Mod. NXW
vers
U.M.
0500
0550
0600
0650
0700 0750
0800
0900
1000
1250
1400
Cooling output
° - L
kW
105
113
139
156
177
209
241
273
305
332
360
Total input power
kW
24.9
26.8
33.0
36.9
41.7
48.8
56.5
64.7
72.3
78.8
85.3
Evaporator water flow rate
l/h
18031 19480 23988 26918 30381 35935
41488
46976
52463
57187
61909
Evaporator pressure drop
kPa
26
31
28
35
38
41
43
48
31
32
32
ENERGY INDEXES
EER
° - L
W/W
4.22
4.23
4.22
4.24
4.23
4.28
4.27
4.22
4.22
4.22
4.22
ELECTRICAL DATA
400V 3 50Hz
Input current (cooling)
° - L
A
54.1
56.7
65.4
70.6
96.3
105.3
114.2
134.4
154.6
156.8
160.2
Maximum current
A
75
80
96
107
122
146
169
193
217
231
248
Starting current
A
240
245
227
238
289
319
341
398
422
490
504
OIL CHARGE
Circuit (C1/C2)
dm
3
6.6/3.6 6.6/3.6 6.6/6.6 6.6/6.6 7.2/7.2 13.4/7.2 13.4/13.4 13.4/13.4 13.4/13.4 13.9/13.9 13.9/13.9
Refrigerant
dm
3
only with a watertight charge
COMPRESSOR (SCROLL)
No. of compressors/circuits
° - L
no./no.
3/2
4/2
EVAPORATOR (plates)
Quantity
° - L
no.
1
Water content
l
7.0
7.0
9.5
9.5
10.4
12.3
14.8
16.7
30.2
32.9
37.4
Victaulic water connections
diam
2"1/2
2"1/2
2"1/2
2"1/2
2"1/2
2"1/2
2"1/2
2"1/2
3"
3"
3"
SOUND DATA
Sound power (1)
°
dB(A)
78
79
79
80
82
86
88
88
88
90
90
Sound pressure (2)
46
47
47
48
50
54
56
56
56
58
58
Sound power (1)
L
dB(A)
72
73
73
74
76
80
82
82
82
84
84
Sound pressure (2)
40
41
41
42
44
48
50
50
50
52
52
DIMENSIONS
Height
°
mm
1835
1835
1835
1835
1835
1775
1775
1775
1820
1820
1820
Width
mm
800
800
800
800
800
800
800
800
800
800
800
Depth
mm
1790
1790
1790
1790
1790
2090
2354
2354
2354
2354
2354
Height
L
mm
1885
1885
1885
1885
1885
1885
1885
1885
1885
1885
1885
Width
mm
800
800
800
800
800
800
800
800
800
800
800
Depth
mm
2090
2090
2090
2090
2090
2090
2354
2354
2354
2354
2354
6.3.
STANDARD VERSION E SIZE 0500-0550-0600-0650-0700-0800-0900-1000-1250-1400
(1) SOUND POWER
Aermec determines the value of the sound power based on the
measurements taken in accordance with standard 9614-2, with
respect to the certification requirement Eurovent.
(2) SOUND PRESSURE
Sound pressure in free field on reflecting plane (direction fact.
Q=2), at 10 metres distance from the external surface of the
unit, in accordance with standard ISO 3744.
Reference data
processed water temperature
7°C
Condensing temperature
45°C
DT
5°C
17