Annex 1 General Technical Data
Model
Carbon CS
Carbon CM
Carbon BS
Carbon BM
Carbon BL
Gross weight extinguishing agent
in grams
720
1,440
4,800
9,600
14,400
Net weight extinguishing agent in
grams
317
634
2,112
4,224
6,336
Fire Classes
A & B
A & B
A & B
A & B
A & B
Activation mechanism
heating element with 6.1 – 7.5 Ohm resistance
Activation current
1.5 Ampère for 1 - 2 seconds, 12/24 Volt DC
Test current
< 0.02 Ampère within x minutes
Gross weight in kilograms
2.7
4.0
14.2
18.7
29.4
Casing
Steel
Steel
Steel
Steel
Steel
Shape
Cylinder
Cylinder
Square
Square
Square
Dimensions in mm
94
⍉
x310
94
⍉
x450
250x250x213
250x250x304
250x250x457
Outflow time in seconds
< 60s
< 60s
< 120s
< 120s
< 120s
Outflow Length in meters
(projection)
> 3m
> 5m
> 4m
> 6m
> 8m
Discharge openings
1
1
1
1
1
Minimum installation height
25cm
25cm
50cm
50cm
50cm
Maximum installation height in
centimetres (coverage)
3m
5m
4m
6m
8m
Outflow length max. temperature
75°C
< 1m
< 1m
< 2m
< 2m
< 2m
Outflow length max. temperature
200°C
< 25cm
< 25cm
< 50cm
< 75cm
< 100cm
Outflow length max. temperature
400°C
< 0 cm
< 0 cm
< 0 cm
< 0 cm
< 0 cm
NB:
The system design and applicability per m3 of the AF-X Fireblocker extinguishers are prescribed
by the manufacturer, recorded in the systems log and cannot be changed by third parties without loss
of warranty.