background image

Aerovent Installation and Maintenance Manual IM-172 

3

Check, Test & Start Procedure

1. Check to verify that the impeller is free to rotate.
2. Verify  that  supply  voltage  on  the  line  side  of 

disconnect agrees with voltage on fan data plate and 

is within the 10% utilization voltage.

3. Apply  power  to  unit  and  check  rotation  of  impeller 

with the directional arrow on the unit. 

4. 

Electrical Input Check:

 Perform check of fan ampere 

draw and verify that motor nameplate amps are not 

exceeded. Take into account the service factor range 

if motor is nameplated above a 1.0 service factor.

5. Fan  RPM  should  be  checked  and  verified  with  a 

tachometer.

Electrical Connection

 1.  Connect supply wiring to a disconnect switch. Check 

the wiring diagrams on the motor for connections.

 2.  The motor is factory set at the voltage marked on 

the fan nameplate. Check the line voltage with the 

nameplate voltage and wiring diagrams.

 3.  The  main  power  wiring  should  be  sized  for  the 

ampacity  shown  on  the  dataplate.  Size  wires  in 

accordance with the ampacity tables in Article 310 

of  the  National  Electrical  Code.  If  long  wires  are 

required, it may be necessary to increase wire size 

to prevent excessive voltage drop. Wires should be 

sized for a maximum of 3% voltage drop.

 4.  (Optional)  Disconnect  switches  are  not  fused.  The 

power  leads  must  be  protected

  at  the  point  of 

distribution in accordance with the fan dataplate.

 5.  On fans without a thermal protector integral to the 

motor (refer to unit or motor dataplate to determine 

if  protector  is  present)  a  separate  overload  device 

is required. Refer to Sections 430-32 of the N.E.C. 

for sizing.

 6.  All units must be electrically grounded in accordance 

with local codes or, in the absence of local codes, 

with  the  latest  edition  of  the  National  Electrical 

Code (ANSI/NFPA 70). 

A ground lug is provided as 

standard  in  the  unit  terminal  box.

  Size  grounding 

conductor in accordance with Table 250-95 of the 

National  Electrical  Code. 

DO NOT

  use  the  ground 

lug for connecting a neutral conductor.

 7.  Supply  voltage  to  the  power  ventilator  should  not 

vary  by  more  than  10%  of  the  value  indicated 

on  the  unit  dataplate.  Phase  unbalance  must  not 

exceed 2%.

Use copper conductors only.

CAUTION

Protect  wiring  from  sharp  edges.  Leave  some 

slack in the line to prevent damage.

CAUTION

Failure  of  motor  due  to  operation  on  improper 

line  voltage  or  with  excessive  phase  unbalance 

constitutes product abuse and may cause severe 

damage to the unit’s electrical components.

WARNING

Electric shock hazard. Could cause severe injury or 

death.  Failure  to  bond  the  frame  of  this  equipment 

to  the  building  electrical  ground  by  use  of  the 

grounding  terminal  provided  or  other  acceptable 

means  may  result  in  electrical  shock.  Disconnect 

electric  power  before  servicing  equipment.  Service 

to be performed only by qualified personnel. Before 

start-up, make sure power is turned off and locked 

in the OFF position.

WARNING

Rotation is critical. If allowed to operate in the wrong 

direction, the motor will overload and burn out.

WARNING

The  fan  was  balanced  at  the  factory  to  be  within 

stringent vibration levels before shipment. However, 

there  are  several  things  that  may  cause  vibration, 

such as rough handling in shipment and installation, 

weak foundations and alignments.

NOTICE

Check units for rotation. For three-phase, rotation 

can be changed by interchanging any two of the 

three  line  leads.  If  unit  is  checked  on  temporary 

wiring, it should be rechecked when permanently 

installed.  Motor  burn-out  or  tripped  overload 

protection devices are usually the result of wrong 

rotation.

WARNING

Содержание BSBP

Страница 1: ...mpellers Only Throughout this manual there are a number of HAZARD WARNINGS that must be read and adhered to in order to prevent possible personal injury and or damage to equipment Two signal words WARNING and CAUTION are used to indicate the severity of a hazard and are preceded by the safety alert symbol WARNING Used when serious injury or death MAY result from misuse or failure to follow specifi...

Страница 2: ...LITY OR FITNESS FOR A PARTICULAR PURPOSE In no event shall seller be liable to buyer for indirect incidental collateral or consequential damages of any kind BUYER S FAILURE TO PAY THE FULL AMOUNT DUE WITHIN SIXTY 60 DAYS OF DATE OF INVOICE SHALL OPERATE TO RELEASE SELLER FROM ANY AND ALL LIABILITY OR OBLIGATION ARISING PURSUANT TO ANY WARRANTY EXPRESS OR IMPLIED WHETHER STATUTORY OR OTHERWISE INCL...

Страница 3: ...es or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 A ground lug is provided as standard in the unit terminal box Size grounding conductor in accordance with Table 250 95 of the National Electrical Code DO NOT use the ground lug for connecting a neutral conductor 7 Supply voltage to the power ventilator should not vary by more than 10 of the val...

Страница 4: ... Control SPEED CONTROLLER AC LINE 115V SWITCH TRI AC MOTOR Table 2 Speed Controller RPM Range NOTES 1 Speed control available only with 115 60 1 open motors thermally protected 2 Three speed motor multiple tap winding 3 Speed control should not be connected to low speed tap on motor because of starting characteristics 4 Speed control connected to high speed tap on motor 5 Speed control connected t...

Страница 5: ...which may lead to premature failure and to prevent the impeller blades from hitting the actuator on motorized damper units Use general installation procedure from page 4 IMPELLER SIZE PANEL SQ WALL OPENING MIN DAMPER SIZE M MIN SURFACE MOUNT RECESS IN WALL BSBP BSDDP BSBP BSDDP BSBP BSDDP BSBP BSDDP 14 17 00 14 50 17 50 14 x 14 16 00 16 20 00 17 50 20 50 17 x 17 18 22 00 19 50 22 50 19 x 19 21 25 ...

Страница 6: ... Motor Side Guard Backdraft Damper Weatherhood Damper Guard Bird Screen Wall Collar Disconnect Switch O F F O N Removable Screen Panel Fan Wall Box Backdraft Damper Weatherhood Bird Screen Damper Guard Disconnect Switch WALL COLLAR WITH ACCESSORIES BSBP BSDDP WALL BOX WITH ACCESSORIES BSBP BSDDP ...

Страница 7: ...REEN BACKDRAFT DAMPER MOUNTING FLANGE REMOVABLE GUARD SCREEN AIR FLOW FAN SUPPORTS BY OTHERS Flush with Interior Wall WEATHERHOOD WITH SCREEN BACKDRAFT DAMPER MOUNTING FLANGE REMOVABLE GUARD SCREEN AIR FLOW FAN SUPPORTS BY OTHERS WEATHERHOOD WITH SCREEN BACKDRAFT DAMPER MOUNTING FLANGE SUPPORTS BY OTHERS FAN REMOVABLE GUARD SCREEN AIR FLOW WEATHERHOOD WITH SCREEN BACKDRAFT DAMPER MOUNTING FLANGE R...

Страница 8: ...wire to enter the collar Be sure the metal edges of the hole are protected so the wire will not get cut 5 If a damper weatherhood or damper guard screen are being used they can be fastened to the collar before the collar is fastened to the frame 6 Make sure the edges around the collar and frame are sealed after it is installed The wall box is installed in the same way SIZE COLLAR WALL BOX SQ WALL ...

Страница 9: ...perpendicularly to the rotating shafts Fan and motor shafts must be parallel Improper alignment will result in excessive belt wear 9 Check sheave setscrews to ensure tightness Proper keys must be in keyways 10 Do not readjust blade pitch or fan RPM If sheaves are replaced use only sheaves of identical size and type 11 If unit is to be left idle for an extended period it is recommended that belts b...

Страница 10: ...mpeller may need to be temporarily installed to get its clearances equal 12 Tighten the bearing mounting bolts 13 Reinstall the lube tubes if applicable 14 Install impeller and belts and adjust the motor to get proper belt tension Also make sure that the sheaves are properly aligned 15 If a new shaft is supplied ignore items 6 thru 8 Aerovent recommends periodic checks of voltage frequency and cur...

Страница 11: ...ill occur Recommended belt tension should permit 1 64 deflection per inch of span of the belt at the center of the belt span To find this point measure halfway between the pulley centerlines as shown in Figure 6 Extreme care must be exercised when adjusting V belts as not to misalign the pulleys Any misalignment will cause a sharp reduction in belt life and will also produce squeaky annoying noise...

Страница 12: ...on of material on impeller 4 Worn or corroded impeller 5 Impeller out of balance 6 Impeller hitting housing 7 Bent shaft 8 Bearings need lubrication 9 Loose bearing bolts 10 Loose or worn bearings 11 Mismatched belts 12 Belts too loose or too tight 13 Belts oily or dirty 14 Belts worn 15 Loose fan mounting bolts 16 Rattle of components in high velocity airstream 17 Electrical noise 18 Noise from h...

Страница 13: ...XHAUST SUPPLY 14 14 25 2 75 17 11 18 14 88 14 x 14 56 16 16 25 3 00 20 11 18 14 88 17 x 17 56 18 18 25 3 00 22 11 18 14 88 19 x 19 56 21 21 25 3 50 25 14 41 17 36 22 x 22 145T 24 24 25 3 50 28 14 55 17 36 25 x 25 184T 30 30 38 4 00 36 14 74 19 05 33 x 33 184T 36 36 38 5 00 42 15 67 19 93 39 x 39 215T 42 42 38 5 50 48 23 59 30 00 45 x 45 254T 48 48 38 6 00 54 23 59 30 00 51 x 51 254T Exhaust Airflo...

Страница 14: ...4T 36 36 38 5 00 42 17 50 19 13 21 50 23 13 39 x 39 145T 184T 42 42 38 5 50 48 17 88 19 38 22 19 23 75 45 x 45 145T 184T 48 48 38 6 00 54 18 75 20 13 23 06 24 63 51 x 51 145T 184T 54 54 38 6 50 60 18 88 20 50 23 69 25 19 57 x 57 145T 184T 60 60 38 7 25 66 19 50 24 75 24 44 29 94 63 x 63 145T 215T Exhaust Airflow Supply Airflow AIR FLOW AIR FLOW 2 00 2 00 A DIA A DIA D MAX D MAX C SQ OUTSIDE B B BS...

Страница 15: ... DIA A DIA BSBP SIZE A B C SQ D MAX DAMPER SIZE MAX MOTOR FRAME EXHAUST SUPPLY 42 42 38 5 50 48 21 31 26 75 45 x 45 215T 48 48 38 6 00 54 21 31 26 75 51 x 51 215T 54 54 38 6 50 60 26 13 32 30 57 x 57 254T 60 60 38 7 25 66 26 13 32 30 63 x 63 256T Exhaust Airflow Supply Airflow BSBP Belt Driven Level 3 Sizes 42 60 ...

Страница 16: ...WWW AEROVENT COM 5959 Trenton Lane N Minneapolis MN 55442 Phone 763 551 7500 Fax 763 551 7501 ...

Отзывы: