Please keep this user manual for future use. It will expire upon
publication of a revised issue. The latest version is available with your
distributor, dealer or at AF-X Systems BV.
User Manual AF-X Fireblocker Carbon Based Fire Extinguishers version 2.2
14
8.
In areas higher than 2m, generators should be placed in the meter of space directly below the ceiling.
For high area’s (e.g. higher than 8m), it may be advisable to work with two ‘installation rings’. Please
consult the AF-X Systems experts when designing systems for areas of such height.
High areas, placed within one meter below ceiling:
9.
It is of the utmost importance that there are no obstacles in front of the discharge opening for a distance
of at least the length of the AF-X generator itself.
Avoid obstacles in front of discharge opening:
5.10 Mounting guidelines AF-X Fireblocker Carbon generators
Please note that the AF-X Fireblocker generators should be mounted in static environments.
a)
Please study the entire systems’ projection plan carefully before mounting any generator.
b)
Systems with a fire extinguishing control panel should at all times contain a maintenance switch separating
the extinguishing units from the control panel during installation as well future maintenance activities.
c)
For the installation of cables use the cables sold and/or advised by AF-X Systems only and make sure that
they are installed neatly, systematically and securely. Follow the cable manufacturer’s guidelines regarding
the installation of cables closely.
d)
De AF-X Fireblocker generators are standard equipped with an IP55 connector chassis with a female inlay
(cf. product drawing). Using the proper tools, the installer must equip the control cable with a cable gland,
a hood and a male inlay, that AF-X Systems supplies.
e)
The male insert is properly connected to the (massive core) control cable with a stripping length of 15mm
to pole number 1 and pole number 2, using a maximum torque of 0,5 Nm. The AF-X Fireblocker is not
earthed.