59
IVEDITI 4880981_03-2106
A
B
AB
IN
OUT
Flow direction
D
p [kPa]
= Pressure drop
q [m
3
/h]
= Water flow rate
VCF
43
4324
45
4524
Pressure drop
Kvs
AB-A
2.5
1.7
Kvs
AB-B (by-pass)
1.6
1.2
Valve connections
A - AB - B
3/4”
1/2”
The valve must be controlled from the control
panels, enabled at the valve control function.
Before selection, consult the features of
the control panels.
A water temperature probe must be
combined with this accessory, consult the
features of the control panels.
Pipes and fittings must be insulated ther
-
mally.
Attention: The VCF valve and the BC4
tray cannot be installed simultaneously on
the same fan coil.
For further information, refer to the
accessory manual.
The kit, composed of a 3-way motorised valve, an actuator and related hydraulic fittings, is suitable for installation in fan coils with both
right and left connections.
The valve is an "all-or-nothing" type, typically closed.
Valves with 230V~50Hz power supply
for fan coils:
- with standard coil
VCF43),
- with heating only coil (BV)
(VCF45).
Valves with 24V~50Hz power supply
for
fan coils:
- with standard coil
(VCF4324),
- with heating only coil (BV)
(VCF4524).
CALCULATION OF THE PRESSURE DROP
ACCESSORIES
VCF 3-WAY VALVES KIT
Содержание VED