- 25 -
E13
Fan failure
System shutdown, fault
reported
Check whether the fan motor and
outdoor PCB are damaged.
E14
TH suction gas temp
sensor failure
System shutdown, fault
reported
Check TH suction gas temp sensor
and outdoor PCB.
E15
Driver EE failure
System shutdown, fault
reported
Check drive board.
E16
Indoor unit PCB EE
failure
System shutdown, fault
reported
Check indoor unit PCB.
E17
Low pressure switch
failure
System shutdown, fault
reported
Check low pressure switch, and
outdoor PCB.
E18
High pressure switch 1
failure
The fault is detected only
when the compressor
shuts down and reported
as a fault.
Check high pressure switch 1, and
outdoor PCB.
E19
High IPM module
temperature
System shutdown, fault
reported
Check drive board.
E20
Instant power failure
System shutdown, fault
reported
Check drive board.
E22
TJ2 economizer inlet
sensor failure
System shutdown, fault
reported
Check TJ2 inlet temp sensor and
outdoor PCB.
E23
TJ economizer oulet
sensor failure
System shutdown, fault
reported
Check TJ outlet temp sensor and
outdoor PCB.
E24
TA inlet water temp
sensor failure
System shutdown, fault
reported
Check TA inlet water temp sensor
and outdoor PCB.
E25
TB plate heat
exchanger outlet water
temp sensor failure
System shutdown, fault
reported
Check TB plate heat exchanger
outlet water temp sensor and
outdoor PCB.
E26
Flow switch FS1
protection
(
Outdoor
unit
)
System shutdown, fault
reported
Check water pump,flow switch 1
and outdoor PCB.
E27
Low water flow
protection
System shutdown, fault
reported
Check water pump and outdoor
PCB.