Installation and Operation
6020HRJ/8030J User’s Manual
3-4
Aerotech, Inc
.
Version 1.1
3.5.
Procedure for Checking and Optimizing Performance
The pre-amplifier compensation for the 6020HRJ/8030J has been factory sealed so that a
position loop bandwidth of 10 to 20 Hz is possible when the correct motor and load are
applied. Problems in attaining a stable position loop response are usually a result of poor
velocity loop response where the latter depends predominantly on system inertia, motor
torque constant, and the setting of the GAIN pot R22 (see Section 3.4.2.).
If the required position loop response is difficult to attain after following the procedure in
Section 3.4.2., then compare actual motor load parameters against the following:
MOTOR TORQUE CONSTANT – “KT” – 28 OZ-IN/AMP
SYSTEM INERTIA (MOTOR and TABLE) – “J” - .4 OZ-IN-SEC
2
TACH VOLTAGE CONSTANT – 3V/1000 RPM
If “new” motor and load parameters vary considerably from the above values, use the
following procedure to reselect the pre-amplifier compensation elements:
∇
∇
∇
C6 =
KT (new) Vtach (new) 1.79 x 10
-3
J (new) (R13 or R10)*
R20=
5.1
C6
and
* depending on what input is used for tach
C6 in micro farads
R13, R20 in kilo ohms
J in oz-in-sec
Vtach in volts/1000 RPM
Содержание 6020HRJ
Страница 5: ...Table of Contents 6020HRJ 8030J User s Manual iv Aerotech Inc Version 1 1...
Страница 7: ...List of Figures and Tables 6020HRJ 8030J User s Manual vi Aerotech Inc Version 1 1...
Страница 9: ...Introduction 6020HRJ 8030J User s Manual 1 2 Aerotech Inc Version 1 1...
Страница 19: ...Maintenance and Repair 6020HRJ 8030J User s Manual 4 4 Aerotech Inc Version 1 1...
Страница 23: ...Index 6020HRJ 8030J User s Manual ii Aerotech Inc Version 1 1...
Страница 25: ......