60
IVEDITI 4880981_03-2106
D
p [kPa]
= Pressure drop
q [m
3
/h]
= Water flow rate
VCF
3X4L
3X4R
Pressure drop
Kvs
AB-A
2.2
Kvs
AB-B (by-pass)
2.2
Valve connections
A - AB - B
3/4”
The valve must be controlled from the control
panels, enabled at the valve control function.
Before selection, consult the features of
the control panels.
A water temperature probe must be com
-
bined with this accessory, consult the fea
-
tures of the control panels.
Pipes and fittings must be insulated ther
-
mally.
Attention: The VCFX4 valve and the BC4
tray cannot be installed simultaneously on
the same fan coil.
For further information, refer to the
accessory manual.
The VCF_X4L and VCF_X4R valves are designed for fan coils with single coil, inserted in 4-pipe systems with "Hot" and "Cold" circuits fully
separated. The kits consist of 2 insulated 3-way valves and 4 connections complete with electro-thermal actuators, valve insulating cover-
ing and relative hydraulic fittings. The valves are an "all-or-nothing" type, typically closed.
VCF_X4L
Fan coil valves kit with left connections:
- with standard coil
(VCF3X4L);
VCF_X4R
Fan coils valves kit with right connec-
tions:
- with standard coil
(VCF3X4R);
CALCULATION OF THE PRESSURE DROP
SYSTEM EXAMPLES
VCF_X4
FANCOIL
SW
SW
VCF_X4
FANCOIL
SW
SW
IN
IN
OUT
OUT
VCF3X4L
ACCESSORIES
VCF VALVES KIT FOR FAN COILS WITH SINGLE COIL IN 4-PIPE SYSTEMS