background image

22.11 – 5806712_07

41

15    MAINTENANCE

NOTICE:

 Aermec cannot be held responsible for any malfunction of the 

units which are due to improper or missing maintenance.

Any cleaning, inspection, control or routine or extraordinary main-

tenance intervention:

 must be carried out by expert technical personnel 

who are authorised and qualified to perform the activities indicated above. 
These activities must be carried out with the machine turned off and not 
powered, and in a workmanlike manner according to what is required by 
the national laws in force. When carrying out these activities, the machine 
has the following risks:

—  Risks of electric discharges;
—  Risk of injuries due to the presence of rotating parts;
—  Risk of injuries due to the presence of sharp edges and heavy weights;
—  Risks of injuries due to the presence of components containing high pressure 

gas;

—  Risks of injuries due to high or low temperature components.
—  Noise-related risks of the machine functioning (refer to what is declared in the 

user manual);

—  Risks related to the presence of harmful substances in hydronic circuits.

These activities must be carried out using personal protective equip-

ment suitable for the activities to carry out.

 

 

 

Maintenance operations are essential to maintain the refrigerant unit efficient, from 
a purely functional point of view and with regard to energy and safety.
In the absence of specific regulations regarding HFC refrigerants, the manufacturer 
prescribes the application of and compliance with that indicated in the: 

1. 

Regulation (EC) No.842/2006- art.3 concerning the "leakage containment";

2. 

Regulation (EC) No.1516/2007 concerning the “standard leakage checking 
requirements” and related national laws implementing the above European 
regulations.

WARNING For the unit, the user must provide a system booklet which 

he must ensure, or its designee authorised to service the machine, 

will contain all required records in order to have a historical doc-

umentation of the unit functioning. The absence of records in the 

booklet may count as evidence of lack of maintenance.

 PRECAUTIONS AND PREVENTIVE MEASURES TO OBSERVE 

DURING MAINTENANCE

WARNING Maintenance operations can only be performed by author-

ised technicians.

 precautions against residual risks mechanical risks

WARNING The cooling circuit contains pressurised refrigerant gas:

—  all operations must be performed by skilled personnel who have the legally re-

quired authorisations or qualifications.

—  The cooling circuit contains under pressure refrigerant gas: any operation must 

be performed by competent personnel in possession of the authorisations and 
qualifications required by current laws

IT IS FORBIDDEN TO LOAD:

 the cooling circuit with a refrigerant other 

than the one indicated. Using a different refrigerant gas could seriously 
damage the unit.

—  Before opening a machine panel, ascertain whether it is or not firmly connected 

to it by hinges;

—  In case a piece is disassembled, make sure it is correctly reassembled before 

restarting the unit;

—  Louvers of the heat exchangers, edges of the components and panels, screws 

can generate cuts;

—  Do not remove the protections from mobile elements while the unit is running

—  Make sure that the protections of mobile elements are correctly in place before 

restarting the unit;

—  It is not permitted to walk on the machine or to place other items on it;
—  Fans, motors and belt drives may be in motion, always wait for them to stop and 

take appropriate precautions to prevent their activation before accessing them;

—  If the unit has components such as integrated inverters, disconnect the power 

supply and wait at least 15 minutes before accessing it for maintenance opera-
tions: the internal components remain energised for this period, generating the 
risk of electrocution;

—  Isolate the unit from the mains by means of the external isolator provided for 

the insertion of padlocks (up to 3) for blocking in "open" position;

—  Place a sign reading "Do not turn on - maintenance in progress" on the open 

isolator;

—  Equip yourself with the appropriate personal protective equipment (helmet, 

insulated gloves, protective goggles, accident-prevention shoes, etc.);

—  Equip yourself with tools in good condition and make sure to have fully under-

stood the instructions before using them;

—  For outdoor units, do not perform interventions in dangerous weather condi-

tions such as rain, snow, fog, etc.

—  Never keep the cooling circuit open, because the oil absorbs humidity and de-

grades;

—  Always use appropriate equipment (extractor, antistatic bracelet, etc.) when 

replacing electronic boards;

—  If replacing a motor, compressor, evaporator, condensing coils or any oth-

er heavy element, make sure that the lifting devices are compatible with the 
weight to be handled;

—  In air units with independent compressor compartment, do not access the fan 

compartment without having first disconnected the machine through the iso-
lator on the board and having placed a sign reading "Do not turn on - mainte-
nance in progress";

—  Contact the company if changes must be made to the refrigerant, hydraulic or 

electric diagram of the unit, as well as its control logic.

 Prevention of chemical / fire / environmental risks

WARNING Any intervention on the machine must be performed with 

"NO SMOKING";

WARNING Never disperse the fluid contained in the cooling circuit in 

the environment;

WARNING The water circuit may contain harmful substances. Prevent 

the contents coming into contact with skin, eyes and clothing. Use 

the prescribed personal protective equipment;

If there is a need to perform a braze-welding, so with the use of special torch with 
naked flame, the same flame must only be activated if in the absence of freon gas in 
the environment and on the cooling circuit pipes. Inside piping must be "washed" 
and contain nitrogen type inert gas. The presence of flame and freon gas decom-
poses the same, forming lethal and carcinogenic compounds.
Hot works require the availability of a Carbon Dioxide (CO

2

) fire extinguisher. DO 

NOT USE WATER, leachates could be hazardous for the discharges; if using water, 
provide a containment tank.

 Prevention against residual risks due to pressure or high/low temperature

WARNING The unit contains under pressure gas:

 no operation must be 

performed on under pressure equipment except during maintenance that 
must be carried out by competent and authorised personnel.

WARNING Perform brazing or welding only on empty pipes and clear 

of any lubricating oil residues; do not near flames or other heat sourc-

es to the pipes containing under pressure fluids;

WARNING Do not work with naked flames near the unit;

WARNING Do not bend or hit pipes containing under pressure fluids;

 

Содержание NRP 0800

Страница 1: ... i o n o f O r i g i n a l i n s t r u c t i o n s w w w a e r m e c c o m Installation Manual EN AIR WATER MULTIPURPOSE C o o l i n g c a p a c i t y 5 2 1 2 0 t o n H e a t i n g c a p a c i t y 7 3 8 3 8 7 1 6 8 9 3 5 1 B T U h NRP 0800 1800 ...

Страница 2: ......

Страница 3: ...to present the product and help you select the unit that best meets the needs of your system WARNING personnelwhopossessthenecessaryskillsaccordingtostate national and local regulations in force must choose and size the machine Aermec Aermec always attentive to the continuous changes in the market and its regulations reserves the right to make all the changes deemed necessary for improving the pro...

Страница 4: ...1800 p 19 9 Hydraulic connections p 20 Connections p 20 Water characteristics p 20 Discharging system p 20 Anti freeze protection p 21 10 Position of hydraulic connections p 22 11 System water content p 24 Minimum system water content p 24 Maximum system water content p 24 Expansion vessel setting p 25 12 Main hydraulic circuits p 26 2 pipe system p 26 4 pipe system p 29 13 Main cooling refrigeran...

Страница 5: ...at the disposal of this product must strictly follow the national and local laws in force All specifications are subject to change without prior notice Although every effort has been made to ensure accuracy Aermec shall not be held liable for any errors or omissions ...

Страница 6: ...ted ensures perfect satisfaction of heating and cooling loads The operating modes are 1 PRODUCTION OF COOLED WATER ONLY The multipurpose unit acts as a classical chiller cool water to the system and con densation heat disposal outside through finned coils 2 PRODUCTION OF HOT WATER ONLY The multipurpose unit acts as a heat pump exploiting the heat of the outside air it makes use of the finned coil ...

Страница 7: ...ec shall not be held liable for the failure to observe the safety and accident prevention regulations in force Personal protective equipment PPE 1 Operations Handling Installation and or maintenance Welding or brazing Safety gloves helmet goggles safety footwear protective garments Earmuffs 1 It is recommended to follow the instructions in EN 378 3 Observe the laws in force in the country of unit ...

Страница 8: ...res on elec trical equipment and for lubricant oil of the compressor and the refrigerant The unit contains pressurised refrigerant gas no operation may be performed on pressurised equipment except during maintenance which must be per formed by skilled and qualified personnel Perform brazing or welding only on empty pipes and clear of any lubricating oil residues do not near flames or other heat so...

Страница 9: ... WARNING Under no circumstances does the unit have to be operated outside the operating limit under penalty of the warranty expiration Aermec S p A cannot be held responsible for any malfunction of the units which are operated outside the established limits and for their consequences OPERATING COOLING MODE RANGE Key A Outdoor air temperature F B Water produced F 1 Standard mode B 1 A 0 14 20 40 60...

Страница 10: ...applicable safety procedures The handling operations must be carried out carefully to prevent damage The unit may only be handled in a horizontal position and only from its base It is prohibited to dispose of the packaging material in the environ ment or leave it within reach of children as it may be a potential source of danger Therefore it must be disposed of according to what is defined by curr...

Страница 11: ...t be fixed to the unit BEFORE being earthed AERMEC is not responsi ble for selecting the capacity of the anti vibration supports Each side of the unit must have space to allow all routine and extraordinary maintenance to be performed the vertical air exhaust must not be obstructed PLACE OF INSTALLATION All the units in this series are designed to be installed outdoors on roofs or on the ground in ...

Страница 12: ...g images indicate the minimum required space SINGLE INSTALLATION 1 42 in B1 B2 C1 C2 A1 B1 B2 C1 C2 A1 1 1 1 1 Minimum technical space to be ensured in order for the chiller to work properly and for possible maintenance The drawings are provided solely as examples VERSION A Size 0800 0900 1000 1250 1400 1500 1650 1800 Minimumtechnicalspaces B1 A in 31 5 31 5 31 5 31 5 31 5 31 5 31 5 31 5 B2 A in 4...

Страница 13: ...S For DIMENSIONS and POSITION OF HYDRAULIC CONNECTIONS refer to the DWG file on site www aermec com or selection program Magellano View from below NRP 0800 1000 71 9in 71 9in Ø20 3 9in 2 0in 3 9in NRP 1250 1800 Ø20 2 0in 15 7in 15 7in 75 4in 75 4in 28 3in ...

Страница 14: ...1 5 70 4 94 4 94 6 94 3 99 6 98 3 A P2 P4 00 in 67 0 69 3 68 0 91 8 92 1 91 7 97 4 96 0 A P2 P4 R1 R3 in 68 0 70 2 69 1 93 0 93 2 92 9 98 3 97 0 A P2 P4 R2 R4 in 68 9 71 1 70 0 93 9 94 1 93 9 99 1 97 8 Y A 00 00 in 7 137 6 7 490 3 7 468 3 9 935 4 10 023 4 10 111 3 10 530 0 10 838 8 A 00 R1 R3 in 7 446 3 7 798 1 7 798 1 10 310 2 10 398 1 10 486 0 10 904 7 11 213 5 A 00 R2 R4 in 7 732 1 8 084 8 8 06...

Страница 15: ...3 22 0 21 9 22 2 18 7 20 0 5 A 00 00 3 8 5 0 4 6 13 4 13 7 13 3 17 8 16 1 A 00 R1 R3 4 2 5 2 4 9 15 4 15 7 15 3 19 7 17 9 A 00 R2 R4 4 4 5 5 5 1 17 0 17 2 16 9 21 3 19 4 A P1 P3 00 3 5 4 6 4 3 12 1 12 4 12 1 16 4 14 7 A P1 P3 R1 R3 3 8 4 9 4 5 14 2 14 4 14 1 18 3 16 6 A P1 P3 R2 R4 4 1 5 1 4 8 15 8 16 0 15 7 19 8 18 1 A P2 P4 00 3 3 4 5 4 1 11 5 11 8 11 5 15 6 14 1 A P2 P4 R1 R3 3 6 4 7 4 4 13 5 1...

Страница 16: ... 2 8 5 A P1 P3 00 10 7 9 7 10 1 10 1 9 9 9 9 8 8 9 1 A P1 P3 R1 R3 10 0 9 1 9 5 9 8 9 6 9 6 8 5 8 8 A P1 P3 R2 R4 9 5 8 6 9 0 9 5 9 4 9 4 8 3 8 6 A P2 P4 00 11 0 9 9 10 3 10 1 9 9 10 0 8 8 9 1 A P2 P4 R1 R3 10 3 9 3 9 7 9 8 9 6 9 7 8 6 8 8 A P2 P4 R2 R4 9 8 8 9 9 3 9 5 9 4 9 4 8 3 8 6 2 A 00 00 11 8 11 1 12 4 12 6 12 5 12 6 9 0 9 6 A 00 R1 R3 10 7 10 1 11 3 11 8 11 7 11 8 8 5 9 1 A 00 R2 R4 9 9 9 ...

Страница 17: ...2 15 9 16 3 16 1 17 2 16 3 A P2 P4 R2 R4 4 1 5 4 5 3 17 4 17 7 17 5 18 3 17 5 7 A 00 00 2 8 2 8 2 7 4 4 4 1 A 00 R1 R3 2 8 2 8 2 7 4 3 4 1 A P1 P3 00 2 8 2 8 2 7 4 3 4 1 A 00 R2 R4 2 8 2 8 2 7 4 2 4 0 A P1 R1 R3 2 8 2 7 2 7 4 2 4 0 A P2 00 R1 R3 2 8 2 7 2 7 4 2 4 0 A P3 R1 R3 2 8 2 7 2 7 4 2 4 0 A P4 00 R1 R3 2 8 2 7 2 7 4 2 4 0 A P1 P3 R2 R4 2 8 2 7 2 7 4 1 4 0 A P2 P4 R2 R4 2 8 2 7 2 7 4 1 3 9 8...

Страница 18: ...18 22 11 5806712_07 7 DIMENSIONAL TABLES NRP 0800 1000 86 6in 96 5in 167 3in NRP 0800 0900 60Hz NRP 1000 60Hz 3 9 in 3 9 in 3 9 in 3 9 in ...

Страница 19: ...22 11 5806712_07 19 NRP 1250 1800 96 5in 226 4in 86 6in 21 7 in 43 3 in 80 8 in 43 3 in 21 7 in ...

Страница 20: ...rmec com It is important to follow the recommendations not complete below The water pipes must not transmit radial or axial forces or vibrations to the ex changers use flexible hoses to reduce the transmitted vibrations It is necessary to install manual or automatic vent valves in the highest points of the circuit and also provide discharge fittings in the lowest points to allow emptying the entir...

Страница 21: ...REEZE PROTECTION The addition of glycol is the only effective protection against freezing the glycol water solution must be sufficiently concentrated to ensure proper protection and prevent ice forming at minimum temperature provided for a given installation Take the necessary precautions if using non passivated anti freeze solu tions monoethylene glycol or monopropylene glycol Corrosion phenom en...

Страница 22: ...75 8 in 9 5 in 14 5 in NRP 0800 0900 versionS R1 R2 R3 R4 P1 P2 P3 P4 31 5 in 13 5 in 31 5 in 55 0 in 75 8 in 71 1 in 9 5 in 15 6 in NRP 1000 version 00 11 0 in 20 4 in 31 5 in 75 8 in 11 0 in 22 4 in NRP 1000 versions R1 R2 R3 R4 P1 P2 P3 P4 31 5 in 31 5 in 13 5 in 55 0 in 75 8 in 51 2 in 14 1 in 20 7 in ...

Страница 23: ... 11 0 in 22 4 in 11 0 in 61 1 in 105 4 in NRP 1250 1800 versions R1 R2 R3 R4 P1 P3 13 5 in 31 5 in 11 0 in 16 7 in 61 1 in 23 4 in 100 7 in 105 4 in NRP 1250 1800 versions R1 R2 R3 R4 P2 P4 13 5 in 31 5 in 61 1 in 23 4 in 105 4 in 80 8 in 11 0 in 20 7 in ...

Страница 24: ...AERMEC Technical Commercial Service NOTICE Under no circumstances does the unit have to be operated when water flow rate on the heat exchanger is below the minimum water flow rate or above the maximum water flow rate under penalty of the warranty expiration Aermec cannot be held responsible for any malfunction of the units which are operated outside the established limits of water flow rate and fo...

Страница 25: ...figure according to the formula p rating psi H ft 33 5 1 0 For example if level difference H is equal to 65 6 ft the calibration value of the vessel will be 33 4 psi If the calibration value obtained from the formula is less than 21 8 psi i e for H 40 2 use the standard calibration Key A Expansion vessel 1 Check that highest utility is not higher than 180 4 ft 2 Ensure that lowest utility can with...

Страница 26: ... System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Electric conductivity 10 500 μS cm Temperature 65 C Oxygen content 0 1 ppm Max glycol amount 50 Phosphates PO 2ppm Manganese Mn 0 05 ppm Iron Fe 0 2 ppm Alkalinity HCO 70 300 ppm Chloride ions Cl 50 ppm Free chlorine 0 5 ppm Sulphate ions SO 50 ppm Sulphide ion S None Ammonium ions NH None Silica SiO 30 ppm NOTICE under n...

Страница 27: ...ECOVERY SIDE hot domestic water SYSTEM SIDE hot cold Water characteristics System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Electric conductivity 10 500 μS cm Temperature 65 C Oxygen content 0 1 ppm Max glycol amount 50 Phosphates PO 2ppm Manganese Mn 0 05 ppm Iron Fe 0 2 ppm Alkalinity HCO 70 300 ppm Chloride ions Cl 50 ppm Free chlorine 0 5 ppm Sulphate ions SO 50 ppm ...

Страница 28: ...d Water characteristics System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Electric conductivity 10 500 μS cm Temperature 65 C Oxygen content 0 1 ppm Max glycol amount 50 Phosphates PO 2ppm Manganese Mn 0 05 ppm Iron Fe 0 2 ppm Alkalinity HCO 70 300 ppm Chloride ions Cl 50 ppm Free chlorine 0 5 ppm Sulphate ions SO 50 ppm Sulphide ion S None Ammonium ions NH None Silica Si...

Страница 29: ... exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Electric conductivity 10 500 μS cm Temperature 65 C Oxygen content 0 1 ppm Max glycol amount 50 Phosphates PO 2ppm Manganese Mn 0 05 ppm Iron Fe 0 2 ppm Alkalinity HCO 70 300 ppm Chloride ions Cl 50 ppm Free chlorine 0 5 ppm Sulphate ions SO 50 ppm Sulphide ion S None Ammonium ions NH None Silica SiO 30 ppm NOTICE under no circumstances does the unit h...

Страница 30: ...6 21 3 3 22 HOT SIDE COLD SIDE Water characteristics System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Electric conductivity 10 500 μS cm Temperature 65 C Oxygen content 0 1 ppm Max glycol amount 50 Phosphates PO 2ppm Manganese Mn 0 05 ppm Iron Fe 0 2 ppm Alkalinity HCO 70 300 ppm Chloride ions Cl 50 ppm Free chlorine 0 5 ppm Sulphate ions SO 50 ppm Sulphide ion S None Am...

Страница 31: ...tics System Chiller with plate heat exchanger PH 7 5 9 Total hardness 4 5 8 5 dH Electric conductivity 10 500 μS cm Temperature 65 C Oxygen content 0 1 ppm Max glycol amount 50 Phosphates PO 2ppm Manganese Mn 0 05 ppm Iron Fe 0 2 ppm Alkalinity HCO 70 300 ppm Chloride ions Cl 50 ppm Free chlorine 0 5 ppm Sulphate ions SO 50 ppm Sulphide ion S None Ammonium ions NH None Silica SiO 30 ppm NOTICE und...

Страница 32: ...C TEV HPT HPS LS VIC LPT IDL CP CN CV CV CV CV CV TEV F AL VIC TEV 1 4 4 4 4 4 4 4 4 4 4 5 5 5 5 9 9 10 10 11 11 12 12 13 13 14 14 9 9 6 6 7 7 8 8 2 A B 3 3 System hot water production Key A Plant return water B System delivery water 1 System side heat exchanger 2 Dhw side exchanger 3 Source side heat exchanger 4 One way valve 5 Thermostatic expansion valve 6 Sight glass 7 Filter drier 8 Liquid ac...

Страница 33: ...VIC TEV CP 2 1 4 4 4 4 4 4 4 4 4 4 5 5 5 5 9 9 10 10 11 11 12 12 13 13 14 14 9 9 6 6 7 7 8 8 2 3 3 2 CIRCUITS TO PRODUCE COLD WATER TO SYSTEM AND HOT WATER TO DHW Key A Plant return water B System delivery water 1 System side heat exchanger 2 Dhw side exchanger 3 Source side heat exchanger 4 One way valve 5 Thermostatic expansion valve 6 Sight glass 7 Filter drier 8 Liquid accumulator 9 Cycle inve...

Страница 34: ...CV CV TEV F AL VIC TEV 1 4 4 4 4 4 4 4 4 4 4 5 5 5 5 9 9 10 10 11 11 12 12 13 13 14 14 9 9 6 6 7 7 8 8 2 B A 3 3 CP MAIN COOLING REFRIGERANT LAYOUTS FOR 4 PIPE SYSTEM Cold water production at system Key A Plant return water B System delivery water 1 System side heat exchanger 2 Dhw side exchanger 3 Source side heat exchanger 4 One way valve 5 Thermostatic expansion valve 6 Sight glass 7 Filter dri...

Страница 35: ...EM H2 O DHW SYSTEM SUPPLY H2 O 1 4 4 4 4 4 4 4 4 4 4 5 5 5 5 9 9 10 10 11 11 12 12 13 13 14 14 6 6 7 7 8 8 2 3 3 Simultaneous production of hot and cold water to the system Key A Plant return water B System delivery water 1 System side heat exchanger 2 Dhw side exchanger 3 Source side heat exchanger 4 One way valve 5 Thermostatic expansion valve 6 Sight glass 7 Filter drier 8 Liquid accumulator 9 ...

Страница 36: ...tions following international regulations and the national regulations of the country in which the unit is installed in compliance with the legislative regulations in force at the moment of installation it is mandatory to check the machine sealing before connecting the electrical wiring The machine must only be powered once the hydraulic and electric operations are completed Electrical connections...

Страница 37: ... always refer exclusively to the wiring diagram supplied with the unit Remove any protections from the cable fixing points For the functional connection of the unit take the power supply cable to the electric control board inside the unit and connect it to clamps L1 L2 L3 N if present and PE respecting the polarities L1 L2 L3 and N as phases and PE as grounding Ensure that all protections removed ...

Страница 38: ...1 410 461 533 612 660 697 703 A P3 P4 R1 R2 A 362 428 479 550 636 684 721 727 A P3 P4 R3 R4 A 365 435 486 557 647 695 732 738 POWER SUPPLY 460V Version Integrated hydronickituser side Integrated hydronickit recoveryside 0800 0900 1000 1250 1400 1500 1650 1800 Peakcurrent LRA A 00 00 A 293 343 358 430 480 505 521 511 A 00 R1 R2 A 299 352 367 439 492 517 533 523 A 00 R3 R4 A 300 355 370 442 497 522 ...

Страница 39: ...4 R1 R2 A 156 162 171 228 278 308 313 300 A P3 P4 R3 R4 A 157 164 173 231 282 312 317 304 POWER SUPPLY 208V Version Integrated hydronickituser side Integrated hydronickit recoveryside 0800 0900 1000 1250 1400 1500 1650 1800 Peakcurrent LRA A 00 00 A 611 784 820 979 1004 1065 1103 1178 A 00 R1 R2 A 622 803 839 998 1030 1091 1129 1204 A 00 R3 R4 A 625 810 846 1005 1041 1102 1140 1215 A P1 P2 00 A 62...

Страница 40: ... are complied with and that a mechanical filter has been installed in each inlet heat exchanger Mandatory component for warranty to be valid Check that the circulation pump s are working and that the wa ter flow rate is sufficient to close the flow switch contact if installed We recommend installing one always upstream of every heat exchanger Check the water flow rate measuring the pressure differ...

Страница 41: ...ements are correctly in place before restarting the unit It is not permitted to walk on the machine or to place other items on it Fans motors and belt drives may be in motion always wait for them to stop and take appropriate precautions to prevent their activation before accessing them If the unit has components such as integrated inverters disconnect the power supply and wait at least 15 minutes ...

Страница 42: ...ss its cooling circuit Connect the necessary instruments pressure gauges connected with suitable extensions to the pressure sockets on the compressor inputs and outputs ther mometers connected to thermocouple probes that are fastened to the pipes at the compressor inputs and outputs Do not use metratasts as they require the operator to approach the machine s cooling circuit Turn on the machine and...

Страница 43: ...clean the coils refer to the dedicated chapter INTERVENTIONS ON THE CIRCUIT DESCRIPTION FREQUENCY Note 3Mths 6Mths 12Mths INTERVENTIONSONTHECOOLINGCIRCUITOPERATINGWITHFULLLOAD Measurementoftheoverheatingtemperature Measurementoftheundercoolingtemperature Measurementoftheexhaustgastemperature Measurementoffaninput Measurementofcompressorinput COMPRESSORCONTROLS Oillevelcontrol Oilaciditycontrol Con...

Страница 44: ... o n e 3 9 0 4 4 2 6 3 3 1 1 1 F a x 3 9 0 4 4 2 9 3 5 7 7 s a l e s a e r m e c c o m w w w a e r m e c c o m 2 2 1 1 5 8 0 6 7 1 2 _ 0 7 5806712_07 DOWNLOAD THE LATEST VERSION TÉLÉCHARGER LA DERNIÈRE VERSION http www aermec com qrcode asp q 14263 http www aermec com qrcode asp q 14262 ...

Отзывы: