26
NRL 0280-0750 60Hz
EN
12. ELECTRICAL DATA NRL COOLING ONLY
ELECTRICAL DATA MODELS WITHOUT PUMP + "°" ON/OFF FAN
LRA:
Peak current
MCA:
Minimum circuit amperage
MOP:
Maximum overcurrent permitted by the protection device
Models
028
030
033
035
050
055
060
065
070
075
Alimentation
230V60Hz
MODELS WITHOUT PUMP
LRA
A
-
-
-
-
372
392
377
447
465
521
E
227
275
288
358
-
-
-
-
-
-
MCA
A
-
-
-
-
150
150
175
225
250
250
E
70
80
90
125
-
-
-
-
-
-
MOP
A
-
-
-
-
175
175
175
250
250
300
E
90
110
110
175
-
-
-
-
-
-
MODELS WITH LOW PUMP
(P1-P2-01-02)
LRA
A
-
-
-
-
378
397
382
458
476
532
E
232
280
292
362
-
-
-
-
-
-
MCA
A
-
-
-
-
150
150
175
225
250
300
E
75
80
90
150
-
-
-
-
-
-
MOP
A
-
-
-
-
175
200
200
250
300
300
E
100
110
110
175
-
-
-
-
-
-
MODELS WITH HIGH PUMP
(P3-P4-03-04)
LRA
A
-
-
-
-
380
400
385
460
478
534
E
235
283
296
366
-
-
-
-
-
-
MCA
A
-
-
-
-
150
175
175
225
300
300
E
80
90
100
150
-
-
-
-
-
-
MOP
A
-
-
-
-
175
200
200
250
300
300
E
100
110
125
175
-
-
-
-
-
-
Alimentation 460/3/60Hz
MODELS WITHOUT PUMP
LRA
A
-
-
-
-
186
195
191
220
228
265
E
124
153
158
187
-
-
-
-
-
-
MCA
A
-
-
-
-
70
75
90
100
110
125
E
40
50
60
70
-
-
-
-
-
-
MOP
A
-
-
-
-
80
90
100
110
125
125
E
50
60
70
80
-
-
-
-
-
-
MODELS WITH LOW PUMP
(P1-P2-01-02)
LRA
A
-
-
-
-
188
197
194
226
234
270
E
126
155
160
190
-
-
-
-
-
-
MCA
A
-
-
-
-
70
80
100
110
125
125
E
45
60
60
70
-
-
-
-
-
-
MOP
A
-
-
-
-
80
90
110
125
125
125
E
50
60
70
90
-
-
-
-
-
-
MODELS WITH HIGH PUMP
(P3-P4-03-04)
LRA
A
-
-
-
-
190
199
195
227
235
271
E
128
157
162
191
-
-
-
-
-
-
MCA
A
-
-
-
-
70
80
100
110
125
125
E
45
60
60
70
-
-
-
-
-
-
MOP
A
-
-
-
-
80
90
110
125
125
150
E
50
70
75
90
-
-
-
-
-
-
Alimentation
575/3/60Hz
MODELS WITHOUT PUMP
LRA
A
-
-
-
-
137
144
132
164
171
199
E
97
102
106
138
-
-
-
-
-
-
MCA
A
-
-
-
-
60
60
70
90
100
110
E
30
40
45
60
-
-
-
-
-
-
MOP
A
-
-
-
-
70
75
75
100
110
125
E
40
50
50
75
-
-
-
-
-
-
MODELS WITH LOW PUMP
(P1-P2-01-02)
LRA
A
-
-
-
-
140
146
134
169
175
204
E
98
103
108
140
-
-
-
-
-
-
MCA
A
-
-
-
-
60
60
70
90
100
110
E
35
40
45
60
-
-
-
-
-
-
MOP
A
-
-
-
-
70
80
80
100
110
125
E
40
50
50
75
-
-
-
-
-
-
MODELS WITH HIGH PUMP
(P3-P4-03-04)
LRA
A
-
-
-
-
141
147
135
170
176
205
E
100
105
109
141
-
-
-
-
-
-
MCA
A
-
-
-
-
60
70
70
90
110
110
E
35
40
45
60
-
-
-
-
-
-
MOP
A
-
-
-
-
75
80
80
100
110
125
E
40
50
50
80
-
-
-
-
-
-
Содержание NRL0280E