15
ST 5110
QM 1329.rev.00
n
Press the push-button. The temperature reading from probe 1 is dis-
played, alternating with the letters "Pr 1" and the on/off state of probe
1.
n
For each additional probe, press the push-button. The temperature
reading from probe x is displayed, alternating with the letters "Pr x"
and the on/off state of the probe, etc.
n
Press the push-button once again to display the letters "Pr 1" alter-
nating with the state of probe 1 , i.e. ON / OFF (flashing). When a
probe is activated, it is used in the calculation of the average room
temperature.
n
Use the adjustment knob to change the state of the probe.
n
For each additional probe, press the push-button. The state of probe
is displayed, alternating with the letters "Pr x", etc.
Notes:
(i) The display returns to the average room temperature after one minute.
(ii) Initially, only probe one is activated.
(iii) At least one probe must be activated at all times.
3
Viewing Minimum / Maximum Temperatures
The minimum and maximum temperatures are the lowest and highest tem-
perature values recorded since the last reset. Maximum and minimum
temperatures values are recorded for the average room temperature as well
as for individual probe temperatures.
n
Set the selection knob to ROOM TEMPERATURE / PROBE TEMP.
The room temperature is displayed.