit Breaker 2 Surge Protective Device Surge Protective Device DCA2 DCA2 PVA2 Circuit Br...

Страница 4: ...roof Do not expose the inverter to water rain snow or spray 8 Alternative uses modifications to the inverter not recommended The warranty can become void if the inverter was tampered with or if the installation is not in accordance with the relevant installation instructions Safety Symbols 02 BNT050KTL BNT060KTL 75 90 100 125 Type Max AC Current A Rate current of AC breaker A Circuit Breaker and S...

Страница 5: ...C 140 F under high power operation Do not touch the inverter enclosure when operation Residual power discharge Do not open the inverter cover until 5 minutes after disconnection both DC and AC power supply Do not dispose of this device with the normal domestic waste Important notes Read all instructions carefully Failure to follow these instructions warnings and precautions may lead to device malf...

Страница 6: ...hown as below Instruction 04 No 1 2 3 4 5 6 7 1 1 1 1 1 1 5 Solar Inverter Certificate Of Inspection Quick Installation Instructions Warranty Card 8 9 10 11 12 13 5 12 1 1 2 1 Mounting Bracket Screw DC Connector sets Monitor Module Zero Injection Connector Optional Security Screw Screwdriver For Security Screw Wall Mounting Bracket Grounding Terminal Plastic Expansion Tube Qty Items No Qty Items 6...

Страница 7: ...g figures show the assignment of the individual connection areas on the bottom of the inverter Installation 05 3 2 Product Overview No 1 2 3 DC Switch DC Connectors For PV Strings DC Connectors For PV Strings Items 306mm 850mm 630mm 3 7 1 2 4 5 6 ...

Страница 8: ... surface far from flammable or corrosion materials where is suitable for inverter s weight and dimensions The ambient temperature should be within 25 60 between 13 F and 140 F The installation of inverter should be protected under shelter Do not expose the inverter to direct sunlight water rain snow spray lightning etc Installation 06 3 3 Mounting Location No 4 5 6 7 Zero Injection Port Optional M...

Страница 9: ...led vertically on the wall or lean back on plane with a limited tilted angle Please refer to below picture Leave the enough space around inverter easy for accessing to the inverter connection points and maintenance 300mm 300mm 500mm 500mm 0 30 Max ...

Страница 10: ...allation 08 3 4 Installation On grid PV Inverter Step 1 Step 2 Step 2 410mm 550mm Check to ensure the inverter is correctly seated Security screw Security screw Make sure to lock it with the security screws ...

Страница 11: ... ground must exceed 10 kΩ The polarity from PV strings are correct Use the DC plugs in the accessory The lightning protector should be equipped between PV strings and inverter Disconnect all of the PV DC switch during wiring 3 5 1 PV Connection Warning The fatal high voltage may on the DC side please comply with electric safety when connecting Please make sure the correct polarity of the cable con...

Страница 12: ...ion 10 MC STOP MC MC STOP MC Step 3 Note It is strongly recommended to connect by 12 strings of panels for models of 12 sets of DC connectors Note You ll hear click sound when the connector assembly is correct ...

Страница 13: ...correctly connected Use the AC plugs in the accessory The surge protector should be equipped between grid and inverter Disconnect the AC grid switch during wiring Installation 11 3 5 2 Grid Connection Warning The fatal high voltage may on the AC side please comply with electric safety when connecting Please make sure the right line of AC grid connected with inverter otherwise inverter could be dam...

Страница 14: ...Installation 12 Step 3 Unscrew the row of screws insert the wire harness into the W U V N caps one by one and tighten the screws N Neutral line W V U Live line Step 2 W U V N W U V N ...

Страница 15: ...prevent electric shock And make sure this PE terminal is properly grounded Installation 13 3 5 3 Earth Connection Step 1 Step 2 3 5 mm Grounding terminal Note copper cable or aluminum cable more than 6mm Grounding terminal is connected to the inverter at left or right side ...

Страница 16: ...nsmit the data to the cloud server and display the data on the PC tablet and smart phone Wi Fi GPRS RS485 communication is applicable to the inverter Please refer to Communication Configuration Instruction for detailed instruction Install the Wi Fi GPRS RS485 Communication Step 1 Fasten ...

Страница 17: ...lectricity the inverter will active export power limit function based on the monitoring data Please refer to Zero injection Smart Meter Instruction for detailed instruction Step 2 13 14 16 17 19 21 24 25 1 4 7 10 13 14 16 17 19 21 24 25 1 2 3 8 PIN Assignment RS485 A PIN 24 RS485B PIN 25 Zero Injection Port pin assignment 12345678 RJ45 Plug ...

Страница 18: ...on ENT Touch Button RUN LED Indicator 1 3 5 2 4 6 UP DOWN ESC ENT RUN FAULT GRID POWER Grid Load PV Inverter Distribu on Cabinet L1 L1 L2 L3 L2 L3 PV Array RS485 WiFi Ethernet GPRS Afore Smart Meter PV Array PV Array Router Cloud Server Weather Sta on Energy Meter PV Inverter PV Inverter Note The Inverter could be connected in parallel with Smart Meter make sure the total load power not exceed Sma...

Страница 19: ...xx ISONGb xx Case_Temp xx C Info Modletemp xx C ScreenTemp xx C Bus xxV Bus xxV RunTime xxxHr SumTime xxxHr Ia xx Ib xx Ic xx Fac Hz Vac V Ua xx Ub xx Uc xx Iac A AC Output System Date Time Date xx xx xxxx Time xx xx xx English Polish 中文 Language Country Energyk xxx x Energyk Etotal x x kwh Etotal Reset Clear ErrRecord Clear RunRecord Factory Reset Enter User PassWord Enter User PassWord Enter Use...

Страница 20: ... the error list of inverter including date and time Set the protection parameter of inverter Development function unavailable View WIFI SN and IP address WIFI info View the inverter information Voltage current power and so no Error Record SET ON OFF Check the software version of the control board and display board Version System ...

Страница 21: ...fo Version System Info Power 60 000KW 15 6 KWh 497000KWh RUNNING 110 50 0 5 8 11 14 1720 23 t P 11 11 2019 11 00 EDay EAll State Enter Enter UP DOWN Lock setting Language Date Time Country EnergyK Etotal Reset Clear ErrRecord Clear RunRecord Factory Reset SET UP DOWN Adjust the time Date XXXX XX XX Time XX XX XX Date Time SET System Running Protection Communication ...

Страница 22: ...lations Commissioning Procedures Turn on the AC switch between inverter output and the public grid Turn on the DC switch on the inverter Turn on the PV switch of the system 5 Commissioning UP DOWN ESC ENT RUN FAULT GRID POWER FAULT Red LED Green LED Green LED GRID Green LED RUN POWER LED Indication On Off Green GRID Normal grid connection Non grid Sign Color Explanation POWER Green On Off On Off G...

Страница 23: ...oblem Turn off the DC switch on the inverter Turn off the PV switch of the system Turn off the AC switch between inverter output and the public grid Follow the procedures below when the inverter needs to be restarted Follow the Shut Down Procedures of Article 6 to shut down inverter Follow the Commissioning Procedures of Article 5 to turn on the inverter Shut Down Restart the Inverter 21 7 Mainten...

Страница 24: ...control board IntProtectA Internal protection B Relay fault turn off AC then DC circuit breaker restart the inverter IntProtectB Internal protection C Inverter current protection turn off AC then DC circuit breaker restart the inverter check the each phases AC voltage is correct through LCD IntProtectC Internal protection D Boost current protection turn off AC then DC circuit breaker restart the i...

Страница 25: ...YES YES YES YES YES YES YES Integrated Type II YES YES YES YES YES YES YES YES YES YES YES RS485 WiFi Wire Ethernet GPRS op onal Intelligent Fan Cooling 55 1 4000 630 x 850 x 306 77 IP65 Aluminum 25 60 Transformerless 0 100 EN IEC 61000 6 2 EN IEC 61000 6 3 EN61000 3 2 EN61000 3 3 EN61000 3 11 EN61000 3 12 EN IEC 62109 1 2 UL1547 IEC 60068 2 EN50549 1 EN50438 RD 1699 UNE 217001 RD 413 IEC61727 IEC...