The three-phase on-grid PV inverters work with grid (380/400/415/440 Vac,
50/60 Hz).
The external AC switch should be installed between inverter and grid to isolate
from grid. Please make sure below requirements are followed before connecting
AC cable to the inverter.
·
The AC (grid) voltage must not exceed inverter’s range
·
The phase-line from AC distribution box are correctly connected
·
Use the AC plugs in the accessory
·
The surge protector should be equipped between grid and inverter
·
Disconnect the AC (grid) switch during wiring
Installation
11
3.5.2 Grid Connection
Warning:
The fatal high voltage may on the AC side, please comply with
electric safety when connecting.
Please make sure the right line of AC grid connected with inverter,
otherwise inverter could be damaged.
Remove the waterproof cap at the AC wiring under the inverter, pass the cable
through the cap, and open the inverter cover.
Sectional Area > 10mm²
Step 1
10±0.5mm