Aerovent BSBP Скачать руководство пользователя страница 4

Aerovent Installation and Maintenance Manual IM-172

Figure 2. Low End Setpoint Adjustment

NOTE:

  5  amp  model  shown.  On  10  and  15 

amp  models,  adjustment  is  made  through 

clearance hole in heat sink.

SETPOINT

ADJUSTMENT

SCREW

Table 1. Speed Controller Size

MOTOR

SPEED CONTROLLER 

DESIGNATION / FLA

HP

RPM

VOLTAGE

KBWC-15K 

5 AMP

KBWC-110 

10 AMP

KBWC-115 

15 AMP

1/8

1650/1500/

1350

115V

X

1/8

860

115V

X

1/6

860

115V

X

1/4

860

115V

X

1/2

860

115V

X

1/6

1140

115V

X

1/4

1140

115V

X

1/2

1140

115V

X

1

1140

115V

X

1/3

1725

115V

X

1/2

1725

115V

X

3/4

1725

115V

X

Speed Control Installation

The  controller  is  designed  to  start  the  motor  at  high 

speed  and  will  then  slow  down.  This  gives  the  motor 

good starting characteristics.
Speed  control  is  available  using 

115/60/1  open

  type 

PSC or shaded pole motors.

Installation

Connect  control  in  series  with  motor  and  line  voltage 

(

115V only

). Never connect across line. See Figure 1.

Minimum Speed Setpoint

All controls are factory set to 65V±3V output as standard 

with  an  input  voltage  of  120V.  If  different  minimum 

speed is desired, the control may be adjusted by turning 

minimum  speed  pot  clockwise  to  decrease  minimum 

speed and counterclockwise to increase minimum speed. 

Refer to Figure 2.

Figure 1. Connection Diagram, Speed Control

SPEED CONTROLLER

AC

LINE

(115V)

SWITCH TRI-AC

MOTOR

Table 2. Speed Controller RPM Range

NOTES:

1.  Speed  control  available 

only

  with  115/60/1  open  motors  (thermally 

protected).

2.  Three-speed motor (multiple tap winding).

3.  Speed control 

should not

 be connected to low speed tap on motor 

because of starting characteristics.

4.  Speed control connected to high speed tap on motor.

5.  Speed control connected to medium speed tap on motor.

HP

RPM

MAX. RPM

MIN. RPM

1/8

1650/1500/1350

2,3

1650

4

1300

4

1500

5

950

5

1/8

860

860

500

1/6
1/4
1/2
1/6

1140

1140

900

1/4
1/2

1

1/3

1725

1725

1200

1/2
3/4

If  minimum  speed  is  readjusted,  verify  unit  ampere 

draw  does  not  exceed  motor  nameplate  amps.  Do 

not  operate  unit  in  range  where  amp  draw  exceeds 

motor nameplate.

WARNING

These motors operate more efficiently in the ranges 

set from the factory. Operating motor outside these 

ranges (see Table 2) may cause motor to run hotter 

and substantially shorten motor life.

CAUTION

Lowering the minimum speed setpoint may adversely 

affect motor start-up characteristics.

NOTICE

Certain  failure  modes  of  solid-state  controls  such 

as  half-waving  can  cause  high  levels  of  DC,  motor 

overheating and motor burn-out. Therefore, a thermal 

overload protection (integral with motor) is required 

to limit the maximum motor temperature under such 

a failure.

WARNING

Do  not  allow  any  sleeve  bearing  motor  to  operate 

below  500  RPM.  Operation  below  500  RPM  will 

substantially shorten bearing life.

NOTICE

Содержание BSBP

Страница 1: ...mpellers Only Throughout this manual there are a number of HAZARD WARNINGS that must be read and adhered to in order to prevent possible personal injury and or damage to equipment Two signal words WARNING and CAUTION are used to indicate the severity of a hazard and are preceded by the safety alert symbol WARNING Used when serious injury or death MAY result from misuse or failure to follow specifi...

Страница 2: ...LITY OR FITNESS FOR A PARTICULAR PURPOSE In no event shall seller be liable to buyer for indirect incidental collateral or consequential damages of any kind BUYER S FAILURE TO PAY THE FULL AMOUNT DUE WITHIN SIXTY 60 DAYS OF DATE OF INVOICE SHALL OPERATE TO RELEASE SELLER FROM ANY AND ALL LIABILITY OR OBLIGATION ARISING PURSUANT TO ANY WARRANTY EXPRESS OR IMPLIED WHETHER STATUTORY OR OTHERWISE INCL...

Страница 3: ...es or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 A ground lug is provided as standard in the unit terminal box Size grounding conductor in accordance with Table 250 95 of the National Electrical Code DO NOT use the ground lug for connecting a neutral conductor 7 Supply voltage to the power ventilator should not vary by more than 10 of the val...

Страница 4: ... Control SPEED CONTROLLER AC LINE 115V SWITCH TRI AC MOTOR Table 2 Speed Controller RPM Range NOTES 1 Speed control available only with 115 60 1 open motors thermally protected 2 Three speed motor multiple tap winding 3 Speed control should not be connected to low speed tap on motor because of starting characteristics 4 Speed control connected to high speed tap on motor 5 Speed control connected t...

Страница 5: ...which may lead to premature failure and to prevent the impeller blades from hitting the actuator on motorized damper units Use general installation procedure from page 4 IMPELLER SIZE PANEL SQ WALL OPENING MIN DAMPER SIZE M MIN SURFACE MOUNT RECESS IN WALL BSBP BSDDP BSBP BSDDP BSBP BSDDP BSBP BSDDP 14 17 00 14 50 17 50 14 x 14 16 00 16 20 00 17 50 20 50 17 x 17 18 22 00 19 50 22 50 19 x 19 21 25 ...

Страница 6: ... Motor Side Guard Backdraft Damper Weatherhood Damper Guard Bird Screen Wall Collar Disconnect Switch O F F O N Removable Screen Panel Fan Wall Box Backdraft Damper Weatherhood Bird Screen Damper Guard Disconnect Switch WALL COLLAR WITH ACCESSORIES BSBP BSDDP WALL BOX WITH ACCESSORIES BSBP BSDDP ...

Страница 7: ...REEN BACKDRAFT DAMPER MOUNTING FLANGE REMOVABLE GUARD SCREEN AIR FLOW FAN SUPPORTS BY OTHERS Flush with Interior Wall WEATHERHOOD WITH SCREEN BACKDRAFT DAMPER MOUNTING FLANGE REMOVABLE GUARD SCREEN AIR FLOW FAN SUPPORTS BY OTHERS WEATHERHOOD WITH SCREEN BACKDRAFT DAMPER MOUNTING FLANGE SUPPORTS BY OTHERS FAN REMOVABLE GUARD SCREEN AIR FLOW WEATHERHOOD WITH SCREEN BACKDRAFT DAMPER MOUNTING FLANGE R...

Страница 8: ...wire to enter the collar Be sure the metal edges of the hole are protected so the wire will not get cut 5 If a damper weatherhood or damper guard screen are being used they can be fastened to the collar before the collar is fastened to the frame 6 Make sure the edges around the collar and frame are sealed after it is installed The wall box is installed in the same way SIZE COLLAR WALL BOX SQ WALL ...

Страница 9: ...perpendicularly to the rotating shafts Fan and motor shafts must be parallel Improper alignment will result in excessive belt wear 9 Check sheave setscrews to ensure tightness Proper keys must be in keyways 10 Do not readjust blade pitch or fan RPM If sheaves are replaced use only sheaves of identical size and type 11 If unit is to be left idle for an extended period it is recommended that belts b...

Страница 10: ...mpeller may need to be temporarily installed to get its clearances equal 12 Tighten the bearing mounting bolts 13 Reinstall the lube tubes if applicable 14 Install impeller and belts and adjust the motor to get proper belt tension Also make sure that the sheaves are properly aligned 15 If a new shaft is supplied ignore items 6 thru 8 Aerovent recommends periodic checks of voltage frequency and cur...

Страница 11: ...ill occur Recommended belt tension should permit 1 64 deflection per inch of span of the belt at the center of the belt span To find this point measure halfway between the pulley centerlines as shown in Figure 6 Extreme care must be exercised when adjusting V belts as not to misalign the pulleys Any misalignment will cause a sharp reduction in belt life and will also produce squeaky annoying noise...

Страница 12: ...on of material on impeller 4 Worn or corroded impeller 5 Impeller out of balance 6 Impeller hitting housing 7 Bent shaft 8 Bearings need lubrication 9 Loose bearing bolts 10 Loose or worn bearings 11 Mismatched belts 12 Belts too loose or too tight 13 Belts oily or dirty 14 Belts worn 15 Loose fan mounting bolts 16 Rattle of components in high velocity airstream 17 Electrical noise 18 Noise from h...

Страница 13: ...XHAUST SUPPLY 14 14 25 2 75 17 11 18 14 88 14 x 14 56 16 16 25 3 00 20 11 18 14 88 17 x 17 56 18 18 25 3 00 22 11 18 14 88 19 x 19 56 21 21 25 3 50 25 14 41 17 36 22 x 22 145T 24 24 25 3 50 28 14 55 17 36 25 x 25 184T 30 30 38 4 00 36 14 74 19 05 33 x 33 184T 36 36 38 5 00 42 15 67 19 93 39 x 39 215T 42 42 38 5 50 48 23 59 30 00 45 x 45 254T 48 48 38 6 00 54 23 59 30 00 51 x 51 254T Exhaust Airflo...

Страница 14: ...4T 36 36 38 5 00 42 17 50 19 13 21 50 23 13 39 x 39 145T 184T 42 42 38 5 50 48 17 88 19 38 22 19 23 75 45 x 45 145T 184T 48 48 38 6 00 54 18 75 20 13 23 06 24 63 51 x 51 145T 184T 54 54 38 6 50 60 18 88 20 50 23 69 25 19 57 x 57 145T 184T 60 60 38 7 25 66 19 50 24 75 24 44 29 94 63 x 63 145T 215T Exhaust Airflow Supply Airflow AIR FLOW AIR FLOW 2 00 2 00 A DIA A DIA D MAX D MAX C SQ OUTSIDE B B BS...

Страница 15: ... DIA A DIA BSBP SIZE A B C SQ D MAX DAMPER SIZE MAX MOTOR FRAME EXHAUST SUPPLY 42 42 38 5 50 48 21 31 26 75 45 x 45 215T 48 48 38 6 00 54 21 31 26 75 51 x 51 215T 54 54 38 6 50 60 26 13 32 30 57 x 57 254T 60 60 38 7 25 66 26 13 32 30 63 x 63 256T Exhaust Airflow Supply Airflow BSBP Belt Driven Level 3 Sizes 42 60 ...

Страница 16: ...WWW AEROVENT COM 5959 Trenton Lane N Minneapolis MN 55442 Phone 763 551 7500 Fax 763 551 7501 ...

Отзывы: