11
No gap
•
When connecting the indoor unit to the connection pipe,
do not force the couplings on the indoor unit, as this
could cause cracks in the capillary pipes and other pipes
on the indoor unit, causing them to leak.
•
The connection pipe must be supported by a suitable
bracket. The unit should not bear the weight of the pipe.
•
To avoid leaks and the formation of condensate on the
connection pipes, these must be covered in thermal insu-
lation material bound with adhesive tape and insulated
from the air.
•
The connection joint with the indoor unit must be wrapped
in thermal insulation. There must be no gaps between the
pipe connection and the wall of the indoor unit.
•
After wrapping the pipes in protective material, they
should never be bent at an acute angle as this could
crack or break them.
•
Use adhesive tape to cover the pipes:
−
Use adhesive tape to bind together the connection pipes
and the cables. To prevent condensate flowing out of the
discharge pipe, separate the discharge pipe from the
connection pipe and cables.
−
Use thermal insulating tape to bind together the pipes
from the bottom of the outdoor unit to the upper end
of the pipe where it enters the wall. When using insulat-
ing tape, the final wrap should half cover the first wrap
of tape.
Indoor unit
Connection Pipe
GAS
mm(inch)
LIQUID
mm(inch)
MVA1000V
15,9(5/8”)
9,52(3/8”)
MVA1400V
15,9(5/8”)
9,52(3/8”)
8.2.
CONDENSATE DISCHARGE
•
The condensate discharge hose can be
positioned on the left or right (removing
the relevant knockout from the casing) or
to the rear as previously indicated.
•
The diameter of the condensate dis-
charge hose must be the same as - or
greater than - the diameter of the con-
nection pipe.
•
Seal the connections and wrap with insu-
lating material to prevent the formation of
condensate on the external surfaces of
the pipe
•
Keep the condensate discharge hose
short and tilt it downwards with a gradient
of at least 1:100.
•
Do not bend the condensate discharge
hose.
•
After connecting the hose, check that the
condensate water flows freely
•
To check the drainage, pour water into
the condensate discharge tray.
•
Check that the condensate water drains
correctly. The connection of the conden-
sate discharge hose must be leak-free
Gas pipe
External sheath
Condensate discharge pipe
Insulation
Liquid pipe
Electrical cables
Insulation