AES•
IntelliNet Central Alarm Reporting System
08/18/00 - 4000571.p6
Rev B
40-0571
AES•
IntelliTAP Satellite / Remote Dialer Data Receiver
Page 11
40-0571
CENTRAL RECEIVER
COMPATIBILITY and REQUIREMENTS
Central Receiver Compatibility:
All current AES receivers 7000/2, 7000/1, 7099, 7701/Net77 and 7703 receivers will
accept TAP signals. Some earlier versions may require an upgrade. If there are any questions, have the central station contact
technical support at AES Corporation at tel 978-535-7310.
7000 Series (7000/2, 7000/1 and 7099)
require version CEN 1.71 network controller board and version ALM 1.72 alarm
output or higher. These receivers will print the TAP messages on the event printer and pass the signal to alarm automation
properly.
7701 with 7700 and Net77 software requires
Net77 version 1.48.4CT, 1.48.4CTD, 1.48.30 or later.
Important Note:
The 7701 receiver with firmware of 1.65 or earlier will not print TAP messages on the event printer. If
Net77 is not running for any reason, the TAP alarm cannot be reported. Thus it is mandatory that at least one zone of the
Subscriber Unit must be activated for any system using the 7701 receiver with 1.65 or earlier firmware.
For Net77 version 1.48.30, TAP messages are sent out the automation port with all other signals.
For Net77 version 1.48CT and 1.48CTD send TAP messages to automation out Com port 3.
All AES 7703 and KELTRON RF7300 Receivers
are compatible with the TAP.
Note: The automation output will send Contact ID information from the alarm panel, including the panel ID number. In a line
cut situation, the Subscriber ID number is used.
FCC Compliance
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) This device must accept any interference received
including interference that may cause undesired operation.
UL / cUL Compliance Notes
Only Contact ID format has been evaluated by UL.
The 7068 IntelliTAP unit has been investigated by UL for Supplemental Use Only.
The 7068 IntelliTAP unit must be mounted inside the AES Subscriber Unit.
The 7068 IntelliTAP unit has been evaluated to the following Standards:
USL:
UL 609 (10th ed) - Local Alarm Units and Systems
UL 365 (4th ed) - Police Station Connected Burglar Alarm Units and Systems
UL 1610 (2nd ed) - Central Station Burglar Alarm Units
UL 864 (8th ed) - control Units for Fire-Protective Signaling Systems
CNL:
CAN/ULC-S527-M87 (1st ed) - Standard for Control Units for Fire Alarm Systems (amend 1995)
ULC Subject C1023-1974 (1st ed) - Preliminary Standard for Household Burglar Alarm System Units
CAN/ULC-S545-M89 (1st ed) - Standard for Residential Fire Warning System Control Units (amended 1995)
CAN/ULC-S303-M91 (1st ed) - Standard for Local Burglar Alarm Units and Systems
CAN/ULC-S304-M88 (1st ed) - Standard for Central and Monitoring Station Burglar Alarm Units
ORD-C1076-1986 (5th ed) - Proprietary Burglar Alarm Units and Systems
Electrical Rating: 12VDC nominal
Current: Typical: 50ma
(no load on ERR or IP outputs)
Maximum: 450ma
(with max load on ERR and IP outputs)