G-Model Inverter Heat Pump
14
F. Testing
1. Inspect heat pump before use
a. The ventilating device and outlets are operating adequately and are not obstructed.
b. It is prohibited to install refrigeration pipe or components in corrosive environment.
c. Inspect the electrical wiring according to the electrical wiring diagram and ground
connection.
d. Double-check that the main power supply to the unit is off.
e. Check the air inlet and outlet.
2. Leakage detection notice and method
a. Leakage checking is prohibited in closed areas.
b. Naked flames are prohibited during the leakage inspection. A halide torch (or any
other detector using a naked flame) must not be used.
c.
Leakage detection fluids can be applied with most refrigerants but the use of detergents containing
chlorine must be avoided as the chlorine may react with the refrigerant and corrode the copper pipe.
d. Vacuum completely before welding. Welding can only be carried out by professional personnel in
service center.
e. If there is any gas leakage, please stop using the unit and contact professional a service center.