14.1.  FUNCTIONS AVAILABLE VIA THE MACHINE’S ON BOARD PANEL

By pressing the 

ON/OFF 

key it is possi-

ble to switch the unit on or off. the col-

our of the RUN icon changes depend-

ing on the status of the unit (red units 

on standby, green unit on).

Pressing the 

Mode 

key will select the 

operating mode to be applied to the 

unit; Each press of the key will scroll 

through the available modes in ac-

cordance with the following layout:

Each different operating mode ena-

bles or disables particular settings:

• 

Automatic

 ( ): the temperature 

set-point and the speed of the fans 

are automatically set (and can not 

be changed by the user); the swing of 

the vertical and horizontal fins will be 

modified;

Cooling

 (   ): the temperature set-

point, the speed of the fans and func-

tions related to swing of the vertical 

and horizontal fins will be modified;

• 

Dehumidification

 ( ): the tempera-

ture set-point and the speed of the 

fans are fixed; the swing of the vertical 

and horizontal fins will be modified;

• 

Ventilation only

 ( ): The tempera-

ture set-point is disabled; the speed of 

the fans and the swing of the vertical 

and horizontal fins will be modified;

• 

Heating

 ( ): the temperature set-

point, the speed of the fans and func-

tions related to swing of the vertical 

and horizontal fins will be modified;

Pressing the 

AMB

. allows to select the operating scenario to be applied to the unit (the 

operating scenario is a specific automatic program based on the type of environ-

ment in which the unit is installed ); each press of the key will scroll through the avail-

able modes in accordance with the following layout:

WARNING the scenarios can only be set via the machine's on board panel; only the 

energy saving (SAVE) or the default (COMMON) scenario can be set via remote con-

trol

Pressing the 

ARROW 

key permits to perform different functions, de-

pending on the context in which they are pressed:

• Increase or decrease the temperature set-point, in the modes that 

permit;

• Allows to scroll through the available functions (after pressing the 

Function key) on the unit;

• By simultaneously pressing both arrow keys and holding them down 

for at least 3 seconds, activates the key lock (indicated by the initials 

LC on the display of the indoor unit);

• Performing one of the available test modes;

WARNING after installing the unit, a heating or cooling test can be run 

for the first start-up; to perform such tests it is necessary to:

HEATING TEST MODE:

When turning on the unit, press the key ( ) twice within 20s; the heat-

ing test will last for 5 minutes (unless interrupted before hand via the 

OFF button on the machine's panel or on the remote control) and in the 

event errors occur during the test, the relative code will appear on the 

display of the indoor unit.

COOLING TEST MODE:

When turning on the unit, press the key ( ) twice within 20s; the heat-

ing test will last for 5 minutes (unless interrupted before hand via the 

OFF button on the machine's panel or on the remote control) and in the 

event errors occur during the test, the relative code will appear on the 

display of the indoor unit.

Содержание MVA

Страница 1: ...USE AND INSTALLATION MANUAL EN MVA 1000V 1400V 5389861_02 ...

Страница 2: ...ime and without the obligation for any notice thereof Thank you once again AERMEC S p A 1 WARNINGS 3 2 MATERIALS PROVIDED WITH THE UNIT 4 3 TECHNICAL DATA 5 4 ACCESSORIES 6 5 RECEIPT OF PRODUCT 7 5 1 PRODUCT IDENTIFICATION 7 6 TECHNICAL SPACES MM IN 7 6 1 DIMENSION OF THE INDOOR UNIT 7 6 2 LABEL PACKAGING 7 7 MECHANICAL INSTALLATION 8 8 COOLING CONNECTIONS 10 8 1 FITTING THE REFRIGERANT LINES 10 8...

Страница 3: ...rectly Before operating the air conditioner ensure that the electric cables con densate discharge pipes and cool ing connections have been correctly installed to avoid the risk of water leaks refrigerant gas leaks and elec tric shocks The air conditioner must be cor rectly earthed Do not connect the earth cable to the gas or water pipes to the lightning conductor or to the earth cable of the tel e...

Страница 4: ... smell turn off the air conditioner and discon nect it from the power supply using the isolator switch If the anomaly persists the unit could be damaged and could cause electric shocks or fires Contact your local After Sales Service Do not use sprays or insecticides on the unit risk of fire Air the room We recommend that the room where the air conditioner is installed is periodically aired es peci...

Страница 5: ...idifying volume l h Fan type Type Centrifugal Air flow indoor units Min m3 h 1400 1400 Med 1600 1600 Max 1850 1850 Sound pressure indoor units Min db A 46 46 Med 48 48 Max 50 50 Sound power indoor units Min db A 56 56 Med 58 58 Max 60 60 Connection pipe Liquid mm inch 9 52 9 52 Connection pipe GAS 15 9 15 9 Diameter condensate drain mm 31 31 Dimensions indorr units Height mm 1870 1870 Width 580 58...

Страница 6: ...ebugging procedures on the MVA range WRC wired Soft Touch panel this Ac cessory is supplied as standard with all Indoor Units it is also possible to purchase an additional WRC Wired Panel to control a single Indoor Unit or set of Indoor Units up to a maxi mum of 16 with the same settings from two separate locations WRC1 Simplified control wired pan el for Indoor Unit with built in External Contact...

Страница 7: ...n data and product specification example of label feature MVA 1000V 1400V mm A 1870 B 580 C 400 Weight kg 54 57 A B C 6 TECHNICAL SPACES MM IN 300 11 50 1 100 3 200 7 100 3 6 1 DIMENSION OF THE INDOOR UNIT 6 2 LABEL PACKAGING Positioned on the packaging it shows the product identifi cation data example of label packaging ...

Страница 8: ... as shown in the figure 5 Execute as indicated in the spe cific chapters the refrigerant and water connections 6 Route the refrigerant lines through the opening and screw in the dam per with the screw as shown in the related image 7 After making all electrical connec tions cooling and hydraulic fit the filter and the front panel simply re versing the steps taken to dismantle them 8 Fix the anchori...

Страница 9: ...ough the damper secure it in the desired position by tightening the screw 1 2 Proceedings to determine the anti tip device 1 Unscrew the screw on top of the unit 2 Place the tilt lock and secure it with the screw removed in the prece ding paragraph 3 attach the security cable to a hook not supplied attached properly to the wall 1 2 3 ...

Страница 10: ...s from the indoor unit until they are at jun ctions provided on refrigerant lines of the system 2 Prepare the lines on the side of the indoor units as follows Accurately measure the inner and outer tube Use a tube slightly longer than the measurement date Cut the copper tube to length with the cutter and smooth the ends using a pipe reamer Fig A Insulate pipes and fit conical nuts before running t...

Страница 11: ...tape to bind together the pipes from the bottom of the outdoor unit to the upper end of the pipe where it enters the wall When using insulat ing tape the final wrap should half cover the first wrap of tape Indoor unit Connection Pipe GAS mm inch LIQUID mm inch MVA1000V 15 9 5 8 9 52 3 8 MVA1400V 15 9 5 8 9 52 3 8 8 2 CONDENSATE DISCHARGE The condensate discharge hose can be positioned on the left ...

Страница 12: ...pply lines must use terminals with wire end ferrules or single wire terminals Stranded cables without wire end ferrules could cause electrical bridges Do not leave any cables in contact with the cooling pipe the compressor or moving parts such as the fans Do not modify the circuits inside the air con ditioner The manufacturer cannot be held responsible for any damage or malfunction due to incorrec...

Страница 13: ... 2 Use a stripping tool to remove the insulation layer 10mm long from the end of the cable 3 Using pliers for crimping applying a terminal com patible with the size of the terminal board at the end of each node of the cable 4 Remove the screw on the terminal block 5 Insert the cable end into the terminal and secure the screw WARNING all the cables related to serial links should be kept separate fr...

Страница 14: ...st end with a termination resistor which will be connected to the final unit of the system such resistance is supplied with the outdoor unit Connection type Max lenght m Note Section minimum recommended Wired pannel connection 250 NOTE For more information about length limitations and about the kinds of installation cable connection refer to the manual for the panel flush The cable should be a two...

Страница 15: ...accessor y C AP C N 35 G N L1 L2 I nduct ance XT3 BK R D 1 X1 PE XT2 H 1 XT2 H 2 BN O G For the need of installation refer necessarily to the wiring diagram supplied with the unit The circuit dia gram along with the manuals must be carefully preserved and made available for future work on the unit NOTE IN CONNECTING THE WRC WIRE PANEL The unit has a display on the machine from which it is possible...

Страница 16: ...ontrol panels accessories H2 Wired controller Panels flush command WRC Optional accessory not supplied RT2 Outlet pipe Temp Sensor indoor unit exchanger temperature sensor output RT4 Inlet pipe temp sensor Temperature probe input indoor unit exchanger RT1 Room Temp Sensor Room temperature sensor EKR Electronic thermostatic valve WH White YEGN yellow green RD red VT Violet GN green BN Brown BU blue...

Страница 17: ...s successful the display will show the acronym of uni ty internal UC indicating that the unit has been set as the master 11 MAINTENANCE 11 1 ORDINARY MAINTENANCE Disconnect the power supply before cleaning the unit Disconnect the power supply when the air conditioner is off Do not pour water directly to the unit may cause an electrical shock Clean the cabinet with a soft dry cloth or a cloth sligh...

Страница 18: ...nce Is the thermal insulation sufficient It could cause condensate and dripping water Does the unit correctly drain the con densate water It could cause condensate and dripping water Does the power supply voltage correspond to the one indicated on the label Electrical operating fault or damage to components which could be blown Have the cables and pipes been con nected correctly and safely Electri...

Страница 19: ...FU Error temperature sensor on the compressor 1 Fb Error temperature sensor on the compressor 2 J1 Over current protection on the compressor 1 J2 Over current protection on the compressor 2 J3 Over current protection on the compressor 3 J4 Over current protection on the compressor 4 J5 Over current protection on the compressor 5 J6 Over current protection on the compressor 6 J7 Protection 4 way va...

Страница 20: ...p switches for selecting the size dL Sensor fault ambient air dE Error carbon dioxide probe db It indicates an active debug mode A0 Unit waiting because debug mode A1 Will implement a procedure to control the operating parameters of the compressor A2 Notice quantity insufficient refrigerant gas A3 Currently undergoing a defrost cycle A5 Unit in test mode A8 Ongoing mode pump down Code Alarm descri...

Страница 21: ... on the machine 1 2 3 4 5 6 7 Alarm Function of the button 1 Selection of the various fan speeds 2 This button allows to scroll through the various available functions 3 Allows to increase a value or to activate a function selected with the Function key 4 Allows to decrease a value or to deactivate a function selected with the Function key 5 Allows to set an automatic program based on the type of ...

Страница 22: ...perature is currently displayed 14 Indicates 15 Indicates that the fans are set to AUTO speed 16 Indicates that the fans are set to MINIMUM speed 17 Indicates that the fans are set to MEDIUM speed 18 Indicates that the fans are set to MAXIMUM speed 19 Indicates that the fans are set to TURBO speed 20 Indicates that the cooling mode is currently active 21 Indicates that the heating mode is currentl...

Страница 23: ...e type of environ ment in which the unit is installed each press of the key will scroll through the avail able modes in accordance with the following layout WARNING the scenarios can only be set via the machine s on board panel only the energy saving SAVE or the default COMMON scenario can be set via remote con trol Pressing the ARROW key permits to perform different functions de pending on the co...

Страница 24: ...if the procedure is performed with the machine on an Off timer will be set and if carried out with the machine off an On timer will be set Pressing the key will increase the number of hours set for the timer while the key will decrease the number of hours set for the timer to confirm the value to be assigned just press the Function key passing to the next function or wait for 5 seconds without pre...

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...erve le droit de modifier à tous moments les données considérées nécessaires à l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to introduce at any time whatever modifications deemed necessary to the improvement of the product Im Sinne des technischen Fortsschrittes behält sich Aermec S p A vor in der Produktion Änderungen und Verbess...

Отзывы: