AES 7068 Скачать руководство пользователя страница 4

AES•

IntelliNet  Central Alarm Reporting System

08/18/00  - 4000571.p6 

   Rev B    

40-0571

AES•

IntelliTAP  Satellite / Remote Dialer Data Receiver

Page 4

40-0571

LINE CUT MONITOR PROGRAMMING  

Refer to Figures 1 + 2

The TAP can detect and report a telephone line cut. The TAP determines that the line is cut when the voltage across termi-

nals 1 and 2 drops below approximately 2.5 volts for a programmable period of time. The line cut function is enabled and

its parameters are set using jumpers 6 and 7 (see figures 1+2).

• Line cut monitor:
    - with 1 minute delay = Jumper on 7
    - with 2 minute delay = Jumper on 6
    - with 3 minute delay = Jumpers on 6 AND  7
• No Phone Line Used, and No Line Cut Monitor = No Jumper
• Push Reset Switch (S1) on TAP after setting jumpers.
• The line cut function can also be used to supervise the line between the alarm panel and the subscriber unit. See
page 8 in this manual for details.

PROGRAM PHONE NUMBER INTO THE TAP AND ALARM PANEL - 

Refer to Figures 1 + 2

Select Phone Number and Type:

 You must select which phone number the TAP is to respond to. Select either the

short (5-5-5) or long (any 15 digit number ending in 2-3-7).
• The short number is usually used when the TAP is not connected to an active telephone line.
• The long 15 digit number ending in 2-3-7 is preferred when the TAP is connected to an active telephone line. This

allows you to dial a non-obtrusive number and prevent intercept tone, which may occur during TAP and panel commu-

nications when using the short number.

"Short" 3-digit telephone number

 - Remove jumper on position 5. Program the alarm panel dialer phone number

with the digits 

5-5-5. 

During a reported event, the phone line is quiet after the 5-5-5 is dialed as it waits for more

digits.  During this period, the TAP provides an answer tone, signalling to the alarm panel to transmit its data, and then

kisses it off.  The control panel then hangs up the line. Test the setup - see next page.

"Long" 15-digit telephone number 

- Install jumper on position 5. Program the alarm panel with a 15 digit phone

number ending with 2-3-7 (A-E-S).  Any numbers can be used, but 

the last 3 numbers must be 2-3-7. 

 Suggestion:

Program the first digits with the phone number of the line in use. Add additional digits to fill up to digit #12. Avoid

using dual digits such as 11 or 12.  During a reported event, this results in "dead air" or a busy signal on the phone line,

but data can usually be conveyed from alarm panel to the TAP if the alarm panel is capable. The control panel then

hangs up the line.

 Test to make sure this works: If you get a telephone company interrupt tone - a loud series of

tones followed by a voice announcement ("Your call did not go through...") 

before

 alarm data has been commu-

nicated, this method will 

not

 work. Test the setup - see next page.

NOTE - If Alarm Panel CANNOT Blind Dial,

  AND you are using a phone line AND you are programming the TAP

for Line Cut: If the telephone line is cut, the line cut will be reported by the TAP, but because the alarm panel cannot

blind dial, no alarm data will be transmitted.

Program the Alarm Panel to Dial the TAP

Follow the alarm panel manufacturer's procedure and enter the appropriate telephone number into the dialer:
• Use "5-5-5" if you've selected the "short" number for the TAP.
• Use a 15 digit number ending in "...2-3-7" if you selected the "long" number for the TAP.

Содержание 7068

Страница 1: ...4 Tap with Phone Line RJ31X 5 Figure 5 Tap with Phone Line w o RJ31X 6 Figure 6 Tap with No Phone Line 6 Figure 7 Tap No Phone Line Can t Blind Dial A 6 Figure 8 Tap No Phone Line Can t Blind Dial B...

Страница 2: ...F 7450 Radio Subscriber Units with Version ESB SUB 1 71 or later Central Receiver Compatibility 7000 2 7000 1 7099 7701 Net77 and 7703 receivers will accept TAP packets Some earlier versions may requi...

Страница 3: ...format has been evaluated by UL 3 1 4 1 4 2 format with 1400Hz answer tone Jumper on 2 only 3 1 4 1 4 2 format with 2300Hz answer tone Jumper on 3 only Note For 3 1 4 1 4 2 program your alarm panel f...

Страница 4: ...rm panel dialer phone number with the digits 5 5 5 During a reported event the phone line is quiet after the 5 5 5 is dialed as it waits for more digits During this period the TAP provides an answer t...

Страница 5: ...th NA Yes pg7 RJ31X Check capabilities of Alarm Panel A t t a c h t o P h o n e L i n e A l a r m P a n e l C a n B l i n d D i a l I n s t a l l a t i o n R e q s D e t e c t i o n o f T o n e S o u...

Страница 6: ...m the panel with the phone number 5 5 5 Make sure there is NO jumper on position 5 Test the setup by generating an event on the alarm panel 1 2 3 4 5 6 T R T1 R1 Figure 6 AES 7068 INTELLITAP ALARM PAN...

Страница 7: ...that the TAP can differentiate between a house phone off hook and an alarm panel dialing If this works as described here proceed to the next step If this test provides different results check wiring t...

Страница 8: ...enough outputs you can send general alarms for more specific clarification such as General Fire Burglary Panic etc The backup zone activation is immediate and will likely activate faster than the TAP...

Страница 9: ...2 Figure 13 Important Note Observe polarity when connecting to ERR or IP outputs Incorrect connections of output can damage the 7068 circuit board Open Collector Open Collector 12V IP Output for Alarm...

Страница 10: ...f data from the alarm panel to the TAP Here is a typical wiring diagram R1 T1 R T RJ31X JACK TIP RING TERMINALS ON ALARM CONTROL PANEL PREMISES PHONES INCOMING PHONE LINE 1 2 3 4 5 6 BROWN T TIP RING...

Страница 11: ...te The automation output will send Contact ID information from the alarm panel including the panel ID number In a line cut situation the Subscriber ID number is used FCC Compliance This device complie...

Отзывы: